i.   In accordance with NEC, CTs may not be installed in    
 

any panel board where they exceed 75% of the wiring  

 

space of any cross sectional area.

ii.  Do not install a Current Transformer in an area where   
 

it would block ventilation openings.

iii.  Do not install a Current Transformer in area of breaker  
 

arc venting.

iv.  Not suitable for Class 2 wiring methods and not  
 

intended for connection to Class 2 equipment. 

 

Field-installed Class 2, Class 3, and other low voltage    

 

conductors shall be separated by a minimum 1/4 inch   

 

(6.4mm) from factory- or field-installed electric light,   

 

power, Class 1, non-power-limited fire alarm circuit    

 

conductors, and medium power network-powered  

 

 

broadband communications cables. Separation of  

 

 

conductors may be obtained by clamping, routing,  

 

or an equivalent means.

v.  Secure Current Transformers and route conductors so  
 

that they can not directly contact live terminals or  

 

 

current carrying conductors.

The SEM3 series Split Core Current Transformers measure 
rated currents up to 2000 Amps. They may be field installed 
within distribution and control equipment such as panel 
boards, switchboards, industrial control equipment, and 
energy-monitoring / management equipment  to measure 
current on the service entrance or branch circuit conductors.

   

 

 

Specifications  
Ratings: 
  Primary voltage:
 600 VAC 
 

Overvoltage category: CAT IV (service entrance) for 

  pollution degree 3 
 

Line frequency: 50/60Hz 

 

Secondary (output) current: 100mA 

 

Listed to: UL 2808

Environmental: 
  Operating temperature:
 -40°F to 158°F (-40°C to 70°C) 

 

 

Operating humidity: 0 to 95% non-condensing 

 

Pollution degree: 3 for CAT IV, 600 VAC 

 

Indoor use: Suitable for indoor use

Electrical: 
  Accuracy class:
 0.5S 
 

Protection: Shorting of CT is not needed since CT already    

  includes shorting means, voltage limited to 5V+/-2V. 

 

 

Lead wires: 18AWG, Stranded 16/30, 600V, UL style 

  1015, Brown/Yellow twisted pair, 2 turns per inch.

 

Type

Rated primary 
current I

p

 (A)

Rated secondary  
current I

s

 (mA) 

7KT1280-5MA00

  50

100

7KT1280-5MA01

  125

100

7KT1280-5MA02

  250

100

7KT1280-5MA03

  400

100

7KT1280-5MA04

  600

100

7KT1280-5MA05

  800

100

7KT1280-5MA06

1200

100

7KT1280-5MA07

1600

100

7KT1280-5MA08

2000

100