QUANTUM™ HD COMPRESSOR CONTROL PANEL
OPERATION
090.040-O (MAR 12)
Page 143
delay.
High Limit Disch Temp Shutdown
- The Discharge
Temperature was greater than or equal to the active
High Discharge Temperature Shutdown setpoint for
its time delay.
High Liquid Level Sensor Warning
– This warning
message is issued if the Liquid Level reading was to
the upper or maximum range (out of range) for its
sensor.
High Liquid Level Shutdown
– If the Liquid Level
rises above the Liquid Level sensor, a delay timer is
started. If the Level does not recover before the delay
timer counts down, a Shutdown is issued.
High Main Oil Inj Pressure Sensor Warning
– This
warning message is issued if the Main Oil Injector
Pressure reading (analog board 2, channel 15) was to
the upper or maximum range (out of range) for its
sensor.
High Manifold Pressure Sensor Warning
– This
warning message is issued if the Manifold Pressure
reading was to the upper or maximum range (out of
range) for its sensor.
High Manifold Pressure Shutdown
- This shutdown
applies if Engine Drive was enabled. When the Mani-
fold Pressure exceeds this setpoint, an alarm will oc-
cur.
High Manifold Pressure Warning
- This warning ap-
plies if Engine Drive was enabled. When the Manifold
Pressure exceeds this setpoint, a warning will occur.
High Motor Current Sensor Warning
– This warning
message is issued if the Motor Current reading (ana-
log board 1, channel 16) was to the upper or maxi-
mum range (out of range) for its sensor.
High Motor Current Shutdown
- The motor amps
was greater than or equal to the High Motor Amps
Shutdown setpoint for its time delay.
High Motor Current Warning
- The Motor Amps was
greater than or equal to the High Motor Amps Warn-
ing setpoint for its time delay.
High Motor Stator #1 Temp Warning
– If Motor
Stator #1 temperature sensor registers a reading that
is higher than the value that has been set for the Mo-
tor Stator #1 Temp. Warning, for the period of time
as set for the Motor Stator #1 Temp. Warning Delay,
a warning will be generated. The default values for
these setpoints Default setpoints for this Warning are
302° F and 5 seconds.
High Motor Stator #1 Temp Shutdown
– If Motor
Stator #1 temperature sensor registers a reading that
is higher than the value that has been set for the Mo-
tor Stator #1 Temp. Shutdown, for the period of time
as set for the Motor Stator #1 Temp. Shutdown Delay,
a Shutdown will be generated. The default values for
these setpoints are 311° F, and 5 seconds.
High Motor Stator #2 Temp Warning
– If Motor Sta-
tor #2 temperature sensor registers a reading that is
higher than the value that has been set for the Mo-
tor Stator #2 Temp. Warning, for the period of time
as set for the Motor Stator #2 Temp. Warning Delay,
a warning will be generated. The default values for
these setpoints 302° F, and 5 seconds.
High Motor Stator #2 Temp Shutdown
– If Motor
Stator #2 temperature sensor registers a reading that
is higher than the value that has been set for the Mo-
tor Stator #2 Temp. Shutdown, for the period of time
as set for the Motor Stator #2 Temp. Shutdown Delay,
a Shutdown will be generated. The default values for
these setpoints are 311° F, 5 seconds.
High Motor Stator #3 Temp Warning
– If Motor
Stator #3 temperature sensor registers a reading that
is higher than the value that has been set for the Mo-
tor Stator #3 Temp. Warning, for the period of time
as set for the Motor Stator #3 Temp. Warning Delay,
a warning will be generated. The default values for
these setpoints are 302° F, and 5 seconds.
High Motor Stator #3 Temp Shutdown
– If Motor
Stator #3 temperature sensor registers a reading that
is higher than the value that has been set for the Mo-
tor Stator #3 Temp. Shutdown, for the period of time
as set for the Motor Stator #3 Temp. Shutdown Delay,
a Shutdown will be generated. The default values for
these setpoints are 311° F, and 5 seconds.
High Motor Temp Shutdown - Opp Shaft Side
–
The motor has temperature sensors that monitor
the Opposite Shaft Side bearing. If the temperature
of this bearing exceeds the Opposite Shaft Side High
Shutdown setpoint, for a period of time exceeding
the Opposite Shaft Side High Shutdown Delay set-
point, this Shutdown will occur. The default values for
these setpoints are 221° F and a delay of 5 seconds.
High Motor Temp Shutdown - Shaft Side
– The
motor has temperature sensors that monitor the
Shaft Side bearing. If the temperature of this bear-
ing exceeds the Shaft Side High Shutdown setpoint,
for a period of time exceeding the Shaft Side High
Shutdown Delay setpoint, this Shutdown will occur.
The default values for these setpoints are 221° F and
a delay of 5 seconds.
High Motor Temp Warning - Opp Shaft Side
– The
motor has temperature sensors that monitor the Op-
posite Shaft Side bearing. If the temperature of this
bearing exceeds the Opposite Shaft Side High Warn-
ing setpoint, for a period of time exceeding the Op-
posite Shaft Side High Warning Delay setpoint, this
Warning will occur. The default values for these set-
points are 203° F and a delay of 5 seconds.