FRICK
QUANTUM™LX AcuAir
CONTROL PANEL 090.510-M (OCT 10)
MAINTENANCE Page 27
MISCELLANEOUS MAINTENANCE SCREENS
About
SCREEN NAME
:
Sequencing
.
ACCESSING
:
DESCRIPTION
: The
About
screen shows the Analog and Digital boards that have been detected. If a board
has lost communications, a shutdown will be issued. All outputs are turned off on a Digital Board that has
lost communications. All inputs will get set to their minimum value range on an Analog Board that has lost
communications. A loss of communications to an analog board should result in sensor fault shutdown
message that is associated with the sensors on that board. If the RX LED on the I/O board is blinking but the
board was not detected on the
About
screen, or an I/O Comm failure occurs, check the address of the
board.
About