background image

2

    CD-Wxx-00-0 Series Wall Mount CO

2

 Transmitter Installation Instructions

Surface Mounting

Use the following procedure to mount the CO

2

transmitter to a drywall surface:
1.  Using a hole saw with a 1-3/8 in. blade, drill the

center hole in the surface where the sensor will be
mounted, then pull the wiring through the drilled
hole.

2.  Using only the drywall mounting holes indicated in

Figure 1, mark the location of the two mounting
holes and drill the 1/8 in. holes.

Center

Hole

Drywall
Mounting
Hole

Drywall
Mounting
Hole

Wallbox
Mounting
Hole

Wallbox
Mounting
Hole

Figure 1: Transmitter Base

Spacer (2) for

3/8 in. (9.5 mm) and 1/2 in.

(12.7 mm) Thick Drywall

1-3/8 in.

 (35 mm)

Hole

Drywall

Drywall

Spring
Clip (2)

Top View

 Drywall

Spring 

Clips (2)

1-3/8 in.

(35 mm)

Hole

 Base

Two No. 6 

Self-Tapping

Screws (Provided)

Figure 2: Surface Mounting to Drywall

   

3.  Insert the spring clips as shown in Figure 2. (Use

the spacers for 3/8 or 1/2 in. drywall.)

Note:

Replacement spring clips, spacers, and
screws can be ordered separately as the
Drywall Mounting Kit (ACC-DWCLIP-0).

4.  Pull the wiring through the base’s center hole.

5.  Center the two holes in the base over the drilled

holes, and fasten the base to the drywall using the
No. 6 screws provided (Figure 1 and Figure 2).

!

  CAUTION:

When mounting to drywall, use

the specified holes (see Figure 2) with the provided
spring clips. Other mounting may cause the screws
to damage the PCB or cause a short circuit.

IMPORTANT:

To prevent drywall damage,

do not overtighten the screws.

6.  To install the PCB into the base, refer to Figure 3

and:

  align the PCB over the latch pins on the base.

  press down on the board until it snaps into

place and is secured by the latches.

7.  Proceed to the 

Wiring

 section.

Summary of Contents for CD-W-00-0 Series

Page 1: ...ications Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his her own expense Canadian C...

Page 2: ...le Base Two No 6 Self Tapping Screws Provided Figure 2 Surface Mounting to Drywall 3 Insert the spring clips as shown in Figure 2 Use the spacers for 3 8 or 1 2 in drywall Note Replacement spring clip...

Page 3: ...es of 18 to 30 VDC or 20 to 30 VAC Although the power input includes a halfwave rectifier to avoid current peaks use a DC supply current consumption peak 170 mA average 85 mA 24 VAC Power Supply Conne...

Page 4: ...do not discard the jumper 5 If the unit has an optional accessory relay relay and display or temperature module follow the procedure described in the applicable wiring section before repositioning th...

Page 5: ...ted for the following output signal 0 to 10V proportional to CO2 concentration 0 to 2 000 ppm altitude range of 0 to 1 969 ft 0 to 600m above sea level without compensation default relay output trigge...

Page 6: ...ng procedure 1 Temporarily turn off power to the unit 2 Temporarily remove wires connected to the relay screw terminal 3 Connect a multimeter to the relay terminals 4 Read the resistance level to dete...

Page 7: ...See Figure 3 Testing the Temperature Module To confirm that the temperature module is operating correctly perform the following procedure 1 Temporarily turn off power to the unit 2 Observing polarity...

Page 8: ...A Maximum Output Voltage 12 5V Relay Contact Ratings Optional 30V 0 5 A Class 2 Analog Temperature Module Optional Linear 0 to 10 VDC for 32 to 122 F 0 to 50 C Resolution of CO2 Output 10 ppm Recommen...

Reviews: