MAGDOS
BW 1 02 98 / 3
Verbessernde Änderungen jederzeit ohne Vorankündigung vorbehalten.
JESCO DOSIERTECHNIK GmbH & Co. KG
6. Installation example
Fig.1
MAGDOS DE/DX 40 and DE/DX 100 can only be
mounted parallel to the wall.
Fig. 3
Fig. 2
1 M A G D O S
MB 1 02 00
2 Suction line with integrated
level control
MB 1 22 01
3 Hand mixer
MB 1 36 02
4 Chemical tank
MB 1 20 01
5 Leakage probe for monitoring
the diaphragm
MB 1 31 01
6 Relief/safety valve
MB 1 25 01
7 Shutoff valve for isolating the
pump from the plant
MB 1 24 01
8 Back pressure valve for max.
metering accuracy
MB 1 25 01
9 Injection nozzle with non-return
valve
MB 1 23 01
1 0 Venting as separate part or
MB 1 33 02
integrated in the metering head
MB 1 33 03
1 1 Water meter with contact unit
MB 1 37 01
1 2 Pulsation dampener for reducing
pressure peaks and smoothing
the flow
MB 1 27 01
1 3 Separation chamber
is recommended if the media
could damage the pump in the
case of a diaphragm failure
MB 1 28 01
ATTENTION!
Leakage must be discharged
into a collection funnel using
a short inclining drain pipe
(and can then be returned to
the chemical tank).
The outlet of the drain pipe
must be visible in order to
actually see the leakage.
1 4 Priming aid
This equipment allows easy
startup of small pumps in particular.
The entrained gas serves as a
pulsation dampener.
MB 1 33 01
1 5 Water meter spacer
MB 1 37 01
ATTENTION!
The spacer is required to
avoid that the drive solenoid
affects the water meter
contact.
1 6 Wall bracket
MB 1 32 00
1 7 Tall or short adapter for tank
mounting