Transferring the
configuration file
1.
Establish an FTP connection between PC and JC-365MC.
2.
Choose a user login with administrator or system rights.
Default login information:
User:
admin
; Password:
admin
User:
system
; Password:
system
3.
Open the
System
folder of the JC-365MC.
4.
Copy the
config.ini
file to the
System
folder.
5.
Clear the FTP connection.
6.
Reboot.
Setting the IP address via non-volatile registers
The IP interface is initialized by the settings in the configuration memory during
the boot phase. You can change the following settings via registers. The values
are then stored to the remanent memory:
■
IP address of the controller
■
Subnet mask
■
IP address of the default gateway
■
IP address of DNS server
■
Host name and suffix type
■
Port numbers for JetIP and JetSym debugger
■
Name for AutoCopy command file
Registers -
Overview
Register (range)
Description
101200
IP address
101201
Subnet mask
101202
IP address of the default gateway
101203
IP address of DNS server
101232
Host name suffix type
101233 … 101251
Host name
101264
Port number for JetIP
101265
Port number for STX debugger
101280 … 101298
Name for AutoCopy command file
101299
Saving the settings (0x77566152)
Tab. 43:
Overview over the configuration memory registers
NOTICE
Limitation of the write cycles
The EEPROM data on the backplane module allow for
100,000 write cycles.
►
Read a value first.
►
Compare the value.
►