A350P Electronic Proportional Plus Integral Temperature Control Product/Technical Bulletin 

A

djustments 

Follow this procedure to set up the A350P control for 
the types of operation desired. 

1.  Remove its cover by loosening the four captive 

cover screws. (See Figure 2.) 

2.  Set the RA/DA operation jumpers to the desired 

mode of operation. Position the operation jumpers 
vertically for RA (Reverse Acting) or horizontally 
for DA (Direct Acting). (See Figure 2.) 

3.  Adjust the throttling range potentiometer to desired 

setting. Rotate Clockwise (CW) to increase the 
throttling range. 

Notes:  Included with the control is a Celsius scale 

throttling range decal. If the Celsius scale is 
desired, refer to the 

Celsius Scale Conversion

 

section for decal installation instructions. 

 

 

If the A350P is to be used in proportional plus 
integral control, the initial throttling range 
adjustment is seldom set below 6F° (3C°). 
A narrow proportional band used in 
conjunction with the integration may result in 
unstable control. 

4.  If minimum output is required, set the minimum 

output potentiometer (see Figure 2) to the desired 
position. The 10-segment front LED panel or a 
voltmeter can be used to read the minimum 
output. (The minimum setting for the 

control

 is 

designated by the 0 on the decal.) 

Notes:  Before adjusting the minimum output 

potentiometer, verify that the control reads 
zero output (that is, no LEDs are lit). 

 

 

For each 10% increase in output, the 

next

  

bar will light on the LED bar graph (only 
one bar is lit at anytime). In a milliampere 
application, each bar equals 2 mA. In a 
voltage application, each bar equals 1 VDC. 
(Refer to Figure 3.) 

 

 

Example: 

 

 

To set the control for a minimum output of 
4 mA, turn the minimum output potentiometer 
clockwise until the second LED segment just 
lights. 

5. 

Make sure the system is stable in the proportional 
mode before selecting integration. Refer to the 

Checkout Procedure

 section. 

6. 

Reinstall the cover and secure in place with the 
four captive cover screws. 

7. 

Adjust the setpoint dial to the desired setpoint. 

If using the D350 Display Module, press and hold 
the setpoint button on the D350 while rotating the 
setpoint dial. 

Note: 

The control’s setpoint is factory calibrated at 
midscale to a tolerance of ±1F° (0.6C°). The 
setpoint tolerance at the extreme ends of the 
setpoint scale may be ± 4F° (2.2C°). The 
D350 Display Module is unaffected by this 
tolerance shift. Use the D350 for the most 
accurate setpoint selection. 

C

heckout Procedure 

Follow this procedure to verify the A350P control is 
connected and functioning properly. 

1. 

Before applying power, make sure that the 
installation and wiring connections are according 
to job specifications. 

2. 

Set up the system for proportional mode 
(Integration = OFF), and make any necessary 
adjustments to the setpoint, throttling range, and 
minimum output. Then select Reverse or Direct 
Acting mode. 

3. 

After making adjustments and electrical 
connections, apply power to the system, and 
observe it for stable operation. 

4. 

If integration is required, select the fast (C1), 
medium (C2), or slow (C3) integration constant. 
Slow is the recommended initial setting. (Refer to 
the 

Integration Function

 section.) 

5. 

Put the system back into operation. If instability 
occurs, consider increasing the throttling range. 

T

roubleshooting

If the control system does not function properly, verify 
that the proper operation mode is selected on each 
module (DA or RA), and perform the following 
procedures to determine the cause of the problem: 

1.  Check for proper voltages on the A350P control. 

a.  Connect a digital voltmeter (DVM) between 

Terminals 24V (+) and C (-) located on the 
A350P’s terminal block. (See Figure 2.) 

 

If an external transformer is used, select AC 
volts on the DVM. Verify that the voltage is 
between 20 and 30 VAC. 

Summary of Contents for System 350T A350P

Page 1: ...dules to be purchased and installed as needed Plug Together Connectors and 35 mm DIN Rail Mounting Eliminates wiring between modules which reduces installation costs Two Models Cover a Wide Setpoint Range of 30 to 250 F 35 to 121 C Reduces inventory by encompassing temperature ranges required to support the majority of Heating Ventilation Air Conditioning and Refrigeration HVAC R applications Mini...

Page 2: ...unted 10 segment Light Emitting Diode LED bar graph indicates percentage of output Features include adjustable setpoint adjustable minimum output adjustable throttling range proportional band selectable integration time constant selectable Reverse Acting RA or Direct Acting DA mode of operation IMPORTANT All System 350 controls are designed for use only as operating controls Where an operating con...

Page 3: ... at any time Note Before setting the minimum output potentiometer verify that the control reads zero output that is no LEDs are lit Throttling Range Proportional Band The throttling range is the range over which a control is active Throttling range for the A350P control can be adjusted from 2 to 30F 1 to 17C Make the adjustment at the throttling range potentiometer marked THROT RANGE see Figure 2 ...

Page 4: ...ntegrator This resets the integration error when the sensor goes just above the setpoint plus the throttling range in DA mode or just below the setpoint minus the throttling range in RA mode This allows the process to recover from an out of range condition without a large overshoot The A350P control has three field selectable integration constants and an off position The integration DIP switch sel...

Page 5: ...wed Y350R 4 2 0 External Class 2 Transformer 9 8 7 S350A On Off Stage Modules S350A On Off stage modules receive power setpoint and sensor input from the A350P control S350A stage modules perform switching functions based on the control s setpoint and sensor information as well as the offset and differential selected at the S350A stage module For more information on these modules refer to the Syst...

Page 6: ...alues The A350P Temperature Control is housed in a compact NEMA 1 plastic enclosure designed for standard 35 mm DIN rail mounting Four key slot mounting holes on the back of the control case are provided should surface mounting be required If a Y350R is used it should be mounted immediately to the right of the control Any S350 modules would follow on the right with the D350 being the last module m...

Page 7: ... different types in a single application Sensor Connection Shielded cable is not generally required for sensor wiring on runs of less than 50 feet When using shielded cable isolate and tape the shield at the sensor Connect the shield to Terminal C on the A350P control Refer to Table 3 for the maximum recommended cable lengths for particular sizes of wire Table 3 Maximum Recommended Sensor Cable Le...

Page 8: ...ghts 5 Make sure the system is stable in the proportional mode before selecting integration Refer to the Checkout Procedure section 6 Reinstall the cover and secure in place with the four captive cover screws 7 Adjust the setpoint dial to the desired setpoint If using the D350 Display Module press and hold the setpoint button on the D350 while rotating the setpoint dial Note The control s setpoint...

Page 9: ... to a value between 4 9 and 5 1 VDC replace the sensor If the DVM voltage is still below 4 9 VDC replace the A350P control 2 Check sensor for proper resistance at a given temperature The resistance across the sensor changes with the temperature of the sensor a Disconnect power from the A350P control b Disconnect the sensor from the control and measure the resistance across sensor leads c When meas...

Page 10: ...is on If not replace the A350P control 2 Adjust the minimum output to zero again and select the DA mode 3 If the right most LED in the bar graph is on Terminal V 10 VDC Terminal I 20 mA go to Step 3h If the LED is not on replace the A350P g If the sensor voltage is above 1 1 VDC on A350PS 1C or above 1 6 VDC on A350PS 2C adjust the setpoint to match the actual temperature Ts The output Terminal V ...

Page 11: ... C Proportional Stage Module S350PQ 1C Dual Scale F and C Power Module Y350R 1C 120 or 240 VAC 50 60 Hz Input Rectified Class 2 24 VAC Output Table 6 System 350 Accessories Item Product Code Number Description Wall Mount Plate TE 6001 4 Includes sensor mounting clip Cover T 4000 2644 For wall mount plate Mounting Clip A99 CLP 1 Surface mounting clip for the A99B Temperature Sensor Duct Mounting TE...

Page 12: ...cation A ten segment LED bar graph indicates percentage of output Control Action Direct or reverse action is jumper selectable Integration Constant Four selectable rates fast medium slow and off Sensor Replaceable positive temperature coefficient sensor Reference resistance 1035 ohms at 77 F 25 C Material Case and cover NEMA 1 high impact thermoplastic Agency Listing UL Listed CCN XAPX File E27734...