Table 9: DSV120C supply air blower performance
Available external static pressure - IWG*
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
Suppl
y CFM
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Field supplied
low static drive
Standard drive + 1.5HP
Optional hi- 2HP
3200
573 0.48 668 0.62 754 0.76 833 0.88 906 1.02 975 1.18 1040 1.32 1102 1.48 1160 1.66 1225 1.86
3600
621 0.66 708 0.80 788 0.96 863 1.10 933 1.26 999 1.42 1061 1.58 1121 1.74 1178 1.90
-
-
4000
667 0.86 748 1.02 823 1.18 893 1.34 960 1.52 1023 1.68 1083 1.86 1141 2.04
-
-
-
-
4400
723 1.12 797 1.28 868 1.46 934 1.64 997 1.84 1057 2.02
-
-
-
-
-
-
-
~
4800
775 1.40 845 1.60 911 1.80 973 2.00
-
-
-
-
-
-
-
-
-
-
-
~
Note:
At higher evaporator airflows and wet bulb conditions, condensate carry-over may occur.
Decrease airflow downward as necessary.
* Blower performance includes evaporator coil and 2" filters.
Table 10: DSV120C condenser fan performance
Available external static pressure - IWG
0.0
0.2
0.4
0.6
0.8
1.0
1.2
Outdoor
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
Standard factory drive + 3HP
Optional hi- 3HP
5500
614
1.22
680
1.44
741
1.66
799
1.90
854
2.14
906
2.38
956
2.62
Table 11: DSV144C supply air blower performance
Available external static pressure - IWG*
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
Suppl
y CFM
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Field supplied
low static drive
Standard drive + 2HP
Optional hi- 3HP
4000
436 0.48 521 0.64 597 0.80 667 0.98 730 1.16 790 1.34 845 1.54 896 1.75 946 2.01 992 2.29
4400
456 0.58 536 0.76 609 0.94 676 1.12 738 1.32 796 1.52 851 1.72 902 1.82 950 2.17 996 2.52
4800
475 0.70 555 0.88 621 1.08 686 1.28 746 1.48 803 1.70 857 1.92 908 2.14 956 2.36 1000 2.70
5200
494 0.84 567 1.04 634 1.24 697 1.46 755 1.68 811 1.90 863 2.12 913 2.36 961 2.60 1007 2.84
5600
517 1.00 587 1.22 651 1.44 711 1.66 768 1.90 822 2.14 873 2.38 922 2.62 969 2.86
-
-
Note:
At higher evaporator airflows and wet bulb conditions, condensate carry-over may occur.
Decrease airflow downward as necessary.
* Blower performance includes evaporator coil and 2" filters.
Table 12: DSV144C condenser fan performance
Available external static pressure - IWG
0.0
0.2
0.4
0.6
0.8
1.0
1.2
Outdoor
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
Standard factory drive + 3HP
Optional hi- 3HP
6000
535
1.02
609
1.28
679
1.56
744
1.84
805
2.14
862
2.44
921
2.82
33
D-Series Vertical (DSV060C-300C) Air-Cooled Self-Contained Units, C Generation with Smart Equipment Controller
Johnson Controls