background image

Fig. 2

Worked example of equivalent flue height

5.1.12 Where flue blocks are used, builders should ensure that no obstruction is created during erection. The installer

should ensure that the connection flue does not project beyond the internal wall of the flue blocks and that there
is provision for examination and servicing.

5.1.13

Important:  

Before installing the appliance, carry out a visual check of the flue system as directed in the relevant

section of BS5440 Pt.1, then check the flue performance as follows:-

a.

Close all doors and windows in the room in which the appliance is to be installed.

b.

Introduce some heat into the flue, using a blow torch or other means.

c.

Carry out a flow visualisation check with a smoke pellet at the intended position for the appliance. Ensure
that there is discharge of smoke from the correct terminal only, and no spillage into the room. Smoke
coming out of other than the correct terminal only, or a down draught or ‘no flow’ condition, indicates that
the flue has failed the test, and the appliance shall not be connected until the defect has been found and
rectified, and the test satisfactorily completed.

5.1.14 An approved terminal should always be used; a ridge terminal or ‘GC1’ terminal is specifically recommended. The

latter should be positioned in a free air space where it is not shielded by any structure. A minimum of 1m (3ft)
from any vertical or inclined roof structure must be allowed for.

1.6m

4.6m

H

a

 = 6.2m

STET Terminal

2 x 300 mm lengths

4 x 1000 mm lengths

45

O

 bend

45

O

 bend

2 x 300 mm lengths

300 mm length

Appliance draught
diverter

100 mm dia flue pipe

6

ZZ602/6

13

ZZ602/6

8.6

MULTIFUNCTIONAL CONTROL REMOVAL:

8.6.1

Remove the Burner and Controls Assembly as detailed in 8.2

8.6.2

Disconnect the Thermocouple and adapter at the Multifunctional Control, avoiding damage to the capillary.

8.6.3

Disconnect the Pilot Feed Pipe from the Multifunctional Control.

8.6.4

Disconnect the Multifunctional Control input and output supply feeds.

8.6.5

Refitting or replacement is in reverse order.

8.7

PIEZO UNIT REMOVAL:

8.7.1

Disconnect the 2 x conductors from Piezo unit.

8.7.2

Release the Piezo retaining nut and remove the Piezo unit from its mounting bracket.

8.7.3

Refitting or replacement is in reverse order.

8.8

CONTROL PANEL REMOVAL:

8.8.1

Ensure that the electrical supply to the appliance is isolated.

8.8.2

Release the 2 x securing screws and remove the appliance lower front door.

8.8.3

At the Control Panel terminal block, (and referring to Fig. 6), disconnect the following:

a.

230V connections ‘

L

’, ‘

N

’ and ‘

E

’ to the Air Circulating Fan at terminals ‘

15

’, ‘

16

’ and ‘

17

’.

b.

230V mains ‘

L

’, ‘

N

’ and ‘

E

’ connections from terminals marked 

230V 50 Hz 

L

’ and ‘

N

’, and the earth

stud.

c.

Thermostat connections from connection block terminals ‘

8

’, ‘

9

’ and ‘

11

’.

d.

Multifunctional Control connections from connection block terminals ‘

5

’ (YELLOW) and ‘

7

’ (BLACK).

e.

Fan Delay Control connections from connection block terminals ‘

1

’ (BROWN), ‘

2

’ (BLUE with RED

sleeve) and earth stud (GREEN/YELLOW).

8.8.4

Disconnect the 2 BROWN conductors from the SUMMER AIR CIRCULATION switch.

8.8.5

Whilst supporting the Control Panel, release the 4 securing screws and withdraw the Control Panel from the
appliance, releasing the wiring from cable clamps and grommets as required.

8.8.6

Refitting or replacement is in reverse order.

8.9

AIR CIRCULATING FAN, REMOVAL AND CLEANING:

8.9.1

Ensure that the electrical supply is isolated.

8.9.2

Remove the Control Panel as detailed in para 8.8

8.9.3

Release the securing screw from the upper front flange of the fan skirt, and withdraw the flange.

8.9.4

Release the 2 screws securing the Fan Assembly to the fan chamber floor, and withdraw the Fan Assembly by
sliding it forward, avoiding damage to fan blades.

8.9.5

Remove all dust from impeller and motor, avoiding damage to the fan blades and taking care not to disturb the
balance of the fan..

8.9.6

Refitting or replacement is in reverse order.

8.10

CAPACITOR REMOVAL:

8.10.1 Remove the Air Circulating Fan as detailed in para 8.9.1 to 8.9.4

8.10.2 Release the capacitor from the retaining clip.

8.10.3 Remove the protective cover from the capacitor and disconnect the 2 black conductors from the capacitor

terminals.

8.10.4 Refitment or replacement is in reverse order.

8.11

FAN DELAY CONTROL REMOVAL:

8.11.1 Ensure that the electrical supply is isolated.

8.11.2 Remove the appliance central front door.

8.11.3 Release the 2 x screws securing the Fan Delay Control cover, and withdraw the cover.

8.11.4 Disconnect ‘

LOAD

’ (BLUE), ‘

COMM

’ (BROWN) and 

EARTH

 (GREEN/YELLOW) connections from the Fan

Delay Control.

8.11.5 Release the 2 securing screws and withdraw the Fan Delay Control.

8.11.6 Refitment or replacement is in reverse order.

Summary of Contents for JU117

Page 1: ...e 2003 These instructions are to be left with the User or adjacent to the Gas Meter 1 Fig 1 General Layout Diagram 1 1 JU78 JU117 and JU156 are open flued fan assisted Upflow ducted warm air heaters the outputs of which are as follows JU78 23 0kW 82 8MJ h 78 500Btu h JU117 34 3kW 123 4MJ h 117 000Btu h JU156 45 7kW 164 5MJ h 156 000Btu h THESEAPPLIANCESCONFORMTOBS800 1 2 3 4 5 6 7 8 9 10 11 Johnso...

Page 2: ... 3A T6 3A 2 HEATER COMPARTMENTAND CLEARANCES See BS6230 2 1 When a heater is fitted into a compartment the following minimum clearances must be maintained 2 1 1 12mm 0 5in from rear and a side fitted with a blanking plate allowing extra space if a gas supply pipe enters the appliance from this side 2 1 2 600mm 24 in from a side fitted with a louvre side return panel 2 1 3 230mm 9 in from the front...

Page 3: ...e similarly insulated and in addition wrapped with a sound vapour proof barrier and protected from crushing 4 2 2 The duct system should be carefully designed as given in the guidelines in the British System Design Manual to suit the needs of its specific heating requirements and building layout The type of duct system i e radial extended plenum stepped should be installed using the least number o...

Page 4: ... The procedure is based on calculating the equivalent height of the flue under consideration i e that height of the straight vertical circular flue pipe of specific size which will produce the same flow rate as the flue under consideration The equivalent height is calculated from the formula Ki Ko e He Ha x ____________________ Ki Ko a Ke Ha Sum K where He is the height of the equivalent flue Ha i...

Page 5: ...2 x screws securing the Limit Switch and withdraw the control from the appliance 8 12 8 Refitment or replacement is in reverse order 8 13 HEAT EXCHANGERACCESS 8 13 1 Remove the upper and central front doors 8 13 2 Remove the Burner and Controls assembly as detailed in para 8 2 8 13 3 Release the 4 x securing screws and remove heat exchanger access plate and gasket from the front of the draught div...

Page 6: ... reverse order 8 8 CONTROL PANEL REMOVAL 8 8 1 Ensure that the electrical supply to the appliance is isolated 8 8 2 Release the 2 x securing screws and remove the appliance lower front door 8 8 3 At the Control Panel terminal block and referring to Fig 6 disconnect the following a 230V connections L N and E to the Air Circulating Fan at terminals 15 16 and 17 b 230V mains L N and E connections fro...

Page 7: ... except for very small rooms i e bathrooms etc Outlet faces may require partial blanking in order to achieve this 6 3 3 Set the SUMMER AIR CIRCULATION switch to OFF ZZ602 6 7 ZZ602 6 12 8 2 BURNER AND CONTROLS ASSEMBLY REMOVAL 8 2 1 Ensure that the Gas and Electrical supplies are switched OFF 8 2 2 Remove the appliance central front door 8 2 3 Disconnect the Multifunctional Control and Limit Switc...

Page 8: ...switches and summer air circulation switch and that the time control if fitted must be reset following a power failure 7 2 3 How to extinguish the pilot and main burner at the Multifunctional control and switch off electrical supply to the heater 7 2 4 How to remove clean and re fit the air filter if fitted and at what intervals i e fortnightly or weekly for new premises 7 2 5 How to control the h...

Page 9: ...er Pressure Settings ZZ602 6 10 AIRFLOW cfm Table 5 Fan Performance Curve ZZ602 6 9 1 Start button 2 Off button 3 Burner Pressure adjuster 4 Outlet Pressure test point 5 Pilot Adjuster Fig 4 Multifunctional Control 6 6 EXTINGUISHING OF BURNERS AND TEMPERATURE RISE TEST 6 6 1 At the Multifunctional control press the OFF button and ensure that both the Main and Pilot burners extinguish 6 6 2 Remove ...

Page 10: ...er Pressure Settings ZZ602 6 10 AIRFLOW cfm Table 5 Fan Performance Curve ZZ602 6 9 1 Start button 2 Off button 3 Burner Pressure adjuster 4 Outlet Pressure test point 5 Pilot Adjuster Fig 4 Multifunctional Control 6 6 EXTINGUISHING OF BURNERS AND TEMPERATURE RISE TEST 6 6 1 At the Multifunctional control press the OFF button and ensure that both the Main and Pilot burners extinguish 6 6 2 Remove ...

Page 11: ...switches and summer air circulation switch and that the time control if fitted must be reset following a power failure 7 2 3 How to extinguish the pilot and main burner at the Multifunctional control and switch off electrical supply to the heater 7 2 4 How to remove clean and re fit the air filter if fitted and at what intervals i e fortnightly or weekly for new premises 7 2 5 How to control the h...

Page 12: ... except for very small rooms i e bathrooms etc Outlet faces may require partial blanking in order to achieve this 6 3 3 Set the SUMMER AIR CIRCULATION switch to OFF ZZ602 6 7 ZZ602 6 12 8 2 BURNER AND CONTROLS ASSEMBLY REMOVAL 8 2 1 Ensure that the Gas and Electrical supplies are switched OFF 8 2 2 Remove the appliance central front door 8 2 3 Disconnect the Multifunctional Control and Limit Switc...

Page 13: ... reverse order 8 8 CONTROL PANEL REMOVAL 8 8 1 Ensure that the electrical supply to the appliance is isolated 8 8 2 Release the 2 x securing screws and remove the appliance lower front door 8 8 3 At the Control Panel terminal block and referring to Fig 6 disconnect the following a 230V connections L N and E to the Air Circulating Fan at terminals 15 16 and 17 b 230V mains L N and E connections fro...

Page 14: ...2 x screws securing the Limit Switch and withdraw the control from the appliance 8 12 8 Refitment or replacement is in reverse order 8 13 HEAT EXCHANGERACCESS 8 13 1 Remove the upper and central front doors 8 13 2 Remove the Burner and Controls assembly as detailed in para 8 2 8 13 3 Release the 4 x securing screws and remove heat exchanger access plate and gasket from the front of the draught div...

Page 15: ... The procedure is based on calculating the equivalent height of the flue under consideration i e that height of the straight vertical circular flue pipe of specific size which will produce the same flow rate as the flue under consideration The equivalent height is calculated from the formula Ki Ko e He Ha x ____________________ Ki Ko a Ke Ha Sum K where He is the height of the equivalent flue Ha i...

Page 16: ...e similarly insulated and in addition wrapped with a sound vapour proof barrier and protected from crushing 4 2 2 The duct system should be carefully designed as given in the guidelines in the British System Design Manual to suit the needs of its specific heating requirements and building layout The type of duct system i e radial extended plenum stepped should be installed using the least number o...

Page 17: ... 3A T6 3A 2 HEATER COMPARTMENTAND CLEARANCES See BS6230 2 1 When a heater is fitted into a compartment the following minimum clearances must be maintained 2 1 1 12mm 0 5in from rear and a side fitted with a blanking plate allowing extra space if a gas supply pipe enters the appliance from this side 2 1 2 600mm 24 in from a side fitted with a louvre side return panel 2 1 3 230mm 9 in from the front...

Page 18: ...e 1 1 1 9 397819 BOS02394 Electrode lead 1 1 1 10 U780 0700000 Burner and Controls Assembly 1 U117 0700000 Burner and Controls Assembly 1 U560 0700000 Burner and Controls Assembly 1 11 U780 0752000 Main Burner 2 3 4 12 1000 0703720 Main Injector BRAYCat 33 1250 2 3 4 13 BOS01676 4 Cross Lighting Injector InterAlbion T100 1 1 14 S00461 Heat Exchanger exchange kit 1 S00462 Heat Exchanger exchange ki...

Page 19: ...e 2003 These instructions are to be left with the User or adjacent to the Gas Meter 1 Fig 1 General Layout Diagram 1 1 JU78 JU117 and JU156 are open flued fan assisted Upflow ducted warm air heaters the outputs of which are as follows JU78 23 0kW 82 8MJ h 78 500Btu h JU117 34 3kW 123 4MJ h 117 000Btu h JU156 45 7kW 164 5MJ h 156 000Btu h THESEAPPLIANCESCONFORMTOBS800 1 2 3 4 5 6 7 8 9 10 11 Johnso...

Reviews: