FEC26
FEC2511
(Asia Only
model)
Signals
Accepted
Point Types
6
4 (Does not
support
Current Mode)
Analog Input,
Voltage Mode,
0–10 VDC
Universal
Input (UI)
Analog Input,
Current Mode,
4–20 mA
Analog Input,
Resistive
Mode, 0–2k
ohm,
resistence
temperature
detector
(RTD) (1k NI
[Johnson
Controls], 1k
PT, A99B SI),
negative
temperature
coefficient
(NTC) (10k
Type L,
2.252k Type
2)
Binary Input,
Dry Contact
Maintained
Mode
FEC26
FEC2511
(Asia Only
model)
Signals
Accepted
Point Types
2
6
Dry Contact
Maintained
Mode
Binary Input
(BI)
Pulse
Counter/Accumulator
Mode (High
Speed), 100
Hz
2
2 (Voltage
Only)
Analog
Output,
Voltage Mode,
0–10 VDC
Analog
Output (AO)
Analog
Output,
Current Mode,
4–20 mA
3
2 (Ext Power
only)
24 VAC Triac
Binary
Output (BO)
4
2
Analog
Output,
Configurable
Output (CO)
Voltage Mode,
0–10 VDC
Binary Output
Mode, 24 VAC
Triac
1
Analog Input, Current Mode is set by hardware for the
FEC26.
14
FEC26Field Equipment Controllers Installation Instructions