System 350

 

A350P Electronic Proportional Plus Integral Temperature Control Product/Technical Bulletin 

3.  Check the A350P control for proper operation. 

Note: 

Perform Steps 1 and 2 first. 

a.  Reconnect the sensor to the control and 

re-apply power. 

b.  Turn the throttling range and the minimum 

output to minimum by turning both 
potentiometers counterclockwise. 

c.  Switch off the integration. 

d.  Select the RA mode. 

e.  Connect the DVM (+) lead to the A350P 

control’s Terminal SN and the (-) lead to 
Terminal C. 

 

If the sensor voltage is less than 1.8 VDC on 

 

model A350PS-1C or less than 2.3 VDC on 

 

model A350PS-2C, go to Step 3g. 

f. 

If the voltage is greater than 1.8 VDC on 
model A350PS 1C or greater than 2.3 VDC on 
model A350PS-2C, adjust the setpoint to 
120°F (49°C) on model A350PS-1C or 240°F 
(116°C) on model A350PS-2C. 

 

The output Terminal V should be less than 
0.1 VDC, and all LEDs in the bar graph display 
should be off. If not, replace the A350P. 

1.  Adjust the minimum output to the 

maximum by turning the potentiometer 
CW. As the potentiometer is turned CW, 
the LEDs in the bar graph should turn on 
from left to right until the fifth or sixth bar is 
on. If not, replace the A350P control. 

2.  Adjust the minimum output to zero again, 

and select the DA mode. 

3.  If the right most LED in the bar graph is on 

(Terminal V = 10 VDC, Terminal I = 20 mA), 
go to Step 3h. If the LED is not on, replace 
the A350P. 

g.  If the sensor voltage is above 1.1 VDC 

on A350PS-1C or above 1.6 VDC on 
A350PS-2C, adjust the setpoint to match the 
actual temperature (Ts). The output Terminal 
V should be less than 0.1 VDC, and all LEDs 
in the bar graph should be off. 

Note: 

Some tolerance error is present between the 
setpoint scale and the setpoint knob pointer. 
Refer to the 

Adjustments

 section. 

1.  Make sure the A350P control is in RA 

mode. 

2.  Increase the setpoint in increments of 2F° 

(1C°). 

3.  As the setpoint is increased, the control’s 

Terminal V output voltage should go from 
0 to 10 VDC, the Terminal I output current 
should go from 0 to 20 mA, and the LEDs 
should turn on, one at a time from left to 
right. 

4.  If the LEDs do not turn on and if the 

outputs of terminals V and I do not change 
as described above, replace the control. 

h.  Readjust the A350P control to the desired 

control settings. 

R

epairs and Replacement 

Do not make field repairs or perform calibration. 
A99B Temperature Sensors and replacement controls 
are available through the nearest Johnson Controls 
representative. (See Tables 5 and 6 for ordering 
information.) 

Summary of Contents for System 350T A350P

Page 1: ...dules to be purchased and installed as needed Plug Together Connectors and 35 mm DIN Rail Mounting Eliminates wiring between modules which reduces installation costs Two Models Cover a Wide Setpoint Range of 30 to 250 F 35 to 121 C Reduces inventory by encompassing temperature ranges required to support the majority of Heating Ventilation Air Conditioning and Refrigeration HVAC R applications Mini...

Page 2: ...unted 10 segment Light Emitting Diode LED bar graph indicates percentage of output Features include adjustable setpoint adjustable minimum output adjustable throttling range proportional band selectable integration time constant selectable Reverse Acting RA or Direct Acting DA mode of operation IMPORTANT All System 350 controls are designed for use only as operating controls Where an operating con...

Page 3: ... at any time Note Before setting the minimum output potentiometer verify that the control reads zero output that is no LEDs are lit Throttling Range Proportional Band The throttling range is the range over which a control is active Throttling range for the A350P control can be adjusted from 2 to 30F 1 to 17C Make the adjustment at the throttling range potentiometer marked THROT RANGE see Figure 2 ...

Page 4: ...ntegrator This resets the integration error when the sensor goes just above the setpoint plus the throttling range in DA mode or just below the setpoint minus the throttling range in RA mode This allows the process to recover from an out of range condition without a large overshoot The A350P control has three field selectable integration constants and an off position The integration DIP switch sel...

Page 5: ...wed Y350R 4 2 0 External Class 2 Transformer 9 8 7 S350A On Off Stage Modules S350A On Off stage modules receive power setpoint and sensor input from the A350P control S350A stage modules perform switching functions based on the control s setpoint and sensor information as well as the offset and differential selected at the S350A stage module For more information on these modules refer to the Syst...

Page 6: ...alues The A350P Temperature Control is housed in a compact NEMA 1 plastic enclosure designed for standard 35 mm DIN rail mounting Four key slot mounting holes on the back of the control case are provided should surface mounting be required If a Y350R is used it should be mounted immediately to the right of the control Any S350 modules would follow on the right with the D350 being the last module m...

Page 7: ... different types in a single application Sensor Connection Shielded cable is not generally required for sensor wiring on runs of less than 50 feet When using shielded cable isolate and tape the shield at the sensor Connect the shield to Terminal C on the A350P control Refer to Table 3 for the maximum recommended cable lengths for particular sizes of wire Table 3 Maximum Recommended Sensor Cable Le...

Page 8: ...ghts 5 Make sure the system is stable in the proportional mode before selecting integration Refer to the Checkout Procedure section 6 Reinstall the cover and secure in place with the four captive cover screws 7 Adjust the setpoint dial to the desired setpoint If using the D350 Display Module press and hold the setpoint button on the D350 while rotating the setpoint dial Note The control s setpoint...

Page 9: ... to a value between 4 9 and 5 1 VDC replace the sensor If the DVM voltage is still below 4 9 VDC replace the A350P control 2 Check sensor for proper resistance at a given temperature The resistance across the sensor changes with the temperature of the sensor a Disconnect power from the A350P control b Disconnect the sensor from the control and measure the resistance across sensor leads c When meas...

Page 10: ...is on If not replace the A350P control 2 Adjust the minimum output to zero again and select the DA mode 3 If the right most LED in the bar graph is on Terminal V 10 VDC Terminal I 20 mA go to Step 3h If the LED is not on replace the A350P g If the sensor voltage is above 1 1 VDC on A350PS 1C or above 1 6 VDC on A350PS 2C adjust the setpoint to match the actual temperature Ts The output Terminal V ...

Page 11: ... C Proportional Stage Module S350PQ 1C Dual Scale F and C Power Module Y350R 1C 120 or 240 VAC 50 60 Hz Input Rectified Class 2 24 VAC Output Table 6 System 350 Accessories Item Product Code Number Description Wall Mount Plate TE 6001 4 Includes sensor mounting clip Cover T 4000 2644 For wall mount plate Mounting Clip A99 CLP 1 Surface mounting clip for the A99B Temperature Sensor Duct Mounting TE...

Page 12: ...cation A ten segment LED bar graph indicates percentage of output Control Action Direct or reverse action is jumper selectable Integration Constant Four selectable rates fast medium slow and off Sensor Replaceable positive temperature coefficient sensor Reference resistance 1035 ohms at 77 F 25 C Material Case and cover NEMA 1 high impact thermoplastic Agency Listing UL Listed CCN XAPX File E27734...

Reviews: