© JBG-HT (v.2.0)
67
INSTRUCTION MANUAL
– HEAT PUMP
System separation:
Heat exchanger installed ☐ YES ☐ NO If yes:
Type of antifreeze medium in the heat pump circuit: ………………………
Freezing point ……….°C
Heat pump circuit vented ☐ YES*
Heat pump circuit pressure ...... bar
Connecting the buffer in parallel ☐ / in series ☐
Notes:
ELECTRICAL INSTALLATION
All electrical connections of modules and devices were routed according to the diagram ☐ YES*
Electrical wires protected inside the electrical box against pulling out ☐ YES*
Access to the electrical system, circuit breakers and protection is provided ☐ YES*
Protective and grounding wires connected ☐ YES*
Temperature sensors connected according to the instructions ☐ YES*
Control wires and sensors routed at a distance of min. 100mm from power wires ☐ YES*
Correct 3-phase power cable used min. 5x2,5mm2 ☐ 5x4mm2 ☐ */**
The correct overcurrent circuit breakers were used for the units:
- ZHHS-01-10K-R290-V5: 16A C characteristics, 3-phase, 3L+N ☐ YES*
- ZHHS-01-15K-R290-V5: 25A C characteristics, 3-phase, 3L+N ☐ YES*
In both cases for the controller: overcurrent circuit breaker 6A characteristic B, 1-phase, 1L+N ☐ YES*
Differential protection used: ☐ YES*** TYPE .......
In case of option with a heater:
An overcurrent circuit breaker for the heater was used:
16A characteristic B, 3-phase, 3L+N ☐ YES*
Notes:
* - mandatory fields - condition for starting up the device
** - the wire should be selected according to the parameters of the fuse used
*** - it is required to use residual current protection in accordance with applicable standards