Johnson Controls CD-W-00-0 Series Installation Instructions Manual Download Page 5

CD-Wxx-00-0 Series Wall Mount CO

2

 Transmitter Installation Instructions    

5

3.  Plug the relay and display module into the 5-pin

(X3) and two 2-pin (X6 and X7) connectors on the
main PCB, shown in Figure 7.

The relay has two setpoint values, the On level and
the Off level. These provide hysteresis and desired
control function. The On level must be higher than the
Off level. When CO

2

 concentration is increasing, the

relay closes at the On level and opens when
concentration is reduced to the Off level.

Note:

The default relay setpoints are 1,000 ppm On
and 950 ppm Off. To change these settings,
use the Relay Setpoint Software ACC-CD-S to
enter new values.

Wiring the Temperature Module

Model CD-WA0-00-0 is shipped with a temperature
module. Observing polarity, connect the temperature
output wires to the screw terminals  and –
(see Figure 10).

Front

Connect to X3

Connect to X7

Screw Terminal

Sensor

Figure 10: Temperature Module (Front View)

Setup and Adjustments

Commissioning

Johnson Controls CO

2

 transmitters come calibrated for

the following:

  output signal (0 to 10V) proportional to

CO

2

 concentration (0 to 2,000 ppm)

  altitude range of 0 to 1,969 ft (0 to 600m) above

sea level without compensation

  default relay output trigger point of 1,000 ppm

Altitude Compensation

The sensors are calibrated for an altitude of 984 ft
(300m) above sea level and are intended for
applications within the range of 0 to 1,969 ft
(0 to 600m) without compensation.

For altitudes above 1,969 ft (600m) where optimum
accuracy of the CO

2

 concentration measurement is

essential, modify the Building Automation System
(BAS) controller’s Analog Input (AI) ranging to
compensate for sensor placement at other than the
standard calibration altitude.

To do this, reset the 2,000 ppm value using the
controller’s Compensation Factor (CF) shown in
Figure 11 or Figure 12, as follows:

Corrected Value = CF x 2,000

For example, if the sensor is situated at an altitude of
3,000 ft (914.4m) above sea level, the CF is 1.10
(see Figure 11 or Figure 12).

The new value is calculated as follows:

Corrected Value = (1.10)(2,000 ppm) = 2,200 ppm

0                     1,000                  2,000                  3,000                   4,000                 5,000                  6,000                  7,000

CF

Altitude (Feet)

0.90

0.95

 1.00

1.05

1.10

1.15

1.20

1.25

1.30

Figure 11: Altitude Compensation in Feet above Sea Level

Summary of Contents for CD-W-00-0 Series

Page 1: ...ications Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his her own expense Canadian C...

Page 2: ...le Base Two No 6 Self Tapping Screws Provided Figure 2 Surface Mounting to Drywall 3 Insert the spring clips as shown in Figure 2 Use the spacers for 3 8 or 1 2 in drywall Note Replacement spring clip...

Page 3: ...es of 18 to 30 VDC or 20 to 30 VAC Although the power input includes a halfwave rectifier to avoid current peaks use a DC supply current consumption peak 170 mA average 85 mA 24 VAC Power Supply Conne...

Page 4: ...do not discard the jumper 5 If the unit has an optional accessory relay relay and display or temperature module follow the procedure described in the applicable wiring section before repositioning th...

Page 5: ...ted for the following output signal 0 to 10V proportional to CO2 concentration 0 to 2 000 ppm altitude range of 0 to 1 969 ft 0 to 600m above sea level without compensation default relay output trigge...

Page 6: ...ng procedure 1 Temporarily turn off power to the unit 2 Temporarily remove wires connected to the relay screw terminal 3 Connect a multimeter to the relay terminals 4 Read the resistance level to dete...

Page 7: ...See Figure 3 Testing the Temperature Module To confirm that the temperature module is operating correctly perform the following procedure 1 Temporarily turn off power to the unit 2 Observing polarity...

Page 8: ...A Maximum Output Voltage 12 5V Relay Contact Ratings Optional 30V 0 5 A Class 2 Analog Temperature Module Optional Linear 0 to 10 VDC for 32 to 122 F 0 to 50 C Resolution of CO2 Output 10 ppm Recommen...

Reviews: