QUANTUM™ HD COMPRESSOR CONTROL PANEL
OPERATION
090.040-O (MAR 12)
Page 95
CONFIGURATION
Digital Auxiliaries - Digital Aux Outputs
ACCESSING:
A
Digital Aux Outputs
Digital Auxiliaries
DESCRIPTION:
Use these screens (Digital Aux. Output A
- J) to setup and control an Auxiliary Digital Output using
the signal from an Analog Input. The following descrip-
tions apply to all Digital Aux. Output pages.
The graphic below illustrates one scenario in which an
analog Temperature input is used to drive a digital output.
When the temperature exceeds the On When value of 75°,
the output will energize. It will remain in this state until
the analog input falls below the Off When value of 73°.
This state will persist until the input again exceeds the
On When value. The resulting temperature control would
resemble the following sine wave:
75°
74
°
73°
76°
72°
Output is
energized
Output is
de-energized
DIGITAL AUX. OUTPUT A
- (Off or On status shown)
Analog Input
•
Capacity Slide Position
•
Volume Slide Position
• Suction
Pressure
• Discharge
Pressure
•
Compressor Oil Pressure
•
Main Oil Injection Pressure
• Economizer
Pressure
• Filter
Pressure
• Intermediate
Pressure
•
Balance Piston Pressure
•
System Discharge Pressure
• Suction
Temperature
• Discharge
Temperature
•
Compressor Oil Temperature
•
Oil Separator Temperature
•
Process/Brine Temperature Leaving
•
Process/Brine Temperature Entering
•
Remote Control Setpoint
• Motor
Current
• RPM
• User
de
fi
ned analog inputs #1 - #20
• User
de
fi
ned analog inputs #12 - #20
• Manifold
Pressure
•
Remote Capacity Position
•
Compressor Vibration – Suction
•
Compressor Vibration – Discharge
•
Motor Vibration – Shaft Side
•
Motor Vibration – Opposite Shaft Side