background image

 

4    

System 350

 

A350P Electronic Proportional Plus Integral Temperature Control Product/Technical Bulletin 

Proportional

Offset

Setpoint

Load Change

System Load

Control Point
Follows the Load

Temperature

Time

Throttling

Range

Proportional Only Control

Temperature

Proportional

Offset = 0

Setpoint

Load Change

System Load

Integration adjusts the
proportional output to
bring the process to
setpoint regardless of load.

Time

Proportional Plus Integral Control

 

Figure 4: Comparison Between Proportional Only and Proportional Plus Integral Control  

The A350P control has an integration feature that 
forces the control point to match the setpoint. Over 
time, the A350P will control the heating/cooling 
equipment to balance the system load at the control 
setpoint. (See Figure 4.) 

On traditional proportional plus integral controls, the 
amount of correction will become too large if the 
system load exceeds the capacity of the equipment. 
When the actuated device (valve or damper) is fully 
open or closed and the setpoint still cannot be 
reached, the integration error continues to grow. The 
result is called 

integral windup

The A350P control avoids 

integral windup

 with a 

patented circuit that puts a dynamic ceiling on the 
integrator. This resets the integration error when the 
sensor goes just above the setpoint plus the throttling 
range (in DA mode) or just below the setpoint minus 
the throttling range (in RA mode). This allows the 
process to recover from an out-of-range condition 
without a large overshoot. 

The A350P control has three field-selectable 
integration constants and an off position. The 
integration DIP switch selects the integration constant. 
(See Figure 2 for location.) 

The field-selectable integration constants include: 

 

OFF: Switch 1 to On position, all others Off 

provides proportional-only operation. 

Note: 

In open-loop (without feedback) applications, 
select OFF (proportional-only) operation. 

 

Slow (C3): Switch 2 to On position, all others 
Off

 is the slowest integration constant (26 minute), 

and is suitable for most proportional plus integral 
applications. Slow is the recommended initial 
setting. 

 

Medium (C2): Switch 3 to On position, all 
others Off

 selects a 13-minute integration 

constant. If the rate of system recovery to setpoint 
is sluggish with the control set to slow, and if the 
system has enough capacity to drive the process 
to setpoint at a faster rate, the medium setting 
may be used. 

 

Fast (C1): Switch 4 in On position, all 
others Off

 is the fastest integration constant 

(6.5 minutes). Use fast only in instances where the 
rate of change at the sensor is extremely rapid 
and system capacity can compensate for that 
rapid change. 

Summary of Contents for System 350T A350P

Page 1: ...dules to be purchased and installed as needed Plug Together Connectors and 35 mm DIN Rail Mounting Eliminates wiring between modules which reduces installation costs Two Models Cover a Wide Setpoint Range of 30 to 250 F 35 to 121 C Reduces inventory by encompassing temperature ranges required to support the majority of Heating Ventilation Air Conditioning and Refrigeration HVAC R applications Mini...

Page 2: ...unted 10 segment Light Emitting Diode LED bar graph indicates percentage of output Features include adjustable setpoint adjustable minimum output adjustable throttling range proportional band selectable integration time constant selectable Reverse Acting RA or Direct Acting DA mode of operation IMPORTANT All System 350 controls are designed for use only as operating controls Where an operating con...

Page 3: ... at any time Note Before setting the minimum output potentiometer verify that the control reads zero output that is no LEDs are lit Throttling Range Proportional Band The throttling range is the range over which a control is active Throttling range for the A350P control can be adjusted from 2 to 30F 1 to 17C Make the adjustment at the throttling range potentiometer marked THROT RANGE see Figure 2 ...

Page 4: ...ntegrator This resets the integration error when the sensor goes just above the setpoint plus the throttling range in DA mode or just below the setpoint minus the throttling range in RA mode This allows the process to recover from an out of range condition without a large overshoot The A350P control has three field selectable integration constants and an off position The integration DIP switch sel...

Page 5: ...wed Y350R 4 2 0 External Class 2 Transformer 9 8 7 S350A On Off Stage Modules S350A On Off stage modules receive power setpoint and sensor input from the A350P control S350A stage modules perform switching functions based on the control s setpoint and sensor information as well as the offset and differential selected at the S350A stage module For more information on these modules refer to the Syst...

Page 6: ...alues The A350P Temperature Control is housed in a compact NEMA 1 plastic enclosure designed for standard 35 mm DIN rail mounting Four key slot mounting holes on the back of the control case are provided should surface mounting be required If a Y350R is used it should be mounted immediately to the right of the control Any S350 modules would follow on the right with the D350 being the last module m...

Page 7: ... different types in a single application Sensor Connection Shielded cable is not generally required for sensor wiring on runs of less than 50 feet When using shielded cable isolate and tape the shield at the sensor Connect the shield to Terminal C on the A350P control Refer to Table 3 for the maximum recommended cable lengths for particular sizes of wire Table 3 Maximum Recommended Sensor Cable Le...

Page 8: ...ghts 5 Make sure the system is stable in the proportional mode before selecting integration Refer to the Checkout Procedure section 6 Reinstall the cover and secure in place with the four captive cover screws 7 Adjust the setpoint dial to the desired setpoint If using the D350 Display Module press and hold the setpoint button on the D350 while rotating the setpoint dial Note The control s setpoint...

Page 9: ... to a value between 4 9 and 5 1 VDC replace the sensor If the DVM voltage is still below 4 9 VDC replace the A350P control 2 Check sensor for proper resistance at a given temperature The resistance across the sensor changes with the temperature of the sensor a Disconnect power from the A350P control b Disconnect the sensor from the control and measure the resistance across sensor leads c When meas...

Page 10: ...is on If not replace the A350P control 2 Adjust the minimum output to zero again and select the DA mode 3 If the right most LED in the bar graph is on Terminal V 10 VDC Terminal I 20 mA go to Step 3h If the LED is not on replace the A350P g If the sensor voltage is above 1 1 VDC on A350PS 1C or above 1 6 VDC on A350PS 2C adjust the setpoint to match the actual temperature Ts The output Terminal V ...

Page 11: ... C Proportional Stage Module S350PQ 1C Dual Scale F and C Power Module Y350R 1C 120 or 240 VAC 50 60 Hz Input Rectified Class 2 24 VAC Output Table 6 System 350 Accessories Item Product Code Number Description Wall Mount Plate TE 6001 4 Includes sensor mounting clip Cover T 4000 2644 For wall mount plate Mounting Clip A99 CLP 1 Surface mounting clip for the A99B Temperature Sensor Duct Mounting TE...

Page 12: ...cation A ten segment LED bar graph indicates percentage of output Control Action Direct or reverse action is jumper selectable Integration Constant Four selectable rates fast medium slow and off Sensor Replaceable positive temperature coefficient sensor Reference resistance 1035 ohms at 77 F 25 C Material Case and cover NEMA 1 high impact thermoplastic Agency Listing UL Listed CCN XAPX File E27734...

Reviews: