9
NION-16C48M Installation & Operation Manual - P/N: 53347:Rev: A1 5/5/09
Section 2 Description and Installation
2.1 NION-16C48M Description
The NION-16C48M (16 Control, 48 Monitor) is a discrete input/output interface used on the
Intelligent Fire Integrator™ network. The NION-16C48M provides a gateway to the network for
discrete monitored devices, equipment and panels that have dry contacts; discrete devices can
operate on the same network as equipment with an EIA-232 output.
The NION-16C48M connects a LonWorks™ wire or fiber network with discrete monitored devices
and conventional panels. It provides a single two-way communication channel for discrete inputs
and outputs. NIONs are specific to the type of network to which they connect (wire or fiber). The
transceiver type must be specified and ordered separately when ordering the NION.
Required Hardware
•
Intelligent Fire Integrator™ system with an Echelon Gateway
•
NION-16C48M board
•
A regulated, UL 1481 listed, power limited, battery backed, +24 VDC power supply for the
NION.
•
SMX Network Transceiver (FTXC, FOXC, or DFXC)
•
“NION-16C48M EP Software Kit” on page 9
•
JNISCAB-1 cabinet (or CHS-4L chassis for use with CAB-3/4 series cabinet installation)
•
Serial interface cable (supplied by customer)
NION-16C48M EP Software Kit
The NION-16C48M software personality module part number is EP-IFI-16C48M-F/D.
“Software Replacement/Upgrade Information” on page 25
for replacing and upgrading this
NION’s software chips.
!
CAUTION: Hardware Compatibility
Only NION-16C48M board revisions
C
and above function properly with Intelligent Fire Integrator™.
Check to make sure the board revision is
C
or later and the BOM revision is
E
or later.
Board Revision
BOM Revision