Ref doc :
330740F/EN
revision 01
29.09.2015
(1)
Reset mode for protection circuits « S11-S14 » and « S21-S24 »
Manual start :
Once the protection circuits connected across S11-S14 and S21-S24 are again active, you must restart the
equipment using the ON button wired on the control panel.
Automatic start :
Once the protection circuits connected across S11-S14 and S21-S24 are again active, the system is automatically
restarted provided the remote control is on its charger.
(2)
Reset after wireless emergency stop
Control panel :
Following an emergency stop using the radio remote control, the equipment must be restarted using the ON button
wired on the control panel.
Wireless :
Following an emergency stop using the radio remote control, the equipment can be restarted using the radio
remote control without returning to the control panel.
Setting transmitter activation time and gate or safety barrier inhibit time
The transmitter activation, protected area access request and gate or safety barrier inhibit times are configurable
by two « A »selectors. The two selectors must always be placed in the same position.
Position of 2 « A » selectors:
Position of
"A" selectors
0
1
2
3
4
5
6
7
8
9
Transmitter
activation or
access request
time
5S
6S
7S
8S
9S
10S
15S
20S
25S
30S
Inhibit time (1)
(muting)
5S
10S
20S
40S
1min
2min
3min
4min
5min
10min
(1) : maximum gate or safety barrier inhibit time.
3.4.2 Definition of receiver indicator lights and diagnostic outputs
The various states and faults of the safety receiver are indicated by 4 leds and by 3 static outputs.
Ind. light state
Off
Flashing
On steady
White ind. light
V1
All outputs inactive
subsequent to a system
fault
Error code : system fault. All
outputs inactive
No system fault
White ind. light
V2
- charger contacts
closed and relays
activated
- all outputs inactive
subsequent to a system
fault
- Flashing as for output 58 if
Led "V1" is on
- system fault if Led "V1" is off
or flashing
Safety outputs
activated
Red ind. light
V3
Not applicable
- Error code:
error in reception module
- Flashing regularly:
reception of incorrect identity
code
Link with RS232
interface
Green ind. light
V4
No radio signal
-Flashing irregularly :
poor reception
- Error code:
error in reception module
Good radio reception
Green ind.
lights K1 and
K2
Safety relays K1 and
K2 inactive
Not applicable
Safety relays K1 and
K2 activated