Table 8: Status LEDs and Descriptions of LED States
Description of LED States
Normal LED
State
LED Color
LED Label
Off Steady = No Supply Power or the controller’s polyswitch/resettable fuse
is open. Check Output wiring for short circuits and cycle power to controller.
On Steady = Power Connected
On Steady
Green
POWER
Off Steady = No Faults
On Steady = Device Fault; no application loaded; Main Code download
required, if controller is in Boot mode, or a firmware mismatch exists between
the FEC and the ZFR1811 Wireless Field Bus Router.
Blink - 2 Hz = Download or Startup in progress, not ready for normal operation
Off Steady
Red
FAULT
Blink - 2 Hz = Data Transmission (normal communication)
Off Steady = No Data Transmission (N/A - auto baud not supported)
On Steady = Communication lost, waiting to join communication ring
Blink - 2 Hz
Green
SA BUS
Blink - 2 Hz = Data Transmission (normal communication)
Off Steady = No Data Transmission (auto baud in progress)
On Steady = Communication lost, waiting to join communication ring
Blink - 2 Hz
Green
FC BUS
On Steady = EOL switch in ON position
Off Steady = EOL switch in Off position
Off (Except on
terminating
devices)
Amber
EOL
Repair Information
If a controller fails to operate within its specifications,
replace the controller. For a replacement controller,
contact your Johnson Controls
®
representative.
Accessories
See
for controller accessories ordering
information.
Table 9: Accessories Ordering Information
Description
Product Code Number
Wireless Commissioning Converter, with Bluetooth
®
Technology
MS-BTCVT-1
Local Controller Display (for use with MS-FEC2611 model only)
MS-DIS1710-0
Wireless Field Bus Routers
MS-ZFR1811 MS-ZFR1812
Transformer, 120 VAC Primary to 24 VAC secondary, 20 VA, Wall Plug
TP-2420
Transformer, 120/208/240 VAC Primary to 24 VAC Secondary, 40 VA, Foot Mount, 8 in.
Primary Leads and Secondary Screw Terminals, Class 2
Note:
Additional Y6x-x Series transformers are also available. Refer to the
Series Y63,
Y64, Y65, Y66, and Y69 Transformers Product Bulletin (LIT-125755)
for more
information.
Y65T31-0
Power transformer (Class 2, 24 VAC, 50 VA maximum output), no enclosure
AS-XFR050-0
Replacement SA Bus Terminal Blocks, 4-Position, Brown, Bulk Pack
AP-TBK4SA-0
Replacement FC Bus Terminal Blocks, 4-Position, Blue, Bulk Pack
AP-TBK4FC-0
Replacement Power Terminal Blocks, 3-Position, Gray, Bulk Pack
AP-TBK3PW-0
USB Dongle with ZigBee
®
Driver provides a wireless connection through CCT to allow
wireless commissioning of the wirelessly enabled FEC, FAC, IOM, and VMA16 field
controllers. Also allows use of the ZFR Checkout Tool (ZCT) in CCT.
Note:
The ZFR-USBHA-0 replaces the IA OEM DAUBI_2400 ZigBee USB dongle. For
additional information on the ZFR-USBHA-0 ZigBee dongle, refer to the
ZFR1800
Series Wireless Field Bus System Technical Bulletin (LIT-12011295)
or
ZFR1800
Series Wireless Field Bus System Quick Reference Guide (LIT-12011630).
ZFR-USBHA-0
26
FEC26Field Equipment Controllers Installation Instructions