UMG 96-S2
www.janitza.com
62
18.2 Parameter and Modbus address list
The parameter list (table 1) contains the settings
for the correct operation of the device, such as
e.g. current transformer and device addresses.
The values for the parameter list can be
described and read.
The Modbus address list (table 2) contains
measured and calculated measured values,
condition data for the outputs and logged values
for reading out.
NOTE
·A complete overview of the parameter list and
the Modbus address list with explanations for
the selected measured values can be found
in the document “Modbus address list” in the
download area on our web site.
·The addresses listed in the parameter list (up
to address 800) are configured on the device.
·From address 1000, the addresses are
configured via the Modbus address list
18.3 Table 1 - Parameter list
Address Format RD/
WR
Unit Remark
Setting range Default set-
ting
0
SHORT RD/WR
-
Device address
0..255
(*1)
1
1
SHORT RD/WR kbps Baud rate (0 = 9.6 kbps, 1 = 19.2 kbps,
2 = 38.4 kbps)
0..2
2
2
SHORT RD/WR
-
Stop bits
0 = 1 bit, parity none
1 = 2 bits, parity none
2 = 1 bit, parity even
3 = 1 bit, parity odd
0..3
0
10
FLOAT RD/WR
A
Current transformer I1.. I3, primary
0..1000000
(*2)
5
12
FLOAT RD/WR
A
Current transformer I1.. I3, secondary
1..5
5
14
FLOAT RD/WR
V
Voltage transformer V1..V3, primary
0..1000000
(*2)
400
16
FLOAT RD/WR
V
Voltage transformer V1..V3, secondary
100, 400
400
35
SHORT RD/WR
-
Contrast of the display, 0 (low), 9 (high)
0..9
4
37
SHORT
RD/
WRw
-
Display profile
0 = configured display profile 1
1 = configured display profile 2
2 = configured display profile 3
0..2
0
38
SHORT RD/WR
-
Display change profile
0 = configured display change profile 1
1 = configured display change profile 2
2 = configured display change profile 3
0..2
0
39
SHORT RD/WR
s
Changeover time
0..60
0
40
SHORT RD/WR
-
Averaging time, I
0..8 *
6
41
SHORT RD/WR
-
Averaging time, P
0..8 *
6
42
SHORT RD/WR
-
Averaging time, U
0..8 *
6
43
USHORT RD/WR
mA
Current measurement response threshold
0..200
5
50
SHORT RD/WR
-
Password
0..999
0 (no password)
100
SHORT RD/WR
-
Digital output 1 (pulse output)
0 = P (active energy)
1 = Q (reactive energy)
2 = S (apparent energy)
3 = OFF
0..3
0
102
FLOAT RD/WR imp /
kWh Pulse value, digital output 1
-1000000..
+1000000
1000
106
SHORT RD/WR
ms
Minimum pulse length
10..1000
50
506
SHORT RD/WR
-
Delete min. and max. values
0, 1
0
507
SHORT RD/WR
-
Delete the energy counter
0, 1
0
508
SHORT RD/WR
-
Force EEPROM describing
0, 1
0
911
SERNR
RD
-
Serial number
913
SHORT
RD
-
Software release
914
SERNR
RD
-
Production number
(*1) The values 0 and 248 to 255 are reserved and may not be used.
(*2) The adjustable value “0” does not yield a reasonable operating value and may not be used.
*
0 = 5 sec.; 1 = 10 sec.; 2 = 30 sec.; 3 = 1 min.; 4 = 5 min.; 5 = 8 min.; 6 = 15 min.; 7 = 30 min.; 8 = 60 min.