background image

5.  Connect 140/R pressure transducer EXEC to the SEC (24V FOR OUTPUT) terminal.

Changing fan speeds

Change the fan speeds on an SEC by changing the parameters in the controller itself. Refer to

Appendix E: SEC parameters for DSV units, C generation

.

Separating the units (DSV060C model)

The DSV060C model's parts can be separated to move it though doorways and elevators. However,

the unit is not designed or certified for installation as a remote condenser and evaporator.

1.  Reclaim the whole refrigerant charge from each compressor circuit.
2.  Disconnect the evaporator motor high voltage wires. Pull all the wiring into the evaporator

compartment. Remove the bushing/clamp from the routing hole for the evaporator motor

wiring.

3.  Cut and remove sections of all the liquid and suction refrigerant lines. Make two cuts in each

line, approximately 6 inches above and below the evaporator floor/condenser roof.

 CAUTION

Use a TUBING CUTTER ONLY - do not use a hacksaw to cut refrigerant tubing otherwise serious

damage can occur to refrigeration system!

4.  Remove the corner securing the brackets from the outside corners of the cabinet, at the joint

line between the evaporator and condenser sections.

5.  Remove the evaporator section.
6.  For assembly instructions, see 

Assembling split units (8–25 ton models)

.

Condensate trap

Condensate trap fitting is provided on all units and is 3/4-inch functional performance testing (FPT).

The unit requires a field installed external condensate trap. Without a trap, condensate can be

thrown into the airstream. This can cause water overflow, unit damage, and property damage.

This system must be trapped according to a negative system pressure (draw-through). Use the

dimensions in Figure 4. Adhere to local codes for piping the external trap and condensate.

Example: trapping a system up to 2 inches external static pressure

Note:

A = (1 inch for each inch of maximum negative static pressure) + 1 inch

B = Half of A

C =A + B + pipe diameter

15

D-Series Vertical (DSV060C-300C) Air-Cooled Self-Contained Units, C Generation with Smart Equipment Controller

Johnson Controls

Summary of Contents for D Series

Page 1: ...rsedes 145 29 IOM4 1119 Installation Guide Issue Date 2020 12 02 Johnson Controls D Series Vertical DSV060C 300C Air Cooled Self Contained Units C Generation with Smart Equipment Controller Installation Operation and Maintenance Manual ...

Page 2: ...2 D Series Vertical DSV060C 300C Air Cooled Self Contained Units C Generation with Smart Equipment Controller Johnson Controls ...

Page 3: ...e units DSV060C model 15 Condensate trap 15 Ductwork 16 Air temperature sensors 16 Louver sizing guidelines 17 Variable frequency drive VFD 18 Indoor fan VFD 18 Outdoor fan VFD 19 Hot gas bypass HGBP 19 Adjusting HGBP setpoint 19 Airside economizer ASE 19 Sequences of operation 20 Dimensions 20 Discharge plenum 22 Low ambient damper installation 24 Evaporator blower discharge conversion 26 Convert...

Page 4: ...ce trip protection and three strikes 42 Lead lag 42 Condensate overflow switch 42 Operation 43 Maintenance and service 45 Evaporator and condenser coils 45 Refrigerant circuits 45 Blowers 45 Drive belts 45 Filters 45 Appendices 47 Appendix A Unit dimensional drawings 47 Appendix B Typical service clearances 65 Appendix C High voltage unit wiring schematics 66 Appendix D Low voltage unit wiring sch...

Page 5: ...possess independent training that will enable them to perform their assigned tasks properly and safely It is essential that prior to performing any task on this equipment this individual shall have read and understood the on product labels this document and any referenced materials This individual shall also be familiar with and comply with all applicable industry and governmental standards and re...

Page 6: ...d electrician The manufacturer will NOT be responsible for damage problems resulting from improper connections to the controls or application of improper control signals Failure to follow this warning will void the manufacturer s warranty and cause serious damage to property or personal injury WARNING This product can expose you to chemicals including formaldehyde which is known to the state of Ca...

Page 7: ...vaporator condenser assembly Nitrogen Warning added July 2020 Associated literature Manual description Form number Mobile Access Portal Gateway Product Bulletin LIT 12011884 Airside Economizer Kit for Models DSH DSV Air Cooled Air Conditioning Units C Generation Installation and Operation Instructions 145 10 NO2 Low Ambient Damper Kit for Air Cooled Self Contained Units DSH DSV Models B C Styles I...

Page 8: ...s and up 2 Evaporator motor VFD standard on 8 ton units and up 3 Condenser VFD not available in 575V 4 Evaporator motor without VFD available only on 2 3 4 and 5 ton D Series Vertical DSV060C 300C Air Cooled Self Contained Units C Generation with Smart Equipment Controller 8 Johnson Controls ...

Page 9: ...requiring operation below this temperature either a low ambient damper field kit accessory or low ambient control featuring a variable frequency drive VFD on condenser fan is available condenser fan VFD is available as a factory installed option only on 8 and 10 ton units The damper is installed on the condenser air discharge and is allowed operation to 0 0 F ambient The VFD on the condenser is fa...

Page 10: ...t to carrier and factory immediately Shipping and handling damages are not warranty items Figure 1 Typical installation configuration D Series Vertical DSV060C 300C Air Cooled Self Contained Units C Generation with Smart Equipment Controller 10 Johnson Controls ...

Page 11: ...t maximum efficiencies choose a dry indoor area where the temperature is controlled between 50 0 F and 115 0 F When choosing a location to install the unit consider the surrounding area Occupants may object to common vibration and sound levels associated with the unit WARNING Failure to allow adequate space between units condenser intake and discharge may result in poor unit performance and possib...

Page 12: ...d into the filter rack Secure floor mounted units on a solid level pad or a sturdy stand Ensure that the unit s base is approximately 6 inches higher than the lower edge of the wall opening This height allows the condenser air ducts to be pitched away from the unit offering protection from rain water entering the base pan see Figure 1 The use of an isolating rubber sheet is recommended to reduce v...

Page 13: ... couplings 5 Ensure that circuit 1 from the condenser connects to the circuit 1 piping in the evaporator Ensure that circuit 2 from the condenser connects to the circuit 2 piping Do not cross the circuits 6 Following common A C service practices braze the copper couplings to the refrigerant pipe using a flow of nitrogen gas max 1 psi through the refrigerant piping This flow minimizes contamination...

Page 14: ...N Do not cross circuits when brazing refrigerant piping between sections Connecting the VFD control wires 1 Connect the VFD 3 pin Molex harness 115 OR 116 R or 117 WH to the SE control SEC terminal P5 2 Connect 151 R to the common terminal on the EVFR relay in the condenser box 3 Connect 152 OR to the NO terminal on EVFR relay in the condenser box 4 For variable air volume VAV units connect the pr...

Page 15: ... not use a hacksaw to cut refrigerant tubing otherwise serious damage can occur to refrigeration system 4 Remove the corner securing the brackets from the outside corners of the cabinet at the joint line between the evaporator and condenser sections 5 Remove the evaporator section 6 For assembly instructions see Assembling split units 8 25 ton models Condensate trap Condensate trap fitting is prov...

Page 16: ...ion and reduce the accumulation of dust and debris To not exceed the maximum external static values refer to blower performance charts in Fan performance engineer duct runs and accessory pressure drop Ensure continuous running of the condenser intake ambient air temperature does not exceed 115 0 F The condenser exhaust discharges into an open area to prevent the short cycling of hot exhaust conden...

Page 17: ...d then the restriction of any interconnecting ductwork The DSH s indoor air cooled air conditioners are designed to accommodate the external static pressure loss associated with properly sized storm proof louvers A storm proof louver typically has a free area approximately 40 45 of the actual louver size To determine the free area required for any given unit adhere to the following guidelines The ...

Page 18: ... for three automatically adjusted discrete speeds 15 20 and 25 ton units feature 4 discrete speed steps In both cases the discrete fan speeds are matched and adjusted automatically based on the active cooling stage Note The unit does not carry a failsafe circuit to bypass the factory installed VFD and run the evaporator or condenser fan in the event of a VFD malfunction The VFD is factory mounted ...

Page 19: ...oil temperature by adjusting the screw on the HGBP valve To set the load run the unit and cool down the evaporator coil To do this either shut the fans or block the airflow until the suction pressure drops at least 5 psi below the chosen evaporator coil setpoint Next allow the bypassed gas to raise the pressure The screw spring adjustment can be set until the HGBP valve closes at the chosen setpoi...

Page 20: ...T plus 9 0 F If the OAT rises above the RAT plus 10 0 F free cooling is no longer available The OAT must drop to no greater than RAT plus 9 0 F to enter free cooling again Free cooling is no longer available if the OA enthalpy rises above the economizer OA enthalpy setpoint For dual enthalpy economizer operation the OA enthalpy must be lower than the RA enthalpy by 1 Btu lb and the OAT is no great...

Page 21: ...Economizer features 21 D Series Vertical DSV060C 300C Air Cooled Self Contained Units C Generation with Smart Equipment Controller Johnson Controls ...

Page 22: ...lle and single side grilles The 12 25 ton models come with double front grilles and single side grilles The discharge plenum is made of heavy gauge sheet metal with supply grilles mounted on three sides front left and right sides It is secured to the unit using the included four corner brackets Table 2 Plenum dimensions Model W D H Side grille Front grille DSV060C 52 29 24 16x12 2x 32x12 DSV096C 7...

Page 23: ...86 5 34 28 24x20 2x 28x20 2x DSV240C 90 5 34 28 24x20 2x 32x20 2x DSV300C 108 5 34 28 24x20 2x 32x20 2x Figure 8 Evaporator with discharge plenum 23 D Series Vertical DSV060C 300C Air Cooled Self Contained Units C Generation with Smart Equipment Controller Johnson Controls ...

Page 24: ...the refrigerant pressure Depending on a proportional pressure control module s output signal a direct coupled electric damper actuator motor drives the damper open or closed A pressure transducer senses the high side refrigerant pressure through a service access port The port is located on the liquid refrigerant line leaving the condenser The pressure controller complete with terminal connection b...

Page 25: ...cuit liquid line fitting Connection to the second stage refrigerant circuit will result in system malfunction For detailed installation instructions refer to the supplementary Low Ambient Damper Kit Installation and Operation Instructions Form 145 10 IOM4 Figure 11 Low ambient dampers Kit Model A B C VADK 060C 1 DSV060C 47 375 in 5 0 in 11 875 in VADK 120C 1 DSV096C DSV120C 66 375 in 5 0 in 14 125...

Page 26: ...evaporator coil during the removal On some models the housings have to be rotated to exit through the panel opening 5 Interchange the blower panel assembly with the position of the alternate access panel Exercise care in locating the panel Do not allow blower housings to contact the evaporator coil Install the attachment screws and tighten securely 6 Install the blank access panel into the remaini...

Page 27: ...iple stage thermostat up to four cooling stages must be used depending on size of the unit Locate the thermostat on an inside wall approximately 56 inches above the floor At this location it is not subject to drafts sun exposure or heat from electrical fixtures or appliances Follow the manufacturer s instructions enclosed with the thermostat for the general installation procedure Use the seven col...

Page 28: ...ing three stage heating for DSH096C DSV120C and DSV144C Note 1 Unit is capable of supporting up to 3 stages of discrete heating 2 Unit is designed to support 3 stages of discrete cooling 3 Jumper is required for any combination of R RC or RH 4 OCC is an output from the thermostat to indicate the Occupied condition 5 X in an input to thermostat to display Error Status 6 Jumper is required if no opt...

Page 29: ...ort 4 stages of discrete cooling 3 Jumper is required for any combination of R RC or RH 4 OCC is an output from the thermostat to indicate the Occupied condition 5 X in an input to thermostat to display Error Status 6 Jumper is required if no options are installed between SD 24 and SD R 29 D Series Vertical DSV060C 300C Air Cooled Self Contained Units C Generation with Smart Equipment Controller J...

Page 30: ...9 43 100 DSV180C4 460 3 60 2 9 6 84 0 3 00 4 2 5 00 6 6 32 40 40 DSV180C5 575 3 60 2 8 4 60 0 3 00 3 4 5 00 5 3 27 60 35 DSV240C2 208 230 3 60 2 32 6 240 0 5 00 14 0 7 50 20 4 107 75 125 DSV240C4 460 3 60 2 14 8 130 0 5 00 6 6 7 50 9 7 49 60 60 DSV240C5 575 3 60 2 11 1 93 7 5 00 5 3 7 50 7 8 38 08 45 DSV300C2 208 230 3 60 2 35 4 240 0 7 50 20 4 10 00 25 0 125 05 150 DSV300C4 460 3 60 2 16 5 140 0 ...

Page 31: ... 3 00 3 4 3 00 3 4 22 08 25 DSV180C2 208 230 3 60 2 25 3 184 0 5 00 14 0 5 00 14 0 84 93 110 DSV180C4 460 3 60 2 9 6 84 0 5 00 6 6 5 00 6 6 34 80 40 DSV180C5 575 3 60 2 8 4 60 0 5 00 5 3 5 00 5 3 29 50 35 DSV240C2 208 230 3 60 2 32 6 240 0 7 50 20 4 7 50 20 4 114 15 125 DSV240C4 460 3 60 2 14 8 130 0 7 50 9 7 7 50 9 7 52 70 60 DSV240C5 575 3 60 2 11 1 93 7 7 50 7 8 7 50 7 8 40 58 50 DSV300C2 208 2...

Page 32: ... 1 15 938 1 33 1006 1 50 Table 7 DSV096C supply air blower performance Available external static pressure inches W C 0 2 0 4 0 6 0 8 1 0 1 2 1 4 1 6 1 8 2 0 Supp ly CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP Low static drive Standard factory drive 1HP Optional hi static 1 5HP 2600 496 0 28 605 0 40 701 0 50 788 0 62 868 0 74 947 0 89 1016 1 04 1045 1 19 107...

Page 33: ...144C supply air blower performance Available external static pressure IWG 0 2 0 4 0 6 0 8 1 0 1 2 1 4 1 6 1 8 2 0 Suppl y CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP Field supplied low static drive Standard drive 2HP Optional hi static 3HP 4000 436 0 48 521 0 64 597 0 80 667 0 98 730 1 16 790 1 34 845 1 54 896 1 75 946 2 01 992 2 29 4400 456 0 58 536 0 76 60...

Page 34: ...82 2 04 742 2 37 800 2 70 854 3 03 906 3 36 Table 15 DSV240C supply air blower performance Available external static pressure inches W C 0 0 0 2 0 4 0 6 0 8 1 0 1 2 1 4 1 6 1 8 2 0 Suppl y CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP Field supplied low static drive Standard drive 5HP Optional hi static 7 5HP Field supplied hi static drive 6400 536 1 2...

Page 35: ...tatic pressure IWG 0 0 0 2 0 4 0 6 0 8 1 0 1 2 Outdo or CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP Standard factory drive 7 5HP Field supplied hi static 7 5HP 12800 735 4 41 790 4 98 843 5 55 894 6 15 944 6 78 992 7 41 1031 8 01 Motor and pulley data Table 19 Evaporator standard blower motor and drive data Motor Adjustable motor pulley Fixed blower pulley Model Drive range RPM HP ...

Page 36: ...00 fan speed condition Perform an air balance after installation to verify the airflow and static This may require adjustments to the drive Refer to the Variable Frequency Drive manual Form 145 13 NO2 Only operate the unit in the regions defined by the fan tables The units can be ordered with oversized motors or drive kits for high static requirements Note Units with oversized motors or oversized ...

Page 37: ...ull turns 5 Replace the external key and tighten the adjustment setscrew Proper torque is 110 130 inches lbs 6 Install the drive belt and adjust the motor mount to the tension belt for further information see the Maintenance and service section 37 D Series Vertical DSV060C 300C Air Cooled Self Contained Units C Generation with Smart Equipment Controller Johnson Controls ...

Page 38: ... for a short period of time under one hour However after several minutes of operation the compressors internal protectors trip If opposite rotation is needed disconnect and reverse any two leads of the three phase supply Then reconnect the power Table 23 Pressure switch settings all models High Low Cut out PSIG 625 68 Cut in PSIG 500 107 Table 24 Refrigerant charge lbs Unit Circuit 1 Circuit 2 DSV...

Page 39: ...le 25 from the discharge pressure to determine the equivalent saturation temperature For example when the discharge pressure is 388 psig and the liquid line temperature is 95 0 F Liquid Pressure Discharge Pressure 388 psig minus 33 psig 355 psig Saturation Temperature for 355 psig 108 0 F Liquid Line Subcooling Saturation Temperature 108 0 F minus Liquid Line Temperature 95 0 13 0 F Subcooling sho...

Page 40: ...pressure is 130 psig and the suction line temperature is 57 0 F Saturation Temperature for 130 psig 45 0 F Evaporator Superheat Suction Line Temperature 57 0 F minus Saturation Temperature 45 0 F 12 0 F When adjusting the expansion valve do not turn the adjusting screw more than one turn at a time This allows sufficient time approximately 15 minutes between adjustments for the system and the therm...

Page 41: ...oller Units come with the state of the art Smart Equipment control SEC system All units are factory commissioned configured and run tested The SEC can be configured to use with a standard thermostat a zone sensor or to communicate with the field controller FC bus using BACnet MS TP Modbus or N2 protocols Temperature sensors Each unit comes with standard supply air temperature SAT and return air te...

Page 42: ...g and cooling fan delay times are independent of one another All units are programmed with default values based upon their cooling or heating capacity configuration Nuisance trip protection and three strikes To prevent nuisance calls the control board has three soft faults before a hard lock out operation The high low pressure switch anti freeze protection low voltage or heating high limit must tr...

Page 43: ...ple stages are requested 5 Here is the sequence of operation for a four stage unit Y1 energizes Compressor 1 stage 1 Y2 energizes Compressor 2 stage 1 Y3 energizes Compressor 2 stage 2 Y4 energizes Compressor 1 stage 2 6 Here is the sequence of operation for a three stage unit Y1 energizes Compressor 1 stage 1 Y2 energizes Compressor 1 stage 2 Y3 energizes Compressor 2 IntelliSpeed supply fan cont...

Page 44: ...on UCB operates the supply fan VFD proportional to the minimum and maximum frequency settings of the VFD the defaults are 30 60hz The supply fan only operation is as follows When there is no demand for heating or cooling to run the supply fan operates at the percent output of the no heat or cool command setpoint The cooling supply fan operation is as follows With a demand for cooling the VFD opera...

Page 45: ...heels Bearings are a permanently sealed ball type and do not require lubrication Check the bearings for signs of wear movement between the inner and outer races Ensure that the bearing locking collars are secure to the shaft and that the collar locking screw is properly set Check that the blower wheel is tight on the shaft and that the hub set screws are properly torqued Drive belts Examine the be...

Page 46: ...x18x2 2 20x18x2 DSV144C 8 20x18x2 DSV180C 3 20x18x2 1 24x18x2 3 20x20x2 1 24x20x2 DSV240C 4 24x20x2 4 20x20x2 DSV300C 6 25x18x2 6 20x18x2 Figure 16 Belt tension adjustment D Series Vertical DSV060C 300C Air Cooled Self Contained Units C Generation with Smart Equipment Controller 46 Johnson Controls ...

Page 47: ...Appendix A Unit dimensional drawings Figure 17 DSV060C dimensional data top discharge 47 D Series Vertical DSV060C 300C Air Cooled Self Contained Units C Generation with Smart Equipment Controller Johnson Controls ...

Page 48: ...Figure 18 DSV096C and DSV120C dimensional data front discharge D Series Vertical DSV060C 300C Air Cooled Self Contained Units C Generation with Smart Equipment Controller 48 Johnson Controls ...

Page 49: ...Figure 19 DSV096C and DSV120C dimensional data front discharge 49 D Series Vertical DSV060C 300C Air Cooled Self Contained Units C Generation with Smart Equipment Controller Johnson Controls ...

Page 50: ...Figure 20 DSV096C and DSV120C dimensional data top discharge D Series Vertical DSV060C 300C Air Cooled Self Contained Units C Generation with Smart Equipment Controller 50 Johnson Controls ...

Page 51: ...Figure 21 DSV144C dimensional data front discharge 51 D Series Vertical DSV060C 300C Air Cooled Self Contained Units C Generation with Smart Equipment Controller Johnson Controls ...

Page 52: ...Figure 22 DSV144C dimensional data top discharge D Series Vertical DSV060C 300C Air Cooled Self Contained Units C Generation with Smart Equipment Controller 52 Johnson Controls ...

Page 53: ...Figure 23 DSV180C dimensional data front discharge rear return 53 D Series Vertical DSV060C 300C Air Cooled Self Contained Units C Generation with Smart Equipment Controller Johnson Controls ...

Page 54: ...Figure 24 DSV180C dimensional data top discharge rear return D Series Vertical DSV060C 300C Air Cooled Self Contained Units C Generation with Smart Equipment Controller 54 Johnson Controls ...

Page 55: ...Figure 25 DSV180C dimensional data front return rear discharge 55 D Series Vertical DSV060C 300C Air Cooled Self Contained Units C Generation with Smart Equipment Controller Johnson Controls ...

Page 56: ...Figure 26 DSV180C dimensional data front return top discharge D Series Vertical DSV060C 300C Air Cooled Self Contained Units C Generation with Smart Equipment Controller 56 Johnson Controls ...

Page 57: ...Figure 27 DSV240C dimensional data front discharge rear return 57 D Series Vertical DSV060C 300C Air Cooled Self Contained Units C Generation with Smart Equipment Controller Johnson Controls ...

Page 58: ...Figure 28 DSV240C dimensional data top discharge rear return D Series Vertical DSV060C 300C Air Cooled Self Contained Units C Generation with Smart Equipment Controller 58 Johnson Controls ...

Page 59: ...Figure 29 DSV240C dimensional data rear discharge front return 59 D Series Vertical DSV060C 300C Air Cooled Self Contained Units C Generation with Smart Equipment Controller Johnson Controls ...

Page 60: ...Figure 30 DSV240C dimensional data top discharge front return D Series Vertical DSV060C 300C Air Cooled Self Contained Units C Generation with Smart Equipment Controller 60 Johnson Controls ...

Page 61: ...Figure 31 DSV300C dimensional data front discharge rear return 61 D Series Vertical DSV060C 300C Air Cooled Self Contained Units C Generation with Smart Equipment Controller Johnson Controls ...

Page 62: ...Figure 32 DSV300C dimensional data top discharge rear return D Series Vertical DSV060C 300C Air Cooled Self Contained Units C Generation with Smart Equipment Controller 62 Johnson Controls ...

Page 63: ...Figure 33 DSV300C dimensional data rear discharge front return 63 D Series Vertical DSV060C 300C Air Cooled Self Contained Units C Generation with Smart Equipment Controller Johnson Controls ...

Page 64: ...Figure 34 DSV300C dimensional data top discharge front return D Series Vertical DSV060C 300C Air Cooled Self Contained Units C Generation with Smart Equipment Controller 64 Johnson Controls ...

Page 65: ...Appendix B Typical service clearances Figure 35 Typical clearance services 65 D Series Vertical DSV060C 300C Air Cooled Self Contained Units C Generation with Smart Equipment Controller Johnson Controls ...

Page 66: ... voltage unit wiring schematics Figure 36 DSV060C vertical A C unit 208 230 460 575 3 60 D Series Vertical DSV060C 300C Air Cooled Self Contained Units C Generation with Smart Equipment Controller 66 Johnson Controls ...

Page 67: ...Figure 37 DSV096 120 144C vertical A C unit 208 230 460 575 3 60 67 D Series Vertical DSV060C 300C Air Cooled Self Contained Units C Generation with Smart Equipment Controller Johnson Controls ...

Page 68: ...D Series Vertical DSV060C 300C Air Cooled Self Contained Units C Generation with Smart Equipment Controller 68 Johnson Controls ...

Page 69: ...Figure 38 DSV180C vertical A C unit 208 230 3 60 69 D Series Vertical DSV060C 300C Air Cooled Self Contained Units C Generation with Smart Equipment Controller Johnson Controls ...

Page 70: ...Figure 39 DSV180C vertical A C unit 460 575 3 60 D Series Vertical DSV060C 300C Air Cooled Self Contained Units C Generation with Smart Equipment Controller 70 Johnson Controls ...

Page 71: ...Figure 40 DSV240C vertical A C unit 208 230 3 60 71 D Series Vertical DSV060C 300C Air Cooled Self Contained Units C Generation with Smart Equipment Controller Johnson Controls ...

Page 72: ...Figure 41 DSV240C vertical A C unit 460 575 3 60 D Series Vertical DSV060C 300C Air Cooled Self Contained Units C Generation with Smart Equipment Controller 72 Johnson Controls ...

Page 73: ...Figure 42 DSV300C vertical A C unit 208 230 3 60 73 D Series Vertical DSV060C 300C Air Cooled Self Contained Units C Generation with Smart Equipment Controller Johnson Controls ...

Page 74: ...Figure 43 DSV300C vertical A C unit 460 3 60 D Series Vertical DSV060C 300C Air Cooled Self Contained Units C Generation with Smart Equipment Controller 74 Johnson Controls ...

Page 75: ...Figure 44 DSV300C vertical A C unit 575 3 60 75 D Series Vertical DSV060C 300C Air Cooled Self Contained Units C Generation with Smart Equipment Controller Johnson Controls ...

Page 76: ...Low voltage unit wiring schematics Figure 45 DSV060C vertical A C unit control wiring D Series Vertical DSV060C 300C Air Cooled Self Contained Units C Generation with Smart Equipment Controller 76 Johnson Controls ...

Page 77: ...Figure 46 DSV096 120 144C vertical A C unit control wiring 77 D Series Vertical DSV060C 300C Air Cooled Self Contained Units C Generation with Smart Equipment Controller Johnson Controls ...

Page 78: ...D Series Vertical DSV060C 300C Air Cooled Self Contained Units C Generation with Smart Equipment Controller 78 Johnson Controls ...

Page 79: ...Figure 47 DSV180 240 300C vertical A C unit control wiring 79 D Series Vertical DSV060C 300C Air Cooled Self Contained Units C Generation with Smart Equipment Controller Johnson Controls ...

Page 80: ...D Series Vertical DSV060C 300C Air Cooled Self Contained Units C Generation with Smart Equipment Controller 80 Johnson Controls ...

Page 81: ...Figure 48 DSV060 300C vertical A C unit economizer 81 D Series Vertical DSV060C 300C Air Cooled Self Contained Units C Generation with Smart Equipment Controller Johnson Controls ...

Page 82: ...2 No Lead Lag En 3 No Clg OAT Cutout En Yes Clg OAT Cutout 45 Clg Adap Tune En No SAT Cool Limit En Yes Sat Cool Limit SP 45 Cooling Freeze SP 26 Htg En 4 No Heating Htg Stgs 0 Fan Ctl Type Single Speed Fan On Dly Cool 0 Details Fan Setup Fan Off Dly Cool 45 Note 1 Factory shipped units equipped with Occ jumper on UCB 2 Do not enable low ambient 3 Do not enable LeadLag 4 Field supplied option D Se...

Page 83: ...Yes Clg OAT Cutout 45 SAT Cool Limit En Yes Sat Cool Limit SP 45 Cooling Freeze SP 26 Htg En 4 No Heating Htg Stgs 0 Fan Ctl Type Variable Fan On Dly Cool 0 Fan Fan Off Dly Cool 30 Dct Prs SP 5 1 5 IWG Details Fan VFD Setup Dct ShutDown SP 5 4 5 IWG Note 1 Factory shipped units equipped with Occ jumper on UCB 2 Do not enable low ambient 3 Do not enable LeadLag 4 Field supplied option 5 Field set p...

Page 84: ...OAT Cutout 45 SAT Cool Limit En Yes Sat Cool Limit SP 45 Cooling Freeze SP 26 Htg En 4 No Heating Htg Stgs 0 Fan Ctl Type Fixed Variable Fan On Occ No Fan On Dly Cool 0 Fan Off Dly Cool 30 Fan Only Cmd 0 1 Clg Stg Cmd 50 2 Clg Stg Cmd 60 3 Clg Stg Cmd 100 Details Fan Setup 4 Clg Stg Cmd 100 Note 1 Factory shipped units equipped with Occ jumper on UCB 2 Do not enable low ambient 3 Do not enable Lea...

Page 85: ...Yes Clg OAT Cutout 45 SAT Cool Limit En Yes Sat Cool Limit SP 45 Cooling Freeze SP 26 Htg En 4 No Heating Htg Stgs 0 Fan Ctl Type Variable Fan On Dly Cool 0 Fan Fan Off Dly Cool 30 Dct Prs SP 5 1 5 IWG Details Fan VFD Setup Dct ShutDown SP 5 4 5 IWG Note 1 Factory shipped units equipped with Occ jumper on UCB 2 Do not enable low ambient 3 Do not enable LeadLag 4 Field supplied option 5 Field set p...

Page 86: ... OAT Cutout 45 SAT Cool Limit En Yes Sat Cool Limit SP 45 Cooling Freeze SP 26 Htg En 4 No Heating Htg Stgs 0 Fan Ctl Type Fixed Variable Fan On Occ No Fan On Dly Cool 0 Fan Off Dly Cool 30 Fan Only Cmd 0 1 Clg Stg Cmd 50 2 Clg Stg Cmd 60 3 Clg Stg Cmd 75 Details Fan Setup 4 Clg Stg Cmd 100 Note 1 Factory shipped units equipped with Occ jumper on UCB 2 Do not enable low ambient 3 Do not enable Lea...

Page 87: ... service pressure rating of 800 psig Leak detectors must be designed to detect HFC refrigerants Systems must be charged with refrigerant Use a commercial type metering device in the manifold hose R 410A can only be used with polyester POE type oils POE type oils rapidly absorb moisture from the atmosphere Vacuum pumps do not remove moisture from POE type oils Do not use liquid line driers with a r...

Page 88: ...Notes 2020 Johnson Controls All rights reserved Subject to change without notice 100 JCI Way York Pennsylvania USA 17406 8469 Johnson Controls ...

Reviews: