UMG 96-PA
www.janitza.de
18
6. 1
Voltage measurement
You can use the UMG 96-PA to measure volt-
age in TN and TT systems.
Voltage measurement in the UMG 96-PA is
designed for the overvoltage category 600V
CATIII (measurement surge voltage 6 kV).
In systems without N, the measurement val-
ues that require an N are based on a calcu-
lated N.
c
WARNING!
Risk of injury from electric
voltage!
If voltage transformers are used, the con-
nections on the secondary side may
not
be
short-circuited!
For this reason, please note the follow-
ing:
•
Check that the
voltage transformers have been prop-
erly installed. To do this, read the re-
spective information about the voltage
transformers.
Fig. Principle circuit diagram - Measurement in three-
phase 4-wire systems.
DC
AC/DC
PE
347V/600V 50/60Hz
L2
L3
N
L1
Auxiliary energy
Voltage measurement
4M
4M
4M
4M
V1
V3
V2
V
N
UMG 96-PA
N
L1
240V
50/60Hz