QUANTUM™ LX COMPRESSOR CONTROL PANEL
COMMUNICATIONS SETUP
090.020-CS (JUNE 11)
Page 22
CHANGE SLIDE VALVE MODE
COMMAND:
#IDMVmID
Command structure:
Command
Description
#
Start command sequence
ID
Compressor (ID) code (01, 14, etc.)
MV
(M)ode of Compressor Slide (V)alve
m
=
O (O)
ff
=
A (A)
uto
=
R (R)
emote
ID
(ID)
code repeated for veri
fi
cation
Returned Answer:
Character
Position
Description
1
(A)cknowledge
2, 3
(ID) code veri
fi
ed
(Carriage return, line feed)
RETURN PRESSURES COMMAND:
#IDPX
Command structure:
Command
Description
#
Start command sequence
ID
Compressor
(ID)
code (01, 14, etc.)
P
Return
(P)
ressures command
X
=
S
Return
(S)
uction Pressure (PSIA)
=
D
Return
(D)
ischarge Pressure (g/hg)
=
O
Return
(O)
il Pressure (g)
=
F
Return
(F)
ilter differential Pressure
=
A
Return
(A)
ll pressures as a string of
data
Command Examples: (Compressor #01 is used here)
#01PS
Returns the Suction Pressure
#01PD
Returns the Discharge Pressure
#01PO
Returns the Oil Pressure
#01PF
Returns the Filter Differential Pressure
#01PA
Returns All pressures
Note: Don’t send CR or LF
Returned Answer:
If using the S command the returned pressure will be:
XXXX = 4 characters followed by a CR, LF.
If using the D, O or F commands, the returned pressure
will be: XXX = 3 characters followed by a CR, LF.
If using the A command, the returned data would be:
XXXXXXXXXXXX = 12 characters followed by a CR, LF.
RETURN TEMPERATURES COMMAND: #IDTX
Command structure:
Command
Description
#
Start command sequence
ID
Compressor
(ID)
code (01, 14, etc.)
T
Return
(T)
emperature command
X
=
S
Return
(S)
uction Temperature
=
D
Return
(D)
ischarge Temperature
=
O
Return
(O)
il Temperature
=
P
Return Se
(P)
arator Temperature
=
A
Return
(A)
ll temps as a string of data
Command Examples: (Compressor #01 is used here)
#01TS
Returns the Suction Temperature
#01TD
Returns the Discharge Temperature
#01TO
Returns the Oil Temperature
#01TP
Returns the Separator Temperature
#01TA
Returns All Temperatures
Note: Don’t send CR or LF
Returned Answer:
If using the S command the returned temp. will be:
+/-XXX = The
fi
rst character will be a + or -, followed
by 3 characters and ending with a CR, LF.
If using the D, O or P commands, the returned temp.
will be:
XXX = 3 characters followed by a CR, LF.
If using the A command, the returned data would be:
XXXXXXXXXXXX = 12 characters followed by a CR, LF.
Summary of Contents for QUANTUM LX
Page 12: ...QUANTUM LX COMPRESSOR CONTROL PANEL COMMUNICATIONS SETUP 090 020 CS JUNE 11 Page 12 ...
Page 34: ...QUANTUM LX COMPRESSOR CONTROL PANEL COMMUNICATIONS SETUP 090 020 CS JUNE 11 Page 34 ...
Page 44: ...QUANTUM LX COMPRESSOR CONTROL PANEL COMMUNICATIONS SETUP 090 020 CS JUNE 11 Page 44 ...
Page 60: ...QUANTUM LX COMPRESSOR CONTROL PANEL COMMUNICATIONS SETUP 090 020 CS JUNE 11 Page 60 ...
Page 102: ...QUANTUM LX COMPRESSOR CONTROL PANEL COMMUNICATIONS SETUP 090 020 CS JUNE 11 Page 102 ...
Page 108: ...QUANTUM LX COMPRESSOR CONTROL PANEL COMMUNICATIONS SETUP 090 020 CS JUNE 11 Page 108 ...
Page 116: ...QUANTUM LX COMPRESSOR CONTROL PANEL COMMUNICATIONS SETUP 090 020 CS JUNE 11 Page 116 ...
Page 139: ...QUANTUM LX COMPRESSOR CONTROL PANEL COMMUNICATIONS SETUP 090 020 CS JUNE 11 Page 139 ...