Table 3: FEC26 Terminal Blocks, Functions, Ratings, Requirements, and Cables
Determine Wire Size and
Maximum Cable Length
Function, Ratings,
Requirements
Terminal Label
Terminal Block Label
See Guideline
C
in
Binary Output - 24 VAC Triac
(External Power Source)
Connects OUT
n
to OCOM
n
when activated.
External Power Source
Requirements:
30 VAC maximum output
voltage
0.5 A maximum output current
1.3 A at 25% duty cycle
40 mA minimum load current
OUTn
BINARY
(Output)
Power Selection Jumper
positioned to External (
EXT
)
power.
Binary Output Common
(for
OUT
n
terminal)
Note:
Each Binary Output
Common terminal
(OCOM
n
) is isolated
from
all
other
commons, including
other Binary Output
Common terminals.
OCOMn
See Guideline
C
in
Binary Output - 24 VAC Triac
(Internal Power Source)
Sources internal 24 VAC power
(24~ HOT).
OUTn
BINARY
(Output)
Power Selection Jumper
positioned to Internal (
INT
)
power.
Binary Output - 24 VAC Triac
(Internal Power Source)
Connects OCOM
n
to 24~ when
activated.
Internal Power Source:
30 VAC maximum output
voltage
0.5 A maximum output current
1.3 A at 25% duty cycle
40 mA minimum load current
OCOMn
18
FEC26Field Equipment Controllers Installation Instructions