QUANTUM™ LX COMPRESSOR CONTROL PANEL
COMMUNICATIONS SETUP
090.020-CS (JUNE 11)
Page 99
Frick®
Address
AB
Address
Modbus
Address
Read/
Write
Description of Data
Units
8998
N119:98
48999
R
Stall Time Setpoint
Seconds
8999
N119:99
49000
R
Jam Current Level Setpoint
Percent (%)
9000
N120:00
49001
R
Jam Run Delay Setpoint
Seconds
9001
N120:01
49002
R
DBS Service Factor Setpoint
Percent (%)
9002
N120:02
49003
R
Current Unbalance Alarm Level Setpoint
9003
N120:03
49004
R
Current Unbalance Alarm Run Delay Setpoint
Seconds
9004
N120:04
49005
R
RTD Temperature Alarm Level Setpoint
Temperature
9005
N120:05
49006
R
RTD Temperature Trip Level Setpoint
9007
N120:07
49008
R
DBS Command Flags
None
Frick®
Address
AB
Address
Modbus
Address
Read/
Write
Description of Data
Units
9100
N121:00
49101
R/W
Real Time Trending Recording Interval
Seconds
9101
N121:01
49102
R/W
History Trending Recording Interval
Minutes
Frick®
Address
AB
Address
Modbus
Address
Read/
Write
Description of Data
Units
9200
N122:00
49201
R/W
Vyper Drive Standby Time
Minutes
9210
N122:10
49211
R
Vyper Drive Auto Speed Command
(NOTE: RPM values are
NOT multiplied by 10
in Allen-Bradley and
MODBUS protocols)
RPM
9211
N122:11
49212
R
Vyper Drive Run Command
None
9215
N122:15
49216
R
Vyper Drive Current Fault
None
9216
N122:16
49217
R
Vyper Drive Current Warning
9218
N122:18
49219
R
Vyper Drive Speed Command
(NOTE: RPM values are
NOT multiplied by 10
in Allen-Bradley and
MODBUS protocols)
RPM
9219
N122:19
49220
R
Vyper Drive Percent of Full Load Amps Percent (%)
9220
N122:20
49221
R
Vyper Drive Actual Speed
(NOTE: RPM values are
NOT multiplied by 10
in Allen-Bradley and
MODBUS protocols)
RPM
9223
N122:23
49224
R
Vyper Drive Operating Mode
None
9224
N122:24
49225
R
Vyper Drive Water Pump
9225
N122:25
49226
R
Vyper Drive Precharge Relay
9226
N122:26
49227
R
Vyper Drive Trigger SCRs
9228
N122:28
49229
R
Vyper Drive Output Frequency
Real
9229
N122:29
49230
R
Vyper Drive Output Voltage
Integer
9230
N122:30
49231
R
Vyper Drive DC Bus Voltage
VSD (VYPER) SETPOINT VALUES:
DBS SETPOINT VALUES (Continued):
GENERAL SETPOINT VALUES:
Summary of Contents for QUANTUM LX
Page 12: ...QUANTUM LX COMPRESSOR CONTROL PANEL COMMUNICATIONS SETUP 090 020 CS JUNE 11 Page 12 ...
Page 34: ...QUANTUM LX COMPRESSOR CONTROL PANEL COMMUNICATIONS SETUP 090 020 CS JUNE 11 Page 34 ...
Page 44: ...QUANTUM LX COMPRESSOR CONTROL PANEL COMMUNICATIONS SETUP 090 020 CS JUNE 11 Page 44 ...
Page 60: ...QUANTUM LX COMPRESSOR CONTROL PANEL COMMUNICATIONS SETUP 090 020 CS JUNE 11 Page 60 ...
Page 102: ...QUANTUM LX COMPRESSOR CONTROL PANEL COMMUNICATIONS SETUP 090 020 CS JUNE 11 Page 102 ...
Page 108: ...QUANTUM LX COMPRESSOR CONTROL PANEL COMMUNICATIONS SETUP 090 020 CS JUNE 11 Page 108 ...
Page 116: ...QUANTUM LX COMPRESSOR CONTROL PANEL COMMUNICATIONS SETUP 090 020 CS JUNE 11 Page 116 ...
Page 139: ...QUANTUM LX COMPRESSOR CONTROL PANEL COMMUNICATIONS SETUP 090 020 CS JUNE 11 Page 139 ...