background image

175619-XIM-C-0109

Johnson Controls Unitary Products

31

ing is still present at the conclusion of the ASCD, the
UCB will re-energize the compressor.

Should a freezestat open three times within two hours
of operation, the UCB will lock-out the compressor and
flash a code (see Table 8).

LOW AMBIENT COOLING

To determine when to operate in low ambient mode,
the UCB has a pair of terminals connected to a temper-
ature-activated switch set at 45ºF. When the low ambi-
ent switch is closed and the thermostat is calling for
cooling, the UCB will operate in the low ambient mode.

Low ambient mode operates the compressors in this
manner: 10 minutes on, 5 minutes off. The indoor
blower is operated throughout the cycle. The 5-minute
off period is necessary to defrost the indoor coil.

Low ambient mode always begins with compressor
operation. Compressor minimum run time may extend
the minutes of compressor operation. The defrost cycle
will begin immediately following the elapse of the mini-
mum run time.

When operating in low ambient mode, the UCB will not
lockout the compressor due to a freezestat trip. How-
ever, a freezestat trip will de-energize the compressor.
If the call for cooling is still present at the end of the
ASCD and the freezestat has closed, the unit will
resume operation.

SAFETY CONTROLS

The unit control board monitors the following inputs for
the cooling system:

1.

A suction line freezestat to protect against low
evaporator temperatures due to a low airflow or a
low return air temperature, (opens at -3°C (26°F)
and resets at 3°C (38°F)).

2.

A high-pressure switch to protect against exces-
sive discharge pressures due to a blocked con-
denser coil or a condenser motor failure, (opens at
2660 kPa gauge (380 psig) and resets at 2068 kPA
gauge (300 psig).

3.

A low-pressure switch to protect against loss of
refrigerant charge, (opens at 48 kPa gauge (7 psig)
and resets at 154 kPa gauge (22 psig).

The above pressure switches are hard-soldered to the
unit. The refrigeration system is monitored and con-
trolled. On any fault, the system will be affected by any
safety/preventive action.

The unit control board monitors the temperature limit
switch of the electric heat.

COMPRESSOR PROTECTION

The compressor also has inherent (internal) protection.
If there is an abnormal temperature rise in a compres-
sor, the protector will open to shut down the compres-
sor. The UCB incorporates features to minimize
compressor wear and damage. An anti-short cycle
delay (ASCD) is utilized to prevent operation of a com-
pressor too soon after its previous run. Additionally, a
minimum run time is imposed any time a compressor is
energized.

The ASCD is initiated on unit start-up and on any com-
pressor reset or lock-out.

FLASH CODES

The UCB will initiate a flash code associated with
errors within the system. Refer to UNIT CONTROL
BOARD FLASH CODES Table 8.

RESET

Remove the call for cooling, by raising thermostat set-
ting higher than the conditioned space temperature.
This resets any pressure or freezestat flash codes.

HEATING SEQUENCE OF OPERATIONS

WITH OR WITHOUT ELECTRIC HEAT

When the thermostat calls for the first stage of heating,
the low voltage control circuit is completed between “R”
and “W1”.  The 24vac signal is passed through the
UCB to the “Y” contact on the Defrost Control (DC)
assuring the reversing valve cannot be energized,
except during defrost.  If the ASCD timer is satisfied the
UCB will energize compressor contactor M1.

If the compressor alone cannot satisfy the heating
requirements, a second stage call from the thermostat
completes the circuit between “R” and “W2”.  This
24vac signal is passed through the UCB to the electric
heat section (if available).  The total available kW of
electric heat will be energized on a call for “W2”.

Summary of Contents for SUNLINE 2000 BQ 036

Page 1: ...ODUCT NOMENCLATURE 6 INSTALLATION 7 OPERATION 29 START UP COOLING 33 TROUBLESHOOTING 33 MAINTENANCE 37 See the following page for a complete Table of Con tents NOTES CAUTIONS AND WARNINGS Installer sh...

Page 2: ...BLOWERS 27 CHECKING SUPPLY AIR FLOW RATE 27 OPERATION 29 SEQUENCE OF OPERATIONS OVERVIEW 29 COOLING SEQUENCE OF OPERATION 29 CONTINUOUS BLOWER 29 INTERMITTENT BLOWER 29 NO OUTDOOR AIR OPTIONS 29 ECONO...

Page 3: ...S Tbl Pg 1 UNIT APPLICATION DATA BQ 7 2 CONTROL WIRE SIZES 12 3 ELECTRIC HEATER SUPPLY AIRFLOW LIMITATIONS 13 4 BQ 4 POINT LOADS WEIGHT DISTRIBUTION KG LBS 17 5 BQ 6 POINT LOADS WEIGHT DISTRIBUTION KG...

Page 4: ...hould install repair main tain or service this equipment Observe all precautions in the literature on labels and tags accompanying the equipment whenever working on air conditioning equipment Be sure...

Page 5: ...ARNING Notes are intended to clarify or make the installation easier Cautions are given to prevent equipment damage Warnings are given to alert installer that personal injury and or equip ment damage...

Page 6: ...ohnson Controller DFS APS Honeywell Controller DFS APS Novar Controller DFS APS Simplicity IntelliComfort Controller Simplicity IntelliComfort Controller w ModLinc 2 Pleated filters BAS Ready Economiz...

Page 7: ...er s and or the customer s expense Size of unit for proposed installation should be based on heat loss heat gain calculation made according to the methods of the Air Conditioning Contractors of Americ...

Page 8: ...the unit Do not remove any packaging until the unit is near the place of installa tion Rig the unit by attaching chain or cable slings to the lifting holes provided in the base rails Spreader bars wh...

Page 9: ...should NOT be sized to match the dimensions of the duct connections on the unit Refer to Figures 7 and 10 for information concerning side and bottom supply and return air duct openings CONDENSATE DRAI...

Page 10: ...l result in frosted coils or safety shutdown Minimum filter area and required sizes are shown in Physical Data Table 8 SERVICE ACCESS The following removable panels provide access to all serviceable c...

Page 11: ...CONTROL TERMINAL BLOCK TERMINALS ON A LIMITED NUMBER OF THERMOSTATS 3 1 2 4 3 1 2 4 Second stage heating not required on single stage heating units Second stage cooling not required on single stage c...

Page 12: ...ment wire must be of the type shown on the wiring diagram and the same mini mum gauge as the replaced wire Electrical line must be sized properly to carry the load Use copper conductors only Each unit...

Page 13: ...e Minimum Position Adjusting screw found on the damper control module fully clockwise and then set the thermostat indoor fan switch to the on position and then off or energize and de energize terminal...

Page 14: ...the signal is below it s setpoint the actuator is allowed to modulate normally in accor dance with the enthalpy and mixed air sensor inputs When the AQ signal exceeds it s setpoint setting and there i...

Page 15: ...175619 XIM C 0109 Johnson Controls Unitary Products 15 FIGURE 4 ENTHALPY SETPOINT ADJUSTMENT...

Page 16: ...IAQ IAQ Min Free Cool T T1 AQ1 AQ SO SO SR SR A B C D TR TR1 24 Vac HOT 24 Vac COM EF EF1 2 3 4 5 1 Exhaust Air Adjustment Screw Exhaust Air LED Damper Min Position Screw Indoor Air Quality Max Adjust...

Page 17: ...TRIBUTION kg Lbs UNIT TOTAL A B C D E F BQ036 252 555 37 82 37 81 36 80 46 102 47 104 48 105 BQ048 270 595 40 88 40 87 39 86 50 110 50 111 51 112 BQ060 281 620 42 92 41 91 41 90 52 114 52 116 53 117 1...

Page 18: ...4200 4500 CONDENSER COILS Rows Deep 1 1 1 Fins Per Inch 25mm 20 20 20 Face Area m2 ft2 1 60 17 1 1 60 17 1 1 60 17 1 COMPRESSOR Qty Per Unit Type Quantity Reciprocating 1 Reciprocating 1 Scroll 1 AIR...

Page 19: ...7 5 10 4 29 5 35 2CE045115462 10 2 14 2 34 2 40 2CE045120462 14 6 20 3 41 9 45 2CE045130462 21 5 29 9 53 9 60 Note 1 HACR Type per NEC Note 2 These electric heaters DO NOT include a fuse box If a fuse...

Page 20: ...S 3 5 TON HEAT PUMP FRONT VIEW FIGURE 8 UNIT WITH ECONOMIZER RAINHOOD 829 325 8 1140 447 8 64 21 2 213 83 8 292 111 2 445 171 2 445 171 2 181 77 8 171 63 4 206 81 8 137 53 8 2089 821 4 165 61 2 mm inc...

Page 21: ...ED OUTDOOR AIR MOTORIZED DAMPER RAINHOOD FIGURE 10 UNIT DIMENSIONS REAR VIEW DETAIL B 454 177 8 184 71 4 699 271 2 485 191 8 1140 447 8 305 12 419 161 2 mm inch 260 101 4 89 31 2 210 81 4 111 43 8 mm...

Page 22: ...FOR DICONNECT SWITCH Shipped attached to the blower housing inside the blower compartment FIELD SUPPLIED DISCONNECT SWITCH LOCATION BLOWER MOTOR ACCESS FILTER ACCESS DOT PLUGS TABLE 14 MINIMUM CLEARAN...

Page 23: ...70 750 1440 725 1410 700 1370 675 1330 650 CFM WATTS CFM WATTS CFM WATTS CFM WATTS HI 1600 765 1540 735 1490 700 1380 670 MED 1450 690 1400 665 1360 650 1270 610 LOW 1290 625 1250 610 1220 600 1130 56...

Page 24: ...800 LOW 1635 810 1610 780 1580 760 1555 740 1540 730 CFM WATTS CFM WATTS CFM WATTS CFM WATTS HI 1840 910 1770 825 1660 825 1530 775 MED 1620 775 1560 740 1480 700 1390 660 LOW 1510 715 1460 690 1400 6...

Page 25: ...1405 1054 1470 1074 1525 1094 1560 1116 1595 1140 1620 1167 1640 2300 1005 1260 1024 1275 1049 1370 1069 1440 1090 1475 1116 1505 1142 1535 2200 980 1160 1002 1170 1022 1190 1044 1250 1066 1350 1090 1...

Page 26: ...15KW 0 04 0 05 0 06 0 07 0 08 0 10 0 12 0 14 0 16 20 30KW 0 06 0 07 0 08 0 09 0 11 0 13 0 15 0 17 0 20 0 06 0 07 0 08 0 09 0 10 0 11 0 12 0 14 0 16 BOTTOM DUCT CONNECTIONS1 ELECTRIC HEATERS1 RESISTAN...

Page 27: ...st be within the limitations shown in the Unit Application Data Table 1 2 Pulleys can be adjusted in half turn increments 3 The tension on the belt should be adjusted as shown in the Belt Adjustment F...

Page 28: ...atly measuring the pressure drop across a wet coil under field conditions would be inaccurate To assure a dry coil the compressors should be deac tivated while the test is being run 4 Knowing the pres...

Page 29: ...the system switch set to either the AUTO or HEAT settings the blower is energized whenever a cooling or heating operation is requested The blower is ener gized after any specified delay associated wit...

Page 30: ...ion provides minimum position but does not provide power exhaust operation MOTORIZED OUTDOOR AIR DAMPERS This system operation is the same as the units with no outdoor air options with one exception W...

Page 31: ...low pressure switch to protect against loss of refrigerant charge opens at 48 kPa gauge 7 psig and resets at 154 kPa gauge 22 psig The above pressure switches are hard soldered to the unit The refrige...

Page 32: ...umper across the test pin terminals on the board Depending on the selected defrost minimum run time of 30 60 or 90 minutes the board will go into defrost in 7 5 15 or 22 5 seconds The DC will remain i...

Page 33: ...essures 2 Measure the temperature drop across the evapora tor coil 3 Measure the system Amperage draw across all legs of 3 phase power wires 4 Measure the condenser fan amp draw SHUT DOWN 1 Set the th...

Page 34: ...room thermostat and the UCB c Loose wiring from the room thermostat to the UCB 9 If 24 volts is present at the room thermostat but not at the UCB check for proper wiring between the thermostat and th...

Page 35: ...4 volts is pres ent at the Y1 OUT terminal check for 24 volts at the Y1 ECON terminal If 24 volts is not present check for loose wiring from the Y1 OUT terminal to the Mate N Lock plug the jumper in t...

Page 36: ...second span the fault history is cleared TEST RESET When this button is pressed and released one time within five seconds any anti short cycle delays ASCD is by passed for one cycle When this button i...

Page 37: ...cation of the motor and bearings can extend the life of components but is optional TABLE 8 UNIT CONTROL BOARD FLASH CODES Flash Code Description On Steady Control Failure Replace Control Heart Beat No...

Page 38: ...otor for ten minutes until excess grease is purged from the cavity Replace the plugs 5 ton units are supplied with blower shaft bearings that do not require maintenance but may be lubricated if desire...

Page 39: ...175619 XIM C 0109 Johnson Controls Unitary Products 39...

Page 40: ...hange without notice Printed in U S A 175619 XIM C 0109 Copyright 2009 by Unitary Products Group All rights reserved Supersedes 175619 YIM B 0507 Johnson Controls Unitary Products 5005 York Drive Norm...

Reviews: