Table 1: Installer Configuration Menu
Remove the cover and press the
CONFIG key from the Status Display
Menu to enter the Installer
Configuration Menu.
Configures Digital Input 1
Default: No Function
(None)
See
Configuring the Digital Inputs
(DI1 and DI2).
Configures Digital Input 2
Default: No Function
(None)
See
Configuring the Digital Inputs
(DI1 and DI2).
Sets Keypad Lockout Level
Default: No Lockout
(0)
See
Enabling Keypad Lockout
(Lockout).
Sets Power-up Delay
Default: Ten Seconds
(10.0 sec)
See
Setting the Power-up Delay
(Pwr del).
Enables/Disables Frost Protection
Default: Disabled
(Off)
See
Enabling Frost Protection
(Frost pr).
Sets the Maximum Heating Setpoint
Default:
90.0
°
F (32.0
°
C)
See
Setting the Maximum Heating
Setpoint (Heat max).
Sets the Minimum Cooling Setpoint
Default:
54.0
°
F (12.0
°
C)
See
Setting the Minimum Cooling
Setpoint (Cool min).
Sets the Anti-Short Cycle Timer
Default: Two Minutes
(2.0 min)
See
Setting the Anti-Short Cycle Timer
(Anticycl).
Sets the Maximum Heating Cycles per
Hour
Default: Four
(4.0)
See
Setting the Maximum Heating
Cycles per Hour (Heat cph).
Sets the Maximum Cooling Cycles per
Hour
Default: Four
(4.0)
See
Setting the Maximum Cooling
Cycles per Hour (Cool cph).
Sets the Minimum Heating/Cooling
Deadband
Default:
2.0
°
F (1.1
°
C)
See
Setting the Heating/Cooling
Deadband (Deadband).
Determines how the Fan Activates in
Response to a call for Heat
Default: Thermostat Controls Fan
(On)
See
Setting the Fan Control
(Fan cont).
Delays Fan Termination at Cycle’s End
for 60 Seconds
Default: No Delay
(Off)
See
Setting the Fan Delay (Fan del).
Sets the Duration for Temporary
Occupancy Time
Default: Three Hours
(3.0 hrs)
See
Establishing the Temporary
Occupancy Time (ToccTime).
Room Air Sensor Calibration (Offset)
Default:
0.0
°
F (0.0
°
C)
See
Room Air Sensor Calibration
(Cal RS).
Outdoor Air Sensor Calibration (Offset)
Default:
0.0
°
F (0.0
°
C)
See
Outdoor Air Sensor Calibration
(Cal OS).
Disables Heating Operation based on
Outdoor Air Temperature
Default:
120
°
F (49
°
C)
See
Setting the Heating Lockout
(H lock).
Disables Cooling Operation based on
Outdoor Air Temperature
Default:
-40
°
F (-40
°
C)
See
Setting the Cooling Lockout
(C lock).
RoomTemp
75.0
°
F
Cool cph
set? Y/N
DI1
set? Y/N
Deadband
set? Y/N
DI2
set? Y/N
Fan cont
set? Y/N
Lockout
set? Y/N
Fan del
set? Y/N
Pwr del
set? Y/N
ToccTime
set? Y/N
Frost pr
set? Y/N
Cal RS
set? Y/N
Heat max
set? Y/N
Cal OS
set? Y/N
H lock
set? Y/N
Cool min
set? Y/N
C lock
set? Y/N
Anticycl
set? Y/N
Heat cph
set? Y/N
T600HCN-1 Non-Programmable Thermostat Installation Instructions