52
stop itself within the set time.
Table 8-8 Description of regular downtime setting
Timed
shutdown
information
Description
Note
T-Value
The inverter will stop automatically in
minutes after reaching this time
( Minutes)
。
8.3.2.2 DSP parameter setting
Used for setting key parameters of solar pump inverter system.
Table 8-9 DESCRIPTION of DSP parameter setting
DSP
Parameter
Setting
Information
Description
Im-Over
Motor overload current protection value, refer to the
water pump motor nameplate to set this parameter, it is
recommended to be the same as 1.2 times the motor
rated current value.
Im-Rate
Motor rated current (this parameter is only valid for
single-phase pump motor parameter detection, and the
setting value is recommended to be 60% of nominal
rated current of load pump).