QUANTUM™ HD COMPRESSOR CONTROL PANEL
OPERATION
090.040-O (MAR 12)
Page 69
above the Control Setpoint. If the PID’s Action
is Reverse, the Proportional Band extends below
the Control Setpoint.
[Integration Time]
- This setpoint controls the
in
fl
uence that the Integral component exerts on
the PI Output value. The Integral component
works to push the Control Input toward the Con-
trol Setpoint by tracking the difference between
the Control Input and the Control Setpoint over
time.
High Limit
- The highest value that the output
can be.
Low Limit
- The lowest value that the output
can be.
I/O Board
- Select from one of the following:
•
None
•
Analog Board 1
•
Analog Board 2
I/O Channel
- Select the output channel that will
be used.
Port Multiplier
– If the Economizer is On and the
Pressure Input selection is not Disabled, this set-
point is used in calculating the Volume Ratio. A
value of 1.6 is used for RXF models, and a value
of 1.4 is used for RWF models.