QUANTUM™ LX COMPRESSOR CONTROL PANEL
COMMUNICATIONS SETUP
090.020-CS (JUNE 11)
Page 97
Frick®
Address
AB
Address
Modbus
Address
Read/
Write
Description of Data
Value Codes
8910
N119:10
48911
W
Remote – Start
1 = Start
See
Note 1
8911
N119:11
48912
W
Remote – Stop
1 = Stop
8912
N119:12
48913
W
Remote - Load Slide Valve
0 = Turn off
1 – 15 = Load x seconds
8913
N119:13
48914
W
Remote - Unload Slide Valve
0 = Turn off
1 – 15 = Unload x seconds
8914
N119:14
48915
W
Remote - RDB Capacity
25, 50, 75, 100 (represents capacity %)
8915
N119:15
48916
W
Remote - Compressor Mode
0 = Manual
1 = Auto
2 = Remote -- Communications
3 = Remote -- I/O
5 = Remote -- Sequencing
6 = Manual -- Browser
8916
N119:16
48917
W
Remote - Capacity Mode
1 = Auto
2 = Remote -- Communications
3 = Remote -- I/O
4 = Remote -- 4-20ma
5 = Remote – Sequencing
6 = Manual -- Browser
8917
N119:17
48918
W
Remote - Clear Alarms
1 = Clear Alarms
8918
N119:18
48919
W
Remote - Clear Recycle Delay
1 = Clear Recycle Delay
8919
N119:19
48920
W
Remote - Sequencing Mode
0 = Disable
1 = Enable
8920
N119:20
48921
W
Remote - Communication Units
0 = C ° / PSIA
1 = Panel Units
See
Note 2
8921
N119:21
48922
W
Remote - Regulation Mode
0 = Regulation Mode 1
1 = Regulation Mode 2
2 = Regulation Mode 3
3 = Regulation Mode 4
See
Note 3
8922
N119:22
48923
W
Remote – Set Slide Valve Position 0 – 100%
See
Note 4
8923
N119:23
48924
W
Remote – Set Drive Speed
0 – 100%
See
Note 5
8924
N119:24
48925
W
Remote – Set Total Capacity
0 - 200
See
Note 6
GENERAL NOTES:
Command Values need tenths
fi
eld added. For example, to
start the compressor, the table above states that 1 = Start.
However, being that one decimal place is assumed, a value of
10 actually needs to be sent.
SPECIFIC NOTES:
Note 1:
The compressor must be in remote communications
to accept the start and stop commands that are sent through
serial communications, and the Capacity Mode must be in re-
mote communications to accept load and unload commands
that are sent.
Note 2:
To read the proper Temperature/Pressure units, use
Frick® address 4566. To change (write to) the Temperature/
Pressure units, use Frick® address 8920.
Note 3:
Mode must already be enabled.
Note 4:
The value passed with this command is the position
(percentage) to which the control will attempt to set the Slide
Valve. The control will automatically load and/or unload the
Slide Valve until it is within a deadband (+/- 0.5%) of the target.
Conditions:
•
the compressor must be running
•
the Capacity Mode must be Remote Comms
•
if the compressor is Variable Speed, the Slide
Valve will not go below the Variable Speed Mini-
mum Slide Valve setpoint
This command is reset by a Remote Load or Remote Unload
command
Note 5:
The value passed with this command is the speed
(percentage) to which the control will attempt to set the Drive.
Conditions:
•
the compressor must be Variable Speed
•
the compressor must be running
•
the Capacity Mode must be Remote Comms
•
the Drive will not go below the Drive Speed Mini-
mum setpoint
This command is reset by a Remote Load or Remote Unload
command
Note 6:
This command is actually a combination the previ-
ous two (Remote – Set Slide Valve Position and Remote – Set
Drive Speed), and is for the convenience of the PLC program-
mer. A value of X from 0 to 100 will set the Slide Valve Position
to X% and the Drive Speed to 0% (or the allowable minimum).
A value of X from 100 to 200 will set the Slide Valve to 100%
and the Drive Speed to (X – 100)%.
COMMANDS:
Summary of Contents for QUANTUM LX
Page 12: ...QUANTUM LX COMPRESSOR CONTROL PANEL COMMUNICATIONS SETUP 090 020 CS JUNE 11 Page 12 ...
Page 34: ...QUANTUM LX COMPRESSOR CONTROL PANEL COMMUNICATIONS SETUP 090 020 CS JUNE 11 Page 34 ...
Page 44: ...QUANTUM LX COMPRESSOR CONTROL PANEL COMMUNICATIONS SETUP 090 020 CS JUNE 11 Page 44 ...
Page 60: ...QUANTUM LX COMPRESSOR CONTROL PANEL COMMUNICATIONS SETUP 090 020 CS JUNE 11 Page 60 ...
Page 102: ...QUANTUM LX COMPRESSOR CONTROL PANEL COMMUNICATIONS SETUP 090 020 CS JUNE 11 Page 102 ...
Page 108: ...QUANTUM LX COMPRESSOR CONTROL PANEL COMMUNICATIONS SETUP 090 020 CS JUNE 11 Page 108 ...
Page 116: ...QUANTUM LX COMPRESSOR CONTROL PANEL COMMUNICATIONS SETUP 090 020 CS JUNE 11 Page 116 ...
Page 139: ...QUANTUM LX COMPRESSOR CONTROL PANEL COMMUNICATIONS SETUP 090 020 CS JUNE 11 Page 139 ...