Intelligent Fire Integrator™

NION-16C48M

Installation & Operation Manual

Document 53347
5/5/09

Rev: 

A1

P/N: 53347:A1

ECN: 09-347

Summary of Contents for Intelligent Fire Integrator NION-16C48M

Page 1: ...Intelligent Fire Integrator NION 16C48M Installation Operation Manual Document 53347 5 5 09 Rev A1 P N 53347 A1 ECN 09 347 ...

Page 2: ...of detec tor may not provide adequate warning of a fire Smoke detectors cannot be expected to provide adequate warning of fires caused by arson children playing with matches especially in bedrooms smoking in bed and violent explosions caused by escap ing gas improper storage of flammable materials etc Heat detectors do not sense particles of combustion and alarm only when heat on their sensors inc...

Page 3: ...punching of the enclosure When possible make all cable entries from the sides or rear Before making modifications verify that they will not interfere with battery transformer and printed circuit board location Do not tighten screw terminals more than 9 in lbs Over tightening may damage threads resulting in reduced terminal contact pressure and difficulty with screw terminal removal Though designed...

Page 4: ...urate If you have any comments you can email us Please include the following information Product name and version number if applicable Manual page number Your comment Send email messages to FireSystems TechPubs honeywell com Please note this email address is for documentation feedback only If you have any technical issues please contact Technical Services ...

Page 5: ...ers Board Layout 17 2 5 NION Power and Serial Data Connections 18 2 5 1 Power Connection 18 Figure 2 7 NION 16C48M Power Connector 18 2 5 2 Serial Data Input Output 19 Figure 2 8 NION 16C48M Input Jumpers 20 Figure 2 9 Output Jumper Settings 21 Figure 2 10 16C48MTB Terminal Board Mounting 22 Table 2 2 Ribbon Cable Mapping 23 Figure 2 11 Terminal I O Mapping 24 Figure 2 12 I O Point Connections 24 ...

Page 6: ...ION 16C48M Installation Operation Manual P N 53347 Rev A1 5 5 09 3 5 5 Special Operational Scenarios Outputs 35 3 5 6 Reset Conditions 35 3 5 7 Memory Loss on the NION 16C48M 35 3 6 NION 16C48M Device Addressing 35 Index 37 ...

Page 7: ... the unit shall be installed in accordance with Proprietary Burglar Alarm Units and Systems Fifth Edition Underwriters Laboratories Canada CAN ULC S524 06 Standard for the Installation of Fire Alarm Systems Fifth Edition CAN ULC S561 03 Installation and Services for Fire Signal Receiving Centres and Systems First Edition NOTE UL 864 9th Edition Intelligent Fire Integrator systems work with product...

Page 8: ... The following is a list of documentation resources related to the Intelligent Fire Integrator system Intelligent Fire Integrator JNFN GW Embedded P N 53138 Intelligent Fire Integrator JNFN GW PC P N 53097 Intelligent Fire Integrator Johnson Controls Echelon Gateway P N 53096 Intelligent Fire Integrator NION 2C8M P N 53346 Intelligent Fire Integrator NION 16C48M P N 53347 Intelligent Fire Integrat...

Page 9: ...iber The transceiver type must be specified and ordered separately when ordering the NION Required Hardware Intelligent Fire Integrator system with an Echelon Gateway NION 16C48M board A regulated UL 1481 listed power limited battery backed 24 VDC power supply for the NION SMX Network Transceiver FTXC FOXC or DFXC NION 16C48M EP Software Kit on page 9 JNISCAB 1 cabinet or CHS 4L chassis for use wi...

Page 10: ...ds provide terminal connections to monitored equipment NION 16C48M NION 16C48M motherboard The NION motherboard contains all relays LEDs CPU configuration jumpers network interface firmware and terminal board connections NISCAB 3 The NION 16C48M mounts in a locking cabinet with a Lexan dress plate UL Listed Power Supply 16C48M requires 800mA 24VDC SMX network transceiver One SMX transceiver daught...

Page 11: ...ly Status service input and output LEDs Inputs can be configured as either two state unsupervised or four state supervised with EOL resistors Transformer coupled network connection using SMX style transceivers Software configurable from the Workstation plug in utility Transient protection to 2400V on all terminals Included wall mount enclosure JNISCAB 3 Network Neuron code U44 Application code U6 ...

Page 12: ...this LED is flashing the NION is unbound If this LED is lit that indicates that the neuron chip is not running or has reached an unrecoverable error When bound the LED is unlit Input LEDs Input LEDs indicate the current status of each input Each LED will display the following patterns for each device status Point Disable The LED will flash once every seven seconds Point Disarm Override with Input ...

Page 13: ...on Step 1 Use the provided key to unlock the enclosure cover Step 2 Remove the enclosure cover Step 3 Mount the enclosure to the wall Refer to the enclosure mounting hole layout below Step 4 Mount the power supply and transformer to the standoffs in the back of the cabinet using the provided hardware Step 5 Mount the NION 16C48M motherboard to the mounting rails in the same manner Figure 2 4 JNISC...

Page 14: ...rresponding transceiver style that is unique to its specific network application connection must be ordered separately SMX Transceiver Installation The procedure for mounting any transceiver daughterboard to a motherboard is the same for all styles of transceivers Step 1 Remove power from the NION Step 2 Install the two standoffs on the motherboard Step 3 Align the transceiver header connectors on...

Page 15: ...up to 6 000 feet 1828 8 m per segment in a dedicated bus configuration or up to 1 500 feet 457 2 m per segment in a star configuration Each segment can support 64 FTXCs and with routers the system can be expanded up to 200 nodes A maximum load of 30 ohms on each leg of the Echelon wire network is permitted Figure 2 5 FTXC Network Transceiver Board Layout Header Connection Bus Termination Electrica...

Page 16: ...he DFXC an ideal solution for large projects with substantial message traffic as well as small projects to connect as few as two nodes together The DFXC provides two ST style fiber optic connectors and is configured for use with 62 5 125 micron or 100 140 micron multi mode fiber 50 125 fiber may also be used at reduced optical link budgets The SMX connector a 2x10 header is compatible with the Int...

Page 17: ...nodes per segment Figure 2 6 FOXC and DFXC Fiber Optic Transceivers Board Layout Table 2 1 DFXC Wire Specifications 880 NM TYPICAL 100 140 µ 62 5 125 µ Coupled power dBm 8 to 10 10 to 12 Receiver sensitivity dBm 26 26 Link budget dBm 16 to 18 14 to 16 Typical link length km w 3 2 dB km 3 dB margin 0 6 dB for 2 connectors 3 9 to 4 5 3 3 to 3 9 FOXC Fiber Optic Transceiver Header Connection DFXC Fib...

Page 18: ...plication This NION requires 24 VDC 800 mA nominal and battery backup in accordance with local code requirements Connect the power supply s 24 VDC and GND connections to the NION 16C48M s TB11 24 VDC and GND pins respectively GND 24VDC NOTE Use only wire for power limited systems Power limited wire runs use type FPLR FPLP FPL or equivalent cabling per NEC 760 Wiring from the NION to the panel or a...

Page 19: ...ate unsupervised or four state supervised inputs or switched voltage SV inputs Each input can be individually configured for maximum flexibility To define the function of each of these inputs WARNING NION Power Wiring Panel power connectors that are used to provide power for a NION must be made to the panel s non resettable connector NOTE Configure input output jumper settings before installing te...

Page 20: ...relay outputs The relays are rated at 2 5A 30VDC They can be wired for normally open or normally closed operation All rated loads are resistive Inductive and tungsten loads will be lower For special applications consult with a Technical Services Representative For SV inputs close pins 1 and 2 For Discrete close pins 2 and 3 Not used For SV inputs close pins 1 and 2 For Discrete close pins 2 and 3 ...

Page 21: ...xteen Above each relay is its related LED and below is a corresponding jumper to set the output for normally open or normally closed operation Refer to the diagram below for jumper settings Figure 2 9 Output Jumper Settings Pin 1 Pin 3 Output LED Output jumper relay typical NION 16C48M motherboard Output relays 1 16 Output operation jumper Set the jumper across pins 1 and 2 for normally closed ope...

Page 22: ... interchangeable Each terminal board is connected to the motherboard via included ribbon cables four per terminal board Point designation for each terminal is determined by the position of the terminal board on the motherboard Refer to the diagrams below for terminal board mounting and ribbon cable connections Figure 2 10 16C48MTB Terminal Board Mounting U44 U6 Mounting standoffs This standoff is ...

Page 23: ...d has eight cable sockets P1 through P8 Each terminal board has four sockets labelled P1 through P4 Terminal board one T1 is mounted on the left and terminal board two T2 is mounted on the right The chart below maps the motherboard sockets to the terminal board sockets Table 2 2 Ribbon Cable Mapping Motherboard Socket Terminal Board Terminal Socket P1 T1 P1 P2 T1 P2 P3 T1 P3 P4 T1 P4 P5 T2 P1 P6 T...

Page 24: ...ts 1 8 Inputs 9 16 Inputs 17 24 Outputs 1 8 Inputs 25 32 Inputs 33 40 Inputs 41 48 Outputs 9 16 Terminal board 1 Terminal board 2 P1 P2 P1 P2 P4 P3 P4 P3 NOTE For each terminal connector the inputs and outputs are numbered from left to right Ground A B C D E F G H Input terminals A H represent any 8 inputs Output terminals A H represent any 8 outputs A B C D E F G H Input R 1K resistor R 3 3K resi...

Page 25: ...he socket Then press it gently but firmly into the socket until it seats Step 5 Re apply power to the NION Step 6 If the network protocol chip was replaced refresh the NION Figure 2 13 NION 16C48M Chip Replacement NOTE Always remove power from the NION before making any changes to switch settings and removing or installing option modules SMX network modules and software upgrade chips or damage may...

Page 26: ...Description and Installation Software Replacement Upgrade Information 26 NION 16C48M Installation Operation Manual P N 53347 Rev A1 5 5 09 ...

Page 27: ...age 30 Holiday Codes on page 31 Configurations defined using these schedulers are downloaded and stored in the NIONs The NION s relative configuration window is accessed through a device icon s right click list of choices The tabbed windows allow saving and loading of the I O configuration time code and holiday code assignments They can be used to duplicate one sub node configuration to any number...

Page 28: ...te it is latched and the point will not clear until the Clear Latched Points command is performed Latched 4 State Normally Closed normally closed input reporting active normal short and open when the input changes to an active state it is latched and the point will not clear until the Clear Latched Points command is performed To configure a large block of inputs to the same state option on a NION ...

Page 29: ... box listing all available time codes 1 30 3 2 6 Multiple State To configure a large block of inputs to the same state option on a NION use the Multiple State Configuration box on the I O Configuration form Enter the range of input points in the From and To fields select the desired state option in the Configure As combo box then click the Set State button to finish Input state options include Not...

Page 30: ...chedule setting times that an individual can access certain locations etc The application of time codes and their related data depends entirely on the application or device that implements them Universal Time Codes and Time Code Groups The Universal Time Code Editor UTE is a utility that allows you to define view and edit IFI Workstation Universal Time Codes These time codes can be imported into t...

Page 31: ...idays which also marks the dates on the calendar Keep in mind that every calendar must contain at least one holiday code Any calendar that does not contain any holiday codes is not saved by the system Holiday codes are commonly used to specify separate time code schedules for set holidays but like time codes the actual usage depends on the application or device in which they are implemented Clicki...

Page 32: ...Input Normal Open Circuit Short Circuit The NION reports different point states based on the current operational mode of the input 3 5 2 Rules for Mode Change Commands The mode of any input may be changed by any of these methods Scheduled time codes defined in the plug in When a time code becomes active Start Time the input is disarmed When the time code expires Stop Time the input is armed During...

Page 33: ...e resulting action is based on the origin of the command If the command originated from a Manual operation the point will be Disarmed A return to normal event will be sent before the point is Disarmed If the command is a Scheduled or Automatic function the point will not be Disarmed until it returns to normal When the point returns to normal the schedule will be checked and the point will immediat...

Page 34: ... the output is activated When the time code expires Stop Time the input is deactivated During the intermediate time between start and stop the scheduler will not automatically alter the state of an output Manual user action Such action can only be initiated from the Workstation Automatic NetLogic equation execution After evaluating an equation NetLogic may execute an action which sends a command t...

Page 35: ...urs all input points are assumed to be in the Armed mode see exception below As part of the boot sequence the scheduler will immediately modify input modes and output states as needed An event will be generated for every point on the node For hard reset only all outputs are deactivated in the hardware During a node reset any input point that was in a Disabled mode at the time of the reset will rem...

Page 36: ...NION 16C48M Configuration NION 16C48M Device Addressing 36 NION 16C48M Installation Operation Manual P N 53347 Rev A1 5 5 09 ...

Page 37: ...XC Network Transceivers 16 F FOXC Network Transceivers 16 FTXC Network Transceivers 15 H Hardware Requirements 9 I Installation Environmental Conditions 8 N NION Hardware Connections Power Connection 18 R Regulatory Listings 18 S SMX Network Transceivers 14 Software Replacement 25 ...

Page 38: ...Index 38 NION 16C48M Installation Operation Manual P N 53347 Rev A1 5 5 09 ...

Page 39: ...r service department Return product transportation prepaid to the manufacturer This writing constitutes the only warranty made by the manufacturer with respect to its products The manufacturer does not represent that its products will prevent any loss by fire or otherwise or that its products will in all cases provide the protection for which they are installed or intended Buyer acknowledges that ...

Page 40: ...Controls Group 507 E Michigan Street P O Box 423 Milwaukee WI 53201 www johnsoncontrols com Release Rev A1 Printed in U S A ...