1-WAY CASSETTE
TC-18002
2-7
2.9 Electrical Data
VOL: Rated Unit Power Supply Voltage (V)
PH: Phase (
f
)
HZ: Frequency (Hz)
MCA: Minimum Circuit Ampacity (A)
MFA: Maximum Fuse Ampacity (A)
OPT: Rated Motor Output (kW)
FLA: Full Load Ampacity (A)
Model
Unit Main Power
Applicable Voltage
Power Supply
Indoor
Fan Motor
Unit
VOL
PH HZ Maximum Minimum
MCA
MFA
OPT
FLA
(H,Y,C)IC1006B21S
208/230
1 60
253
188
0.2
15
0.050
0.2
(H,Y,C)IC1008B21S
0.3
15
0.050
0.2
(H,Y,C)IC1012B21S
0.4
15
0.050
0.3
(H,Y,C)IC1015B21S
0.5
15
0.050
0.4
NOTE:
Power supply voltage should be satisfied with the following.
Supply Voltage:
Rated Voltage within ±10%
Starting Voltage: Rated Voltage within -15%
Operating Voltage: Rated Voltage within ±10%