108
UMG 512
Temperature measurement input
3-wire measurement
Update time
1 second
Connectable sensors
PT100, PT1000, KTY83, KTY84
Total burden ( cable)
max. 4 kOhm
Cable length
up to 30m unshielded, from 30m shielded
Sensor type
Temperature range
Resistor range
Measurement uncertainty
KTY83
-55°C to +175°C
500Ohm to 2.6kOhm
± 1.5% rng
KTY84
-40°C to +300°C
350Ohm to 2.6kOhm
± 1.5% rng
PT100
-99°C to +500°C
60Ohm to 180Ohm
± 1.5% rng
PT1000
-99°C to +500°C
600Ohm to 1.8kOhm
± 1.5% rng
Terminal connection capacity (temperature measurement input)
Connectable conductors. Only one conductor can be connected per terminal!
Single core, multi-core, fine-stranded
0.08 - 1.5mm
2
Terminal pins, core end sheath
1mm
2
Potential separation and electrical safety
-
The thermistor input is double-insulated from the current and voltage measurement inputs as well as the supply voltage.
- There is no insulation from the RCM measurement input.
- There is only a functional insulation from the Ethernet, Profibus and RS485 interfaces and the digital I/Os.
- The external temperature sensor must be double insulated from the system parts that carry voltages that are dangerous to
the touch (per IEC61010-1:2010).