Table 3: FEC26 Terminal Blocks, Functions, Ratings, Requirements, and Cables
Determine Wire Size and
Maximum Cable Length
Function, Ratings,
Requirements
Terminal Label
Terminal Block Label
See Guideline
A
in
Analog Output - Voltage
Mode (0–10 VDC)
10 VDC maximum output
voltage
10 mA maximum output current
Required an external load of
1,000 ohms or more.
OUTn
CONFIGURABLE
(Outputs)
See Guideline
C
in
Binary Output - 24 VAC Triac
(External Power Source only)
Connects OUT
n
to OCOM
n
when activated.
External Power Source
Requirements:
30 VAC maximum output
voltage
0.5 A maximum output current
1.3 A at 25% duty cycle
40 mA minimum load current
Same as (Configurable)
OUTn
.
Analog Output Signal
Common
All Configurable
Outputs (COs) defined as
Analog Outputs (AOs) share a
common, which is isolated from
all other commons except the
Binary Input common.
OCOMn
Binary Output Signal
Common
All Configurable
Outputs (COs) defined as
Binary Outputs are isolated
from all other commons,
including other CO commons.
19