JetMove 204-480
7.9 Jetter System Bus
Jetter AG
73
7.9
Jetter System Bus
The Jetter system bus is used for connecting the JetMove 204-480 to the PLC and
to other JetMoves or Jetter PLC modules. The system bus input BUS-IN is a 9-pin
SUB-D male connector, while the output BUS-OUT is a 9-pin SUB-D female
connector.
7.9.1
Specifications of the Jetter system bus
cable
Specification of Connectors
BUS-OUT side (X19)
• 9-pin male SUB-D connector
• Metallized housing
BUS-IN side (X18)
• 9-pin female SUB-D connector
• Metallized housing
System bus cable specification
For manufacturing a system bus cable, the following minimum requirements have to
be considered:
System Bus Cable - Technical Data
Function
Description
Core cross-sectional area
1 MBaud:
0.25 to 0.34 mm
2
(AWG 24 to 22)
500 kBaud:
0.34 to 0.50 mm
2
(AWG 22 to 20)
250 kBaud:
0.34 to 0.60 mm
2
(AWG 22 to 19)
125 kBaud:
0.50 to 0.60 mm
2
(AWG 20 to 19)
Cable capacitance
Maximum 60 pF / m
Resistivity
1 MBaud:
Maximum 70
/km
500 kBaud:
Maximum 60
/km
250 kBaud:
Maximum 60
/km
125 kBaud:
Maximum 60
/km
Number of cores
5
Shielding
Complete shielding, no paired shielding
Twisting
Core pairs CL and CH must be twisted.
Material
Copper
Temperature class
60 °C
Ω
Ω
Ω
Ω
Summary of Contents for JM-204-480
Page 1: ...User Manual JM 204 480 Digital Servo Amplifier 60870618 We automate your success...
Page 34: ...4 Physical Dimensions 34 Jetter AG...
Page 42: ...5 Technical Data 42 Jetter AG...
Page 82: ...82 Jetter AG...
Page 86: ...86 Jetter AG...
Page 106: ...13 Safe Standstill Option 106 Jetter AG...
Page 116: ...15 Ordering Information 116 Jetter AG...
Page 117: ...JetMove 204 480 Appendices Jetter AG 117 Appendices...
Page 118: ...Appendices 118 Jetter AG...