QUANTUM™ HD COMPRESSOR CONTROL PANEL
OPERATION
090.040-O (MAR 12)
Page 66
unloading the slide valve when a Full Time or
Demand pump is selected. When this option is
enabled, it allows the pump output to energize
when starting the compressor, if the slide valve
position is above the “Highest Capacity to Permit
Starting” setpoint.
•
Disabled
– Oil Pump Unload Assist is
disabled.
•
Enabled
– Oil Pump Unload Assist is
enabled.
[Main Oil Injection]
•
Is Above (Setpoint)
- The Main Oil In-
jection output will energize when the
Discharge Temperature exceeds this
setpoint.
•
For (Delay)
– Once the Main Oil Injec-
tion output has been energized by the
above setpoint, it will remain energized
for this amount of time.
LUBRICATION
[Oil Pump Lube Time Before Starting]
- The
amount of time that the compressor will be de-
layed from starting to allow the Oil Pump to pre-
lube the compressor components.
DESCRIPTION:
This is Oil Pump / Lubrication setup screen.
Use this screen to set the basic operational characteristics
of the oil and lubrication system.
OIL PUMP
[Pump Type]
• No
Pump
• Full
Time
• Demand
•
Shaft With Auxiliary
• Shaft
[Dual Pump Control]
• Disabled
– Dual Pump is disabled.
• Enabled
[Oil Log]
•
Disabled
– Oil Log is disabled.
•
Enabled
– If for the Oil Log Delay set-
point period, the oil pump has been on
and the compressor is Off or Starting
without going into Running, an Oil Log
shutdown will occur.
[Oil Pump Unload Assist]
- This is to assist in
CONFIGURATION
Package - Oil Pump / Lubrication
ACCESSING:
Oil Pump / Lubrication
Package