60
© JBG-HT (v.2.0)
INSTRUCTION MANUAL
– HEAT PUMP
Code
Description
Type
Result
Modbus
AL096
Circuit 1 - Suction temperature probe alarm
Automatic reset
Disconnect-
ing circuit 1
DI1038
AL097
Circuit 1 - Liquid temperature probe alarm
Automatic reset
Only message
DI1039
AL098
Circuit 1 Envelope - High compression ratio
Automatic reset
Disconnect-
ing circuit 1
DI1040
AL099
Circuit 1 Envelope - High pressure discharge
Automatic reset
to: 3 times
within 3600 s
Disconnect-
ing circuit 1
DI1041
AL100
Circuit 1 Envelope - High motor current
Automatic reset
Disconnect-
ing circuit 1
DI1042
AL101
Circuit 1 Envelope - High suction pressure
Automatic reset
Disconnect-
ing circuit 1
DI1043
AL102
Circuit 1 Envelope - Low compression ratio
Automatic reset
Disconnect-
ing circuit 1
DI1044
AL103
Circuit 1 Envelope - Low differential pressure
Automatic reset
Disconnect-
ing circuit 1
DI1045
AL104
Circuit 1 Envelope - Low discharge pressure
Automatic reset
Disconnect-
ing circuit 1
DI1046
AL105
Circuit 1 Envelope - Low suction pressure
Automatic reset
Disconnect-
ing circuit 1
DI1047
AL106
Circuit 1 Envelope - High
discharge temperature
Automatic reset
Disconnect-
ing circuit 1
DI1048
AL107
Circuit 1 Expansion valve - Low overheating
Automatic reset
to: 3 times
within 3600 s
Disconnect-
ing circuit 1
DI1049
AL108
Circuit 1 Expansion valve - Low
evaporation pressure
Automatic reset
Disconnect-
ing circuit 1
DI1050
AL109
Circuit 1 Expansion valve - High
evaporation pressure
Automatic reset
Disconnect-
ing circuit 1
DI1051
AL110
Circuit 1 Expansion valve - High
condensation temperature
Automatic reset
Disconnect-
ing circuit 1
DI1052
AL111
Circuit 1 Expansion valve - Low
suction temperature
Automatic reset
Disconnect-
ing circuit 1
DI1053
AL112
Circuit 1 Expansion valve - Motor error
User reset
Disconnect-
ing circuit 1
DI1054
AL113
Circuit 1 Expansion valve -
Emergency shutdown
User reset
Disconnect-
ing circuit 1
DI1055
AL114
Circuit 1 Expansion valve - Set out of range
Automatic reset
Disconnect-
ing circuit 1
DI1056
AL115
Circuit 1 Expansion valve - Setup range error
Automatic reset
Message only
DI1057
AL116
Circuit 1 Expansion valve - Offline
Automatic reset
Disconnect-
ing circuit 1
DI1058
AL117
Circuit 1 Expansion valve - Low battery
Automatic reset
Message only
DI1059
AL118
Circuit 1 Expansion valve - EEPROM memory
Automatic reset
Message only
DI1060
AL119
Circuit 1 Expansion valve - Incom-
plete closure of the valve
Automatic reset
Disconnect-
ing circuit 1
DI1061
AL120
Circuit 1 Expansion valve -
firmware incompatible
Automatic reset
Disconnect-
ing circuit 1
DI1062