background image

 

System 350 A350P Electronic Proportional Plus Integral Temperature Control Product/Technical Bulletin    

7

 

 

Wiring Terminals 

Install all wiring to conform to the National Electrical 
Code and local regulations. For maximum electrical 
rating of control, refer to the label inside the control 
cover. Terminals will accept 12 to 26 AWG wire. Use 
only copper conductors. 

1.  Use a 1/8 in. (3 mm) flat-blade screwdriver to push 

the clamp arm down. 

2.  Insert the appropriate wire into the opening. 

Refer to Table 2 for terminal designations. 

3.  Release the clamp arm to secure the wire. 

See Figure 7. 

V

I

SN VDC

 

Figure 7: Cage Clamp Terminal Block  

Table 2: Terminal Designations 

Terminal 

Description 

0 to 10 VDC output 

0 to 20 mA output 

SN 

Temperature sensor input 

VDC 

5 VDC power supply (not used) 

Common for power supply, 
temperature sensor, and outputs 

24V 

24 Volts AC 

Note: 

Output signals from the A350P control vary 
from 0 to 10 VDC and 0 to 20 mA. (Both 
outputs can be used simultaneously.) 
Connections can be made to both the V and 
I terminals, allowing the control to drive 
two outputs from the same RA or DA ramp 
simultaneously. This feature can be used to 
drive motor actuators of different types in a 
single application. 

 

 

Sensor Connection 

Shielded cable is not generally required for sensor 
wiring on runs of less than 50 feet. When using 
shielded cable, isolate and tape the shield at the 
sensor. Connect the shield to Terminal C on the 
A350P control. 

Refer to Table 3 for the maximum recommended cable 
lengths for particular sizes of wire. 

Table 3: Maximum Recommended 
Sensor Cable Lengths 

Wire 

Shielded Cable Length 

Gauge 

Feet 

Meters 

14 AWG 

800 

244 

16 AWG 

500 

152 

18 AWG 

310 

94 

20 AWG 

200 

61 

22 AWG 

124 

38 

 

Various A99B Series Temperature Sensors and 
mounting hardware are available for use with 
A350P Series controls. 

The sensor must be connected to Terminals SN 
and C. (See Figure 2.) The sensors are not 
polarity sensitive. 

 

The sensor must be mounted so that it can 
accurately sense the temperature of the controlled 
medium. 

Table 4: A350P Controls And Sensors 

Control 

Sensor Included 

Sensor Lead Length is 9-3/4 in. 

(0.25 m) 

A350PS-1C 

A99BB-25C; Range: -40 to 212°F  
(-40 to 100°C) 

A350PS-1CM 

A99BB-25C; Range: -40 to 212°F  
(-40 to 100°C) 

A350PS-2C 

A99BC-25; Range: -40 to 248°F 
(-40 to 120°C) 

A350PS-2CM 

A99BC-25; Range: -40 to 248°F 
(-40 to 120°C) 

A350PT-1C 

No Sensor Included 

A350BA-2C 

A99BC-25; Range: -40 to 248°F 
(-40 to 120°C) 

 

For more information regarding sensor options 
and installation, refer to the

 A99B Series 

Temperature Sensors Product/Technical Bulletin 
(LIT-125186). 

Summary of Contents for System 350T A350P

Page 1: ...dules to be purchased and installed as needed Plug Together Connectors and 35 mm DIN Rail Mounting Eliminates wiring between modules which reduces installation costs Two Models Cover a Wide Setpoint Range of 30 to 250 F 35 to 121 C Reduces inventory by encompassing temperature ranges required to support the majority of Heating Ventilation Air Conditioning and Refrigeration HVAC R applications Mini...

Page 2: ...unted 10 segment Light Emitting Diode LED bar graph indicates percentage of output Features include adjustable setpoint adjustable minimum output adjustable throttling range proportional band selectable integration time constant selectable Reverse Acting RA or Direct Acting DA mode of operation IMPORTANT All System 350 controls are designed for use only as operating controls Where an operating con...

Page 3: ... at any time Note Before setting the minimum output potentiometer verify that the control reads zero output that is no LEDs are lit Throttling Range Proportional Band The throttling range is the range over which a control is active Throttling range for the A350P control can be adjusted from 2 to 30F 1 to 17C Make the adjustment at the throttling range potentiometer marked THROT RANGE see Figure 2 ...

Page 4: ...ntegrator This resets the integration error when the sensor goes just above the setpoint plus the throttling range in DA mode or just below the setpoint minus the throttling range in RA mode This allows the process to recover from an out of range condition without a large overshoot The A350P control has three field selectable integration constants and an off position The integration DIP switch sel...

Page 5: ...wed Y350R 4 2 0 External Class 2 Transformer 9 8 7 S350A On Off Stage Modules S350A On Off stage modules receive power setpoint and sensor input from the A350P control S350A stage modules perform switching functions based on the control s setpoint and sensor information as well as the offset and differential selected at the S350A stage module For more information on these modules refer to the Syst...

Page 6: ...alues The A350P Temperature Control is housed in a compact NEMA 1 plastic enclosure designed for standard 35 mm DIN rail mounting Four key slot mounting holes on the back of the control case are provided should surface mounting be required If a Y350R is used it should be mounted immediately to the right of the control Any S350 modules would follow on the right with the D350 being the last module m...

Page 7: ... different types in a single application Sensor Connection Shielded cable is not generally required for sensor wiring on runs of less than 50 feet When using shielded cable isolate and tape the shield at the sensor Connect the shield to Terminal C on the A350P control Refer to Table 3 for the maximum recommended cable lengths for particular sizes of wire Table 3 Maximum Recommended Sensor Cable Le...

Page 8: ...ghts 5 Make sure the system is stable in the proportional mode before selecting integration Refer to the Checkout Procedure section 6 Reinstall the cover and secure in place with the four captive cover screws 7 Adjust the setpoint dial to the desired setpoint If using the D350 Display Module press and hold the setpoint button on the D350 while rotating the setpoint dial Note The control s setpoint...

Page 9: ... to a value between 4 9 and 5 1 VDC replace the sensor If the DVM voltage is still below 4 9 VDC replace the A350P control 2 Check sensor for proper resistance at a given temperature The resistance across the sensor changes with the temperature of the sensor a Disconnect power from the A350P control b Disconnect the sensor from the control and measure the resistance across sensor leads c When meas...

Page 10: ...is on If not replace the A350P control 2 Adjust the minimum output to zero again and select the DA mode 3 If the right most LED in the bar graph is on Terminal V 10 VDC Terminal I 20 mA go to Step 3h If the LED is not on replace the A350P g If the sensor voltage is above 1 1 VDC on A350PS 1C or above 1 6 VDC on A350PS 2C adjust the setpoint to match the actual temperature Ts The output Terminal V ...

Page 11: ... C Proportional Stage Module S350PQ 1C Dual Scale F and C Power Module Y350R 1C 120 or 240 VAC 50 60 Hz Input Rectified Class 2 24 VAC Output Table 6 System 350 Accessories Item Product Code Number Description Wall Mount Plate TE 6001 4 Includes sensor mounting clip Cover T 4000 2644 For wall mount plate Mounting Clip A99 CLP 1 Surface mounting clip for the A99B Temperature Sensor Duct Mounting TE...

Page 12: ...cation A ten segment LED bar graph indicates percentage of output Control Action Direct or reverse action is jumper selectable Integration Constant Four selectable rates fast medium slow and off Sensor Replaceable positive temperature coefficient sensor Reference resistance 1035 ohms at 77 F 25 C Material Case and cover NEMA 1 high impact thermoplastic Agency Listing UL Listed CCN XAPX File E27734...

Reviews: