Configuring the Digital Inputs (DI1 and DI2)
Press the configuration menu access key. The first
prompt is to program Digital Inputs DI1 and DI2.
The digital inputs display an alarm condition when the
input is closed. An alarm message is included on the
scrolling Status Display Menu and when the message
is displayed, the backlight momentarily lights up.
Each digital input can be programmed in one of five
conditions.
•
None
– No function is associated with the input.
•
Service
– A Service alarm is displayed.
•
Filter
– A Filter alarm is displayed.
•
RemNSB
– Remote night setback timer clock
input. The scheduling is set per the digital input
when this option is selected.
−
Open Contact = Occupied setpoints
−
Closed Contacts = Unoccupied setpoints
•
RemOVR
– Remote override contact. This
disables all override menu functions of the
thermostat. The override function is controlled
manually by a remote, momentarily closed
contact. When configured in this mode, the input
operates in a toggle mode. With this function
enabled, it is now possible to toggle between
unoccupied and occupied setpoints for the amount
of time set by the temporary occupancy time
parameter.
When override is enabled through the digital inputs, an
Override
message appears in the Status Display
Menu.
To configure the digital inputs while in the Installer
Configuration Menu:
1. The first prompt is to configure the digital inputs.
Press YES to configure Digital Input 1 or NO to
advance to Digital Input 2.
2. Use the UP/DOWN arrow keys to locate the
desired function for the Digital Input 1. Press YES
to select the desired function.
3. Press YES to configure Digital Input 2 or NO to
advance to the keypad lockout setup prompt.
4. Use the UP/DOWN arrow keys to locate the
desired function for the Digital Input 2. Press YES
to select the desired function.
The display now shows the keypad lockout setup
prompt. See the
Enabling Keypad Lockout (Lockout)
section for instructions.
Enabling Keypad Lockout (Lockout)
The T600HCN-1 has three levels of keypad lockout.
The levels and degree of lockout are shown in Table 2.
To set the keypad lockout level while in the Installer
Configuration Menu:
1. Answer NO to all prompts until the keypad lockout
setup prompt appears in the display. Press YES to
enter the keypad lockout menu.
2. Use the UP/DOWN arrow keys to locate the
desired lockout level. Press YES to select the
level.
The display now shows the power delay setup prompt.
See the
Setting the Power-up Delay (Pwr del)
section
for instructions.
Table 2: Keypad Lockout Levels
Level 0
Level 1
Level 2
*Resume to
Scheduling
Yes access
Yes access
No access
Temperature
Setpoints
Yes access
No access
No access
System
Mode Setting
Yes access
Yes access
No access
Fan Mode
Setting
Yes access
Yes access
No access
*Permanent
Hold
Yes access
Yes access
No access
* Displayed only if digital input DI1 or DI2 is configured
for remote NSB.
Setting the Power-up Delay (Pwr del)
On initial power up of the T600HCN-1 (or each time
power is removed and reapplied), there is a delay
before any operation is authorized (fan, cooling, and
heating). The delay time is adjustable between
10 and 120 seconds. You can also use this parameter
to sequence the startup of multiple units in one
location.
Note:
When adjusting the time with the UP/DOWN
arrow keys, holding the keys down changes the time
by 10-second intervals.