CD-Wxx-00-0 Series Wall Mount CO

2

 Transmitter Installation Instructions    

7

8.  Reconnect the wires to the relay screw terminal.

9.  Reconnect power to the transmitter.

10.  Reposition the cover, shown in Figure 3.

Testing the Relay and Display Module

To confirm that the the relay and display are operating
correctly, perform the following procedure:

1.  Test the relay following Step 1 through Step 10 in

the previous section, 

Testing the Relay Module

.

Note:

When the relay contacts are closed, the yellow
LED next to the display should be on.

2. A 

CO

concentration should be displayed. If not,

replace the unit.

3.  Reposition the cover. (See Figure 3.)

Testing the Temperature Module

To confirm that the temperature module is operating
correctly, perform the following procedure:
1.  Temporarily turn off power to the unit.

2.  Observing polarity, connect a voltmeter across the

screw terminals  and – (see Figure 10).

3.  Apply power to the transmitter.

4.  Apply heat to the temperature sensor by gently

holding it between a finger and thumb (see
Figure 10).

5.  Verify that the voltage reading rises. If no increase

is noted, replace the module.

6.  Disconnect power to the transmitter.

7.  Disconnect the voltmeter from the temperature

module screw terminals.

8.  Apply power to the transmitter.

9.  Reposition the cover. (See Figure 3.)

Repairs and Replacement

The following modules are replaceable:

 Relay 

Module 

ACC-CD-R

  Relay and Display Module ACC-CD-DR

  Temperature Module ACC-CD-A

Summary of Contents for CD-W-00-0 Series

Page 1: ...ications Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his her own expense Canadian C...

Page 2: ...le Base Two No 6 Self Tapping Screws Provided Figure 2 Surface Mounting to Drywall 3 Insert the spring clips as shown in Figure 2 Use the spacers for 3 8 or 1 2 in drywall Note Replacement spring clip...

Page 3: ...es of 18 to 30 VDC or 20 to 30 VAC Although the power input includes a halfwave rectifier to avoid current peaks use a DC supply current consumption peak 170 mA average 85 mA 24 VAC Power Supply Conne...

Page 4: ...do not discard the jumper 5 If the unit has an optional accessory relay relay and display or temperature module follow the procedure described in the applicable wiring section before repositioning th...

Page 5: ...ted for the following output signal 0 to 10V proportional to CO2 concentration 0 to 2 000 ppm altitude range of 0 to 1 969 ft 0 to 600m above sea level without compensation default relay output trigge...

Page 6: ...ng procedure 1 Temporarily turn off power to the unit 2 Temporarily remove wires connected to the relay screw terminal 3 Connect a multimeter to the relay terminals 4 Read the resistance level to dete...

Page 7: ...See Figure 3 Testing the Temperature Module To confirm that the temperature module is operating correctly perform the following procedure 1 Temporarily turn off power to the unit 2 Observing polarity...

Page 8: ...A Maximum Output Voltage 12 5V Relay Contact Ratings Optional 30V 0 5 A Class 2 Analog Temperature Module Optional Linear 0 to 10 VDC for 32 to 122 F 0 to 50 C Resolution of CO2 Output 10 ppm Recommen...

Reviews: