To set the parameters of the display press the SET key for 2 seconds. Use the SET key to
page through the function blocks. Use the shift (<) key to select the parameter to change.
Change the setting using the arrow keys. Press the SET key to store the new value and move
to the next function block.
Table 1
Parameter Setting Mode
Temperature
Controller
Parameter Set Mode
Function
Block
Parameter
Spec.
Value
Description
Code
Description
EV1
Event 1 set value
50
Value at which event occurs
EV2
Event 2 set value
50
Value at which event occurs
EV3
Event 3 set value
50
Unused
EV4
Event 4 set value
50
Unused
LbA
Control loop break alarm
210
Unused
Ldb
LBA deadband
0.0
Unused
P
Proportional band (heat-side)
32
Set during AT
I
Integral time (heat-side)
105
Set during AT
d
Derivative time (heat-side)
26
Set during AT
rPT
Control response parameter
2
Pc
Proportional band (cool-side)
30
Set during AT
lc
Integral time (cool-side)
240
Set during AT
de
Derivative time (cool-side)
60
Set during AT
db
Overlap/Dead band
0.0
Overlap of hot/cold control
Mr
Manual reset
0.0
Unused
SVrU
Setting change rate limiter (up)
0 (off)
SVrd
Setting change rate limiter (down)
0 (off)
AST
Area soak time
0.00
LnKA
Link area number
0 (off)
Summary of Contents for WHE - 3
Page 2: ......
Page 6: ...vi KI OM 0591 Rev 3 Intentionally blank ...
Page 8: ...viii KI OM 0591 Rev 3 Intentionally blank ...
Page 46: ...38 KI OM 0591 Rev 3 Part Identification Intentionally blank ...
Page 56: ...B 2 KI OM 0591 Rev 3 Intentionally blank ...
Page 61: ...KI OM 0591 Rev 3 C 5 Sheet 2 of 2 ...
Page 62: ...C 6 KI OM 0591 Rev 3 WHE 3 Electrical Schematic 440 V Heater Circuit With Remote ...
Page 63: ...KI OM 0591 Rev 3 C 7 WHE 3 Electrical Schematic With Remote Busbar Manufacturing Detail ...
Page 65: ...KI OM 0591 Rev 3 C 9 Sheet 2 of 2 ...