UMG 512
Installation
Position of installation
The UMG 512 is suitable for integration into fixed and
weatherproof switch panels in indoor areas. Conductive
switch panels must be earthed.
Mounting position
To ensure adequate ventilation, the UMG 512 must
be installed vertically. There should be separation
above and below of at least 50mm with 20mm space
to the sides.
Front panel section
Cut-out size:
138
+0.8
x 138
+0.8
mm.
m
Failure to meet the minimum clearances
can destroy the UMG 512 at high ambient
temperatures!
Fig. mounting
position UMG 512
(View from rear)