Table 13: DSV180C supply air blower performance
Available external static pressure - inches W.C.
0.0
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
Supply
CFM
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Field supplied
low static drive
Standard drive + 2HP
Optional hi- 5HP
Field supplied hi-
static drive +5 HP
4500
509 0.54 613 0.75 705 0.93 789 1.11 867 1.32 939 1.53 1006 1.74 1071 1.95 1131 2.19
5000
566 0.75 660 0.96 746 1.17 825 1.38 898 1.59 967 1.83 1032 2.04 1094 2.28 1153 2.52
5500
623 1.02 709 1.23 789 1.47 863 1.68 933 1.92 998 2.16 1061 2.40 1121 2.67 1178 2.91
6000
679 1.32 759 1.56 833 1.80 903 2.04 969 2.31 1032 2.55 1092 2.82 1150 3.09 1205 3.36
6500
736 1.68 810 1.95 879 2.19 945 2.46 1008 2.73 1068 3.03 1125 3.30 1181 3.57 1234 3.87
7000
792 2.10 862 2.37 927 2.67 989 2.94 1049 3.24 1106 3.54 1161 3.84 1214 4.14 1266 4.44
Note:
At higher evaporator airflows and wet bulb conditions, condensate carry-over may occur.
Decrease airflow downward as necessary.
* Blower performance includes evaporator coil and 2" filters.
Table 14: DSV180C condenser fan performance
Available external static pressure - IWG
0.0
0.2
0.4
0.6
0.8
1.0
1.2
Outdoor
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
Standard factory drive + 5HP
Optional hi- 5HP
Field supplied hi- 5HP
7200
548
1.44
618
1.74
682
2.04
742
2.37
800
2.70
854
3.03
906
3.36
Table 15: DSV240C supply air blower performance
Available external static pressure - inches W.C.
0.0
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
Suppl
y CFM
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Field supplied low static drive
Standard drive + 5HP
Optional hi- 7.5HP
Field supplied hi-
static drive
6400
536 1.28 606 1.56 671 1.86 733 2.16 792 2.50 849 2.84 904 3.20 956 3.56 1007 3.94 1055 4.32 1102 4.72
7200
601 1.76 665 2.08 724 2.40 781 2.74 836 3.10 889 3.48 940 3.86 989 4.24 1037 4.66 1084 5.06 1128 5.48
8000
668 2.42 725 2.76 780 3.12 832 3.50 883 3.88 932 4.28 979 4.70 1026 5.12 1071 5.54 1115 5.98 1158 6.44
8800
735 3.22 787 3.60 837 3.98 886 4.40 932 4.80 978 5.24 1023 5.68 1066 6.12 1109 6.58 1150 7.06 1191 7.54
9600
802 4.18 850 4.60 896 5.02 941 5.44 985 5.90 1027 6.36 1069 6.82 1110 7.30 1150 7.80 -
-
-
-
Note:
At higher evaporator airflows and wet bulb conditions, condensate carry-over may occur.
Decrease airflow downward as necessary.
* Blower performance includes evaporator coil and 2" filters.
Table 16: DSV240C condenser fan performance
Available external static pressure - IWG
0.0
0.2
0.4
0.6
0.8
1.0
1.2
Outdo
or CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
Standard factory drive + 7.5HP
Field supplied hi- 7.5HP
7200
748
3.99
799
4.41
848
4.86
895
5.34
940
5.79
984
6.27
1026
6.75
D-Series Vertical (DSV060C-300C) Air-Cooled Self-Contained Units, C Generation with Smart Equipment Controller