background image

 

 

To set the delay time while in the Installer 
Configuration Menu: 
1.  Answer NO to all prompts until the power delay 

setup prompt appears in the display. Press YES to 
enter the power delay setup menu. 

2.  Use the UP/DOWN arrow keys to adjust the 

power up delay setting. Press YES to store the 
setting. 

The display now shows the frost protection setup 
prompt. See the 

Enabling Frost Protection (Frost pr)

 

section for setup instructions. 

Enabling Frost Protection (Frost pr) 

Frost protection establishes a minimum heating 
setpoint of 42

°

F (5.5

°

C) to prevent freezing in the zone 

controlled by the thermostat. If enabled, frost 
protection is activated even if the thermostat is set to 
the Off System Mode. If frost protection is active, it is 
displayed as an alarm (

Frost on

 with the backlight lit) 

on the Status Display Menu. 

To enable frost protection while in the Installer 
Configuration Menu: 

1.  Answer NO to all prompts until the frost protection 

setup prompt appears in the display. Press YES to 
enter the frost protection menu. 

2.  Use the UP/DOWN arrow keys to select 

off

 or 

on

Press YES to store the selection. 

The display now shows the maximum heating setpoint 
prompt. See the 

Setting the Maximum Heating 

Setpoint (Heat max)

 section for instructions. 

Setting the Maximum Heating Setpoint (Heat max) 

The maximum heating setpoint establishes the 
maximum temperature in the heating setpoint range 
that can be adjusted from the Main User Menu. The 
parameter is adjustable from 40 to 90

°

F (4.5 to 32

°

C). 

Note: 

When adjusting the temperature, holding the 

keys down changes the temperature by 5 F/C

°

 

increments. 

To set the maximum heating setpoint while in the 
Installer Configuration Menu: 

1.  Answer NO to all prompts until the maximum 

heating setpoint prompt appears in the display. 
Press YES to enter the maximum heating setpoint 
menu. 

2.  Use the UP/DOWN arrow keys to adjust the 

maximum heating setpoint temperature. Press 
YES to store the value. 

The display now shows the minimum cooling setpoint 
prompt. See the 

Setting the Minimum Cooling Setpoint 

(Cool min)

 section for instructions. 

Setting the Minimum Cooling Setpoint (Cool min) 

The minimum cooling setpoint establishes the 
minimum temperature in the cooling setpoint range 
that can be adjusted from the Main User Menu. The 
parameter is adjustable from 54 to 100

°

(12 to 37.5

°

C). 

Note: 

When adjusting the temperature, holding the 

keys down changes the temperature by 5 F/C

°

 

increments. 

To set the minimum cooling setpoint while in the 
Installer Configuration Menu: 

1.  Answer NO to all prompts until the minimum 

cooling setpoint prompt appears in the display. 
Press YES to enter the minimum cooling setpoint 
menu. 

2.  Use the UP/DOWN arrow keys to adjust the 

minimum cooling setpoint temperature. Press YES 
to store the value. 

The display now shows the anti-short cycle timer 
prompt. See the 

Setting the Anti-Short Cycle Timer 

(Anticycl)

 section for instructions. 

Setting the Anti-Short Cycle Timer (Anticycl) 

The anti-short cycle timer establishes the minimum 
on/off times for the cooling and heating stages. The 
timer is adjustable from 0 to 5 minutes in 1-minute 
increments. Set the anti-short cycling to 0 for 
equipment that possesses its own anti-short cycling 
timer. 

!

  CAUTION:  Risk of Property Damage. 

Do not set the T600HCN-1 anti-short cycling timer to 
0 minutes if the controlled equipment is not 
protected by its own internal anti-short cycling timer. 
Setting the T600HCN-1 anti-short cycling timer to 
0 minutes can damage controlled equipment that 
does not have an anti-short cycling timer. 

 

To set the anti-short cycle time while in the Installer 
Configuration Menu: 

1.  Answer NO to all prompts until the anti-short cycle 

timer prompt appears in the display. Press YES to 
enter the anti-short cycle timer menu. 

2.  Use the UP/DOWN arrow keys to adjust the 

minimum on/off times for the heating and cooling 
stages. Press YES to store the value. 

The display now shows the heating cycles per hour 
setup prompt. See the 

Setting the Maximum Heating 

Cycles per Hour (Heat cph)

 section for instructions. 

T600HCN-1 Non-Programmable Thermostat Installation Instructions    

7

 

Summary of Contents for T600HCN-1

Page 1: ...the thermostat cover see Figure 1 2 Unlock the Printed Circuit Board PCB by carefully pressing the locking tabs to the right see Figure 2 Open the thermostat s PCB to the left 3 Pull out approximatel...

Page 2: ...e the thermostat 1 Strip each wire 1 4 in 6 35 mm and connect to the appropriate terminal according to the wiring diagram see Figure 5 2 Gently push excess wire back into wall plug the wall hole with...

Page 3: ...24 VAC from equipment transformer 24 VAC common from equipment transformer 24 VAC for heating stage Configurable digital input Configurable digital input Remote room sensor Sensor common Outdoor air s...

Page 4: ...uring normal thermostat operation The menu continually scrolls through the following parameters see Figure 6 Room Temperature System Mode Schedule Status Occupied Unoccupied see Note Outdoor Temperatu...

Page 5: ...Maximum Cooling Cycles per Hour Cool cph Sets the Minimum Heating Cooling Deadband Default 2 0 F 1 1 C See Setting the Heating Cooling Deadband Deadband Determines how the Fan Activates in Response to...

Page 6: ...nfigure Digital Input 2 or NO to advance to the keypad lockout setup prompt 4 Use the UP DOWN arrow keys to locate the desired function for the Digital Input 2 Press YES to select the desired function...

Page 7: ...ows the minimum cooling setpoint prompt See the Setting the Minimum Cooling Setpoint Cool min section for instructions Setting the Minimum Cooling Setpoint Cool min The minimum cooling setpoint establ...

Page 8: ...hes the minimum difference between the heating and cooling setpoints The range is adjustable from 2 to 4 F 1 to 2 C To change the minimum deadband between the heating and cooling setpoints while in th...

Page 9: ...the display Press YES to enter the outdoor sensor calibration menu 2 Use the UP DOWN arrow keys to adjust the correction that should be applied to the sensor reading Press YES to store the offset The...

Page 10: ...de schedule prompt only appears when the thermostat is in the unoccupied state This menu selection gives the user the option of overriding the unoccupied setpoints with the occupied setpoints for the...

Page 11: ...et prompt appears in the display it may be the first prompt Press YES to enter temperature setting menu Press YES to change occupied cooling setpoint Press NO to advance to occupied heating setpoint m...

Page 12: ...rn to the Status Display Menu or NO to return to the fan mode selection menu Setting Permanent Hold Note Displayed only if Digital Input DI1 or DI2 is configured for remote NSB This menu is used to se...

Page 13: ...d to comply with the limits for a Class A digital device and verified to Class B pursuant to Part 15 of FCC Rules These limits are designed to provide reasonable protection against harmful interferenc...

Reviews: