QUANTUM™ HD COMPRESSOR CONTROL PANEL
OPERATION
090.040-O (MAR 12)
Page 82
DESCRIPTION:
Use this screen to set the speci
fi
c Drive
safeties information for a Vyper motor starter. These
safeties are important for the safe operation of the com-
pressor and motor.
VYPER CONTROL
Standby Time
- The amount of time after the
compressor is stopped that the Vyper will keep
the DC Bus charged to quickly react to Start
commands.
Time Remaining
- The time remaining for stand-
by time once the standby time expires, allowing
the DC Bus to discharge.
Command Rate
- The frequency of communica-
tions per second.
CONFIGURATION
Drive - Vyper Control
ACCESSING:
Drive
Vyper
Control
Self Clearing Vyper Faults
- Many Vyper faults
are self-clearing. If the Self-Clearing Faults has
been enabled, the Vyper can clear faults and be
re-started if needed.
• Disabled
• Enabled
Clear Total kWh
- Clears the total KiloWatt
hours accurued by the Vyper.
Clear VSD Fault Memory
- Clears the VSD fault
memory.