Table 1: Installer Configuration Menu 

 

Remove the cover and press the 

CONFIG key from the Status Display 

Menu to enter the Installer 
Configuration Menu. 

 

Configures Digital Input 1 
Default: No Function 

(None) 

See 

Configuring the Digital Inputs 

(DI1 and DI2).

 

 

Configures Digital Input 2 
Default: No Function 

(None) 

See 

Configuring the Digital Inputs 

(DI1 and DI2).

 

 

Sets Keypad Lockout Level 
Default: No Lockout 

(0) 

See 

Enabling Keypad Lockout 

(Lockout).

 

 

Sets Power-up Delay 
Default: Ten Seconds 

(10.0 sec) 

See 

Setting the Power-up Delay 

(Pwr del).

 

 

Enables/Disables Frost Protection 
Default: Disabled 

(Off) 

See 

Enabling Frost Protection 

(Frost pr).

 

 

Sets the Maximum Heating Setpoint 
Default: 

90.0

°

F (32.0

°

C)

 

See 

Setting the Maximum Heating 

Setpoint (Heat max).

 

 

Sets the Minimum Cooling Setpoint 
Default: 

54.0

°

F (12.0

°

C)

 

See 

Setting the Minimum Cooling 

Setpoint (Cool min).

 

 

Sets the Anti-Short Cycle Timer 
Default: Two Minutes 

(2.0 min)

 

See 

Setting the Anti-Short Cycle Timer 

(Anticycl).

 

 

Sets the Maximum Heating Cycles per 
Hour 
Default: Four 

(4.0) 

See 

Setting the Maximum Heating 

Cycles per Hour (Heat cph).

 

 

Sets the Maximum Cooling Cycles per 
Hour 
Default: Four 

(4.0) 

See 

Setting the Maximum Cooling 

Cycles per Hour (Cool cph).

 

 

Sets the Minimum Heating/Cooling 
Deadband 
Default: 

2.0

°

F (1.1

°

C) 

See 

Setting the Heating/Cooling 

Deadband (Deadband).

 

 

Determines how the Fan Activates in 
Response to a call for Heat 
Default: Thermostat Controls Fan 

(On)

See 

Setting the Fan Control 

(Fan cont).

 

 

Delays Fan Termination at Cycle’s End 
for 60 Seconds 
Default: No Delay 

(Off) 

See 

Setting the Fan Delay (Fan del).

 

 

Sets the Duration for Temporary 
Occupancy Time 
Default: Three Hours 

(3.0 hrs)

 

See 

Establishing the Temporary 

Occupancy Time (ToccTime).

 

 

Room Air Sensor Calibration (Offset) 
Default: 

0.0

°

F (0.0

°

C) 

See 

Room Air Sensor Calibration 

(Cal RS).

 

 

Outdoor Air Sensor Calibration (Offset)
Default: 

0.0

°

F (0.0

°

C) 

See 

Outdoor Air Sensor Calibration 

(Cal OS).

 

 

Disables Heating Operation based on 
Outdoor Air Temperature 
Default: 

120

°

F (49

°

C) 

See 

Setting the Heating Lockout 

(H lock). 

 

Disables Cooling Operation based on 
Outdoor Air Temperature 
Default: 

-40

°

F (-40

°

C) 

See 

Setting the Cooling Lockout 

(C lock).

 

RoomTemp 
75.0

°

F

 

Cool cph
set? Y/N 

DI1 
set? Y/N

 

Deadband
set? Y/N 

DI2 
set? Y/N 

Fan cont
set? Y/N 

Lockout 
set? Y/N 

Fan del
set? Y/N 

Pwr del 
set? Y/N 

ToccTime
set? Y/N 

Frost pr 
set? Y/N 

Cal RS
set? Y/N 

Heat max 
set? Y/N 

Cal OS
set? Y/N 

H lock
set? Y/N 

Cool min 
set? Y/N 

C lock
set? Y/N 

Anticycl 
set? Y/N 

 

Heat cph 
set? Y/N 

 

T600HCN-1 Non-Programmable Thermostat Installation Instructions    

5

 

Summary of Contents for T600HCN-1

Page 1: ...the thermostat cover see Figure 1 2 Unlock the Printed Circuit Board PCB by carefully pressing the locking tabs to the right see Figure 2 Open the thermostat s PCB to the left 3 Pull out approximatel...

Page 2: ...e the thermostat 1 Strip each wire 1 4 in 6 35 mm and connect to the appropriate terminal according to the wiring diagram see Figure 5 2 Gently push excess wire back into wall plug the wall hole with...

Page 3: ...24 VAC from equipment transformer 24 VAC common from equipment transformer 24 VAC for heating stage Configurable digital input Configurable digital input Remote room sensor Sensor common Outdoor air s...

Page 4: ...uring normal thermostat operation The menu continually scrolls through the following parameters see Figure 6 Room Temperature System Mode Schedule Status Occupied Unoccupied see Note Outdoor Temperatu...

Page 5: ...Maximum Cooling Cycles per Hour Cool cph Sets the Minimum Heating Cooling Deadband Default 2 0 F 1 1 C See Setting the Heating Cooling Deadband Deadband Determines how the Fan Activates in Response to...

Page 6: ...nfigure Digital Input 2 or NO to advance to the keypad lockout setup prompt 4 Use the UP DOWN arrow keys to locate the desired function for the Digital Input 2 Press YES to select the desired function...

Page 7: ...ows the minimum cooling setpoint prompt See the Setting the Minimum Cooling Setpoint Cool min section for instructions Setting the Minimum Cooling Setpoint Cool min The minimum cooling setpoint establ...

Page 8: ...hes the minimum difference between the heating and cooling setpoints The range is adjustable from 2 to 4 F 1 to 2 C To change the minimum deadband between the heating and cooling setpoints while in th...

Page 9: ...the display Press YES to enter the outdoor sensor calibration menu 2 Use the UP DOWN arrow keys to adjust the correction that should be applied to the sensor reading Press YES to store the offset The...

Page 10: ...de schedule prompt only appears when the thermostat is in the unoccupied state This menu selection gives the user the option of overriding the unoccupied setpoints with the occupied setpoints for the...

Page 11: ...et prompt appears in the display it may be the first prompt Press YES to enter temperature setting menu Press YES to change occupied cooling setpoint Press NO to advance to occupied heating setpoint m...

Page 12: ...rn to the Status Display Menu or NO to return to the fan mode selection menu Setting Permanent Hold Note Displayed only if Digital Input DI1 or DI2 is configured for remote NSB This menu is used to se...

Page 13: ...d to comply with the limits for a Class A digital device and verified to Class B pursuant to Part 15 of FCC Rules These limits are designed to provide reasonable protection against harmful interferenc...

Reviews: