INSTALLATION
INSTALLATION SAFETY INFORMATION:
Read these instructions before continuing this appli-
ance installation. This is an outdoor combination heat-
ing and cooling unit. The installer must assure that
these instructions are made available to the consumer
and with instructions to retain them for future reference.
1.
Install this unit only in a location and position as
specified on page 8 of these instructions.
2.
This equipment is not to be used for temporary
heating of buildings or structures under construc-
tion.
LIMITATIONS
These units must be installed in accordance with the
following national and local safety codes:
In U.S.A.:
•
National Electrical Code ANSI/NFPA No. 70.
In Canada:
•
Current Canadian Electrical Code C22.1.
•
Local plumbing and waste water codes.
•
Other applicable local codes.
Refer to the Unit Application Data table and to the Elec-
tric Heat Application Data table.
If components are to be added to a unit to meet local
codes, they are to be installed at the dealer's and/or
the customer's expense.
Size of unit for proposed installation should be based
on heat loss/heat gain calculation made according to
the methods of the Air Conditioning Contractors of
America (ACCA).
This unit is not to be used for temporary heating of
buildings or structures under construction.
The
Simplicity
® control board used in this product
will effectively operate the cooling system down to
0°F when this product is applied in a comfort cooling
application for people. An economizer is typically
included in this type of application. When applying
this product for process cooling applications (com-
puter rooms, switchgear, etc.), please reference
applications bulletin AE-011-07 or call the applica-
tions department for Unitary Products @ 1-877-
UPG-SERV for guidance. Additional accessories
may be needed for stable operation at temperatures
below 30° F.
TABLE 1: UNIT APPLICATION DATA (BQ)
UNIT MODEL NUMBER
036
048
060
Voltage Variation,
Min. / Max.
1
380 / 415
342 / 456
Supply Air m
3
/s (ft
3
/min.), Nom.
0.57 (1200)
0.76 (1600)
0.94 (2000)
Wet Bulb Temperature of Air on
Evaporator Coil, Min. / Max
14°C / 22°C
57°F / 72°F
Dry Bulb Temperature of Air on
Condenser Coil, Min. / Max.
-18°C / 49°C
0°F / 120°F
1.
Utilization range “A” in accordance with ARI Standard 110.