QUANTUM™ HD COMPRESSOR CONTROL PANEL
OPERATION
090.040-O (MAR 12)
Page 125
CONFIGURATION
Analog I/O
ACCESSING:
Analog 1
Analog I/O
DESCRIPTION:
The Analog I/O screens are used to view
and set the Analog Input and Output sensor ranges, sen-
sor type and board/channel assignments, and should be
used anytime an Analog I/O point needs to be con
fi
gured.
Each screen consists of the same layout, with the excep-
tion of the I/O point name:
ANALOG 1 (2, 3)
I/O Point
- See the list below for each page.
Low
- Enter the low end range that the sensor is
capable of reading here.
High
- Enter the high end range that the sensor
is capable of reading here.
Sensor Output -
A pop-up menu provides for
the following selection for sensor types:
• 0-5V
• 1-5V
• 4-20mA
• ICTD
• 0-20mA
• 0-10V
• 2-10V
I/O Board
- A pop-up menu provides for the fol-
lowing selection for the I/O board:
• None
•
Analog Bd 1
•
Analog Bd 2
I/O Channel
- Enter the I/O Channel (with regard
to the I/O Board selection) that the I/O point will
be assigned to.
The following list shows the I/O point assignments for
each page:
ANALOG 1
Suction Temperature
Discharge Temperature
Oil Temperature
Separator Temperature
Leaving Process Temperature
Oil Process
Filter Pressure
Discharge Pressure
Suction Pressure
Entering Process Temperature
System Discharge Pressure
Drive Speed
ANALOG 2
Economizer Pressure
Capacity Slide
Volume Slide
Motor Amps