QUANTUM™ LX COMPRESSOR CONTROL PANEL
COMMUNICATIONS SETUP
090.020-CS (JUNE 11)
Page 70
Frick®
Address
AB
Address
Modbus
Address
Read/
Write
Description of Data
Value Code
4027
N40:27
44028
R
Condenser Enabled
0 = Disabled
1 = Running
2 = Always
4070
N40:70
44071
R
Compressor Start Status
0 = Ready
1 = Start Inhibit In Shutdown
2 = Start Inhibit In Recycle Delay
3 = Start Inhibit High Discharge Temperature
4 = Start Inhibit High Oil Temperature
5 = Start Inhibit Low Separator Temperature
6 = Start Inhibit Slide Valve Too High
7 = Start Inhibit Still In Prelube
8 = Start Inhibit High Suction Pressure
9 = Start Inhibit High Suction/Discharge Differential
10 = Start Inhibit Permissive Start
11 = Start Inhibit Digital Auxiliaries
12 = Power Fail Restart
13 = Start Inhibit Low Oil Pressure
14 = Running
15 = Start Inhibit In Discharge Pressure Blowdown
4071
N40:71
44072
R
Capacity Status
0 = Idle
1 = Load
2 = Unload
4072
N40:72
44073
R
Volume Status
0 = Idle
1 = Increase
2 = Decrease
4073
N40:73
44074
R
Language (Local Display
Only)
0 = English
1 = French
2 = Chinese
3 = Portuguese
4 = Polish
5 = Chinese
6 = Spanish
7 = Russian
8 = Italian
4074
N40:74
44075
R
Temperature Units (Local
Display Only)
0 = Celsius
1 = Fahrenheit
4075
N40:75
44076
R
Pressure Units (Local Dis-
play Only)
0 = Kpaa
1 = Bar
2 = BarA
3 = PSIA
4 = PSIG/hg
5 = kpaG
4077
N40:77
44078
R
Regulation Mode 1
0 = Disabled
1 = Enabled
4078
N40:78
44079
R
Regulation Mode 2
4079
N40:79
44080
R
Regulation Mode 3
4080
N40:80
44081
R
Regulation Mode 4
4081
N40:81
44082
R
Sequencing Control Enable
4199
N41:99
44200
R
Manual Capacity Load/Un-
load
0 = Idle
1 = Load
2 = Unload
MODE VALUES: (Continued)
Summary of Contents for QUANTUM LX
Page 12: ...QUANTUM LX COMPRESSOR CONTROL PANEL COMMUNICATIONS SETUP 090 020 CS JUNE 11 Page 12 ...
Page 34: ...QUANTUM LX COMPRESSOR CONTROL PANEL COMMUNICATIONS SETUP 090 020 CS JUNE 11 Page 34 ...
Page 44: ...QUANTUM LX COMPRESSOR CONTROL PANEL COMMUNICATIONS SETUP 090 020 CS JUNE 11 Page 44 ...
Page 60: ...QUANTUM LX COMPRESSOR CONTROL PANEL COMMUNICATIONS SETUP 090 020 CS JUNE 11 Page 60 ...
Page 102: ...QUANTUM LX COMPRESSOR CONTROL PANEL COMMUNICATIONS SETUP 090 020 CS JUNE 11 Page 102 ...
Page 108: ...QUANTUM LX COMPRESSOR CONTROL PANEL COMMUNICATIONS SETUP 090 020 CS JUNE 11 Page 108 ...
Page 116: ...QUANTUM LX COMPRESSOR CONTROL PANEL COMMUNICATIONS SETUP 090 020 CS JUNE 11 Page 116 ...
Page 139: ...QUANTUM LX COMPRESSOR CONTROL PANEL COMMUNICATIONS SETUP 090 020 CS JUNE 11 Page 139 ...