Establishing the Temporary Occupancy Time 
(ToccTime) 

The temporary occupancy time is the length of time 
the occupied mode setpoints are used when the 
override function is enabled (the override function can 
be enabled from the Main User Menu or from one of 
the digital inputs) or a temporary setpoint is entered. 
The range is adjustable from 0 to 12 hours. 

To change the temporary occupancy time while in the 
Installer Configuration Menu: 

1.  Answer NO to all prompts until the temporary 

occupancy time prompt appears in the display. 
Press YES to enter the temporary occupancy time 
menu. 

2.  Use the UP/DOWN arrow keys to adjust the length 

of time the temporary occupancy setpoint should 
be in effect. Press YES to store the time. 

The display now shows the room sensor calibration 
prompt. See the 

Room Air Sensor Calibration (Cal RS)

 

section for instructions. 

Room Air Sensor Calibration (Cal RS) 

An offset can be added or subtracted to the actual 
displayed room temperature as needed. The range is 

±

5.0 F

°

 (

±

2.5 C

°

), adjustable in increments of 1 F

°

 

(0.5 C

°

). 

To change the room sensor calibration/offset while in 
the Installer Configuration Menu: 

1.  Answer NO to all prompts until the room sensor 

calibration prompt appears in the display. Press 
YES to enter the room sensor calibration menu. 

2.  Use the UP/DOWN arrow keys to adjust the 

correction that should be applied to the sensor 
reading. Press YES to store the offset. 

The display now shows the outdoor air sensor 
calibration prompt. See the 

Outdoor Air Sensor 

Calibration (Cal OS)

 section for instructions. 

Outdoor Air Sensor Calibration (Cal OS) 

An offset can be added or subtracted to the actual 
displayed outdoor air temperature as needed. The 
range is 

±

5.0 F

°

 (

±

2.5 C

°

), adjustable in increments of 

1 F

°

 (0.5 C

°

). 

To change the outdoor air sensor calibration/offset 
while in the Installer Configuration Menu: 

1.  Answer NO to all prompts until the outdoor sensor 

calibration prompt appears in the display. Press 
YES to enter the outdoor sensor calibration menu. 

2.  Use the UP/DOWN arrow keys to adjust the 

correction that should be applied to the sensor 
reading. Press YES to store the offset. 

 

The display now shows the heating lockout prompt. 
See the 

Setting the Heating Lockout (H lock)

 section 

for instructions. 

Setting the Heating Lockout (H lock) 

This feature disables heating operation based on 
outdoor air temperature (requires outdoor air 
temperature sensor to be connected for the function to 
be enabled). If the outdoor air temperature is above 
the heating lockout temperature, heating operation is 
disabled. 

The heating lockout temperature parameter is 
adjustable from -15 to 120

°

F (-26 to 49

°

C) in 

increments of 5 F/C

°

To change the outdoor air temperature heating lockout 
while in the Installer Configuration Menu: 

1.  Answer NO to all prompts until the heating lockout 

prompt appears in the display. Press YES to enter 
the heating lockout menu. 

2.  Use the UP/DOWN arrow keys to adjust the 

lockout temperature. Press YES to store the value. 

The display now shows the cooling lockout prompt. 
See the 

Setting the Cooling Lockout (C lock)

 section 

for instructions. 

Setting the Cooling Lockout (C lock) 

This feature disables cooling operation based on 
outdoor air temperature (requires outdoor air 
temperature sensor to be connected for the function to 
be enabled). If the outdoor air temperature is below 
the cooling lockout temperature, cooling operation is 
disabled. 

The cooling lockout temperature parameter is 
adjustable from -40 to 95

°

F (-40 to 35

°

C) in 

increments of 5 F/C

°

To change the outdoor air temperature cooling lockout 
while in the Installer Configuration Menu: 

1.  Answer NO to all prompts until the cooling lockout 

prompt appears in the display. Press YES to enter 
the cooling lockout menu. 

2.  Use the UP/DOWN arrow keys to adjust the 

lockout temperature. Press YES to store the value. 

3.  The exit menu is displayed. Press YES to exit the 

Installer Configuration Menu or press NO to return 
to the beginning of the menu (digital input 
configuration). 

T600HCN-1 Non-Programmable Thermostat Installation Instructions    

9

 

Summary of Contents for T600HCN-1

Page 1: ...the thermostat cover see Figure 1 2 Unlock the Printed Circuit Board PCB by carefully pressing the locking tabs to the right see Figure 2 Open the thermostat s PCB to the left 3 Pull out approximatel...

Page 2: ...e the thermostat 1 Strip each wire 1 4 in 6 35 mm and connect to the appropriate terminal according to the wiring diagram see Figure 5 2 Gently push excess wire back into wall plug the wall hole with...

Page 3: ...24 VAC from equipment transformer 24 VAC common from equipment transformer 24 VAC for heating stage Configurable digital input Configurable digital input Remote room sensor Sensor common Outdoor air s...

Page 4: ...uring normal thermostat operation The menu continually scrolls through the following parameters see Figure 6 Room Temperature System Mode Schedule Status Occupied Unoccupied see Note Outdoor Temperatu...

Page 5: ...Maximum Cooling Cycles per Hour Cool cph Sets the Minimum Heating Cooling Deadband Default 2 0 F 1 1 C See Setting the Heating Cooling Deadband Deadband Determines how the Fan Activates in Response to...

Page 6: ...nfigure Digital Input 2 or NO to advance to the keypad lockout setup prompt 4 Use the UP DOWN arrow keys to locate the desired function for the Digital Input 2 Press YES to select the desired function...

Page 7: ...ows the minimum cooling setpoint prompt See the Setting the Minimum Cooling Setpoint Cool min section for instructions Setting the Minimum Cooling Setpoint Cool min The minimum cooling setpoint establ...

Page 8: ...hes the minimum difference between the heating and cooling setpoints The range is adjustable from 2 to 4 F 1 to 2 C To change the minimum deadband between the heating and cooling setpoints while in th...

Page 9: ...the display Press YES to enter the outdoor sensor calibration menu 2 Use the UP DOWN arrow keys to adjust the correction that should be applied to the sensor reading Press YES to store the offset The...

Page 10: ...de schedule prompt only appears when the thermostat is in the unoccupied state This menu selection gives the user the option of overriding the unoccupied setpoints with the occupied setpoints for the...

Page 11: ...et prompt appears in the display it may be the first prompt Press YES to enter temperature setting menu Press YES to change occupied cooling setpoint Press NO to advance to occupied heating setpoint m...

Page 12: ...rn to the Status Display Menu or NO to return to the fan mode selection menu Setting Permanent Hold Note Displayed only if Digital Input DI1 or DI2 is configured for remote NSB This menu is used to se...

Page 13: ...d to comply with the limits for a Class A digital device and verified to Class B pursuant to Part 15 of FCC Rules These limits are designed to provide reasonable protection against harmful interferenc...

Reviews: