Johnson Controls CD-W-00-0 Series Installation Instructions Manual Download Page 6

6

    CD-Wxx-00-0 Series Wall Mount CO

2

 Transmitter Installation Instructions

CF

0             200           400           600           800          1,000       1,200         1,400        1,600         1,800        2,000        2,200 

Altitude (Meters)

0.90

0.95

1.00

1.05

1.10

1.15

1.20

1.25

1.30

Figure 12: Altitude Compensation in Meters above Sea Level

Troubleshooting

The transmitter is not field-repairable.

If the unit is not functioning properly, use the following
checklist to identify the symptoms and determine a
solution:

1.  Verify that the unit is mounted properly and the

appropriate output jumper is selected.

2.  Verify that all wiring is correct.

3.  Verify that the power supply voltage level is

20 to 30 VAC or 18 to 30 VDC.

Note:

The diagnostic Light-Emitting Diode (LED)
shown at the right-hand corner of Figure 7
indicates operational status:

  V7 lights up if the self-diagnostics procedure

detects an abnormality.

  V10 pulses to indicate that the device is

operational.

If the transmitter will not operate after completing
these steps, replace the unit.

Testing the Relay Module

To confirm that the relay is operating correctly, perform
the following procedure:

1.  Temporarily turn off power to the unit.

2.  Temporarily remove wires connected to the relay

screw terminal.

3.  Connect a multimeter to the relay terminals.

4.  Read the resistance level to determine whether

the contacts are open or closed.

  If the contacts are closed, replace the unit with

the appropriate relay module and restart this
procedure.

  If the contacts are open, apply power to the

transmitter.

5.  Determine whether the contacts are open or

closed.

  If the contacts are closed, the relay is

functioning properly and no further testing is
necessary.

  If the contacts are open, increase the CO

2

concentration by exhaling near the sensor
looking for a change in the resistance value.
(See Figure 3.)

  If no change is noted, confirm that the CO

2

concentration has been raised above the trip
point.

- Check the transmitter output signal with a 

voltmeter to make sure the signal has risen 
above the 1000 ppm relay trip point.

- If the output signal has not reached the trip 

point, it may be necessary to further
increase the CO

2

 concentration.

  If the contacts are open after exceeding the

trip point, replace the unit with the appropriate
module and restart this procedure.

6.  Disconnect power to the transmitter.

7.  Disconnect the multimeter from the relay

terminals.

Summary of Contents for CD-W-00-0 Series

Page 1: ...ications Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his her own expense Canadian C...

Page 2: ...le Base Two No 6 Self Tapping Screws Provided Figure 2 Surface Mounting to Drywall 3 Insert the spring clips as shown in Figure 2 Use the spacers for 3 8 or 1 2 in drywall Note Replacement spring clip...

Page 3: ...es of 18 to 30 VDC or 20 to 30 VAC Although the power input includes a halfwave rectifier to avoid current peaks use a DC supply current consumption peak 170 mA average 85 mA 24 VAC Power Supply Conne...

Page 4: ...do not discard the jumper 5 If the unit has an optional accessory relay relay and display or temperature module follow the procedure described in the applicable wiring section before repositioning th...

Page 5: ...ted for the following output signal 0 to 10V proportional to CO2 concentration 0 to 2 000 ppm altitude range of 0 to 1 969 ft 0 to 600m above sea level without compensation default relay output trigge...

Page 6: ...ng procedure 1 Temporarily turn off power to the unit 2 Temporarily remove wires connected to the relay screw terminal 3 Connect a multimeter to the relay terminals 4 Read the resistance level to dete...

Page 7: ...See Figure 3 Testing the Temperature Module To confirm that the temperature module is operating correctly perform the following procedure 1 Temporarily turn off power to the unit 2 Observing polarity...

Page 8: ...A Maximum Output Voltage 12 5V Relay Contact Ratings Optional 30V 0 5 A Class 2 Analog Temperature Module Optional Linear 0 to 10 VDC for 32 to 122 F 0 to 50 C Resolution of CO2 Output 10 ppm Recommen...

Reviews: