Fan performance
Table 5: DSV060C supply air blower performance
Available external static pressure - IWG*
0.0
0.2
0.4
0.6
0.8
1.0
1.2
1.4
Supply
CFM
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Field supplied
low static drive
Standard drive + 1HP
Optional hi- 1.5HP
1600
408
0.13
555
0.29
652
0.38
739
0.45
819
0.54
893
0.63
963
0.71 1029 0.81
1800
459
0.20
600
0.39
689
0.48
770
0.58
846
0.66
917
0.76
984
0.86 1047 0.96
2000
510
0.25
647
0.51
729
0.61
806
0.71
877
0.81
944
0.92 1008 1.00 1069 1.14
2200
561
0.35
695
0.65
772
0.76
843
0.88
911
0.99
975
1.10 1036 1.23 1094 1.34
2400
612
0.45
745
0.83
816
0.95
883
1.07
947
1.19 1008 1.31 1066 1.44 -
-
Note:
At higher evaporator airflows and wet bulb conditions, condensate carry-over may occur.
Decrease airflow downward as necessary.
* Blower performance includes evaporator coil and 2" filters.
Table 6: DSV060C condenser fan performance
Available external static pressure - IWG
0.0
0.2
0.4
0.6
0.8
1.0
1.2
Outdoor
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
Standard factory drive 1.5HP
Hi-static drive
3100
513
0.50
615
0.65
706
0.80
790
0.98
867
1.15
938
1.33
1006
1.50
Table 7: DSV096C supply air blower performance
Available external static pressure - inches W.C.
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
Supp
ly
CFM RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Low static drive
Standard factory drive + 1HP
Optional hi- 1.5HP
2600
496 0.28 605 0.40 701 0.50 788 0.62 868 0.74 947 0.89 1016 1.04 1045 1.19 1075 1.35 1105 1.50
2900
514 0.36 618 0.48 710 0.60 794 0.72 872 0.86 944 0.98 1017 1.12 1075 1.28 1128 1.42
-
-
3200
538 0.44 636 0.58 725 0.70 806 0.84 881 0.98 952 1.12 1018 1.26 1081 1.42
-
-
-
-
3500
571 0.56 664 0.70 748 0.84 826 0.98 898 1.14 967 1.28 1031 1.44
-
-
-
-
-
-
3800
613 0.70 700 0.86 779 1.00 853 1.16 923 1.32 989 1.48
-
-
-
-
-
-
-
-
Note:
At higher evaporator airflows and wet bulb conditions, condensate carry-over may occur.
Decrease airflow downward as necessary.
* Blower performance includes evaporator coil and 2" filters.
Table 8: DSV096C condenser fan performance
Available external static pressure - IWG
0.0
0.2
0.4
0.6
0.8
1.0
1.2
Outdoor
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
Standard factory drive + 2HP
Optional hi- 2HP
4400
478
0.60
560
0.78
634
0.96
702
1.14
765
1.34
824
1.54
880
1.74
D-Series Vertical (DSV060C-300C) Air-Cooled Self-Contained Units, C Generation with Smart Equipment Controller
32
Johnson Controls